Safe low-voltage 12 V AC output is fuse-protected internally. This appliance is IP54
protected, provided blanking caps are fitted to unused cable holes and the cover seal
is fitted correctly.
All AC cable used on the installation must be HAR approved (0.75 mm).
The PCB has four connections to enable auxiliary items to be used in conjunction
with the pulse system (e.g.pump, fan, lights and disinfection).
The connection of these auxiliaries must be through a 12V relay with a maximum coil
resistance of 160 ohms.
Maximum cable runs for solenoid connection are as follows:
Cable Lengths
Metres
Sq mm
2.00
1.00
0.75
0.50
104
53
40
27
1.
Use the installation template (supplied) to mark the positions of the fixing holes
for the control box.
2.
Drill and plug the fixing holes.
3.
Remove the cover from the control box.
4.
Hold the control box in position and secure with the fixing screws (supplied).
Note!
On some wall surfaces or structures alternative fixings may be required
(not supplied).
Programming of all outlets is via the hand held programmer.
WARNING!
Under normal operating conditions the input water temperature to the unit
SHALL be regulated to less than 55
O
C
During the disinfection process high water temperatures can be discharged
from the shower heads or taps. During this process suitable safety
precautions SHALL be taken to ensure that persons are not exposed to the
risk of scalding.