The cable shielding must be connected to ground at both ends of the cable.
Label
RJ45
Profinet Color
Tx+
1
Yellow
Tx-
2
Orange
Rx+
3
White
Rx-
6
Blue
Table 2.1: Ethernet wiring instruction.
Note
Connecting the Reset poles for for 0.5 to 2 seconds during operation will cause the sensor
to temporarily use the default IPV4 address 192.168.111.71 until the system is rebooted.
Connecting the Reset poles for longer than 10 seconds during operation will cause the
sensor to reset to default factory settings and reboot. The indicator LED will flash
rapidly during this procedure. Refer to Appendix 3: LED blinking modes for a
description of the LED blinking modes.
Warning
Improper wiring can damage the radar’s communication board. Always check that power
is applied to the right connector before connecting it!
Warning
Make sure the housing of the device is properly connected to the ground reference! Make
sure the electrical resistance of the ground connection is below the maximum prescribed
by local requirements!
Upon powering the system the status LED will turn on and continue to shine while the
system is starting up. When the startup process is completed and the system is running in
normal mode, the LED will blink twice for half a second after which it will remain off for 4
seconds. Any other blinking mode will warn you that the system is not functioning in its
normal mode of operation. See Appendix 3: LED blinking modes for a description of the
different LED blinking modes.
7