FAULT DIAGNOSIS
Symptom
Cause/Rectification
1.
All outlets do not
operate
(e.g. washbasin,
shower, urinal,
W.C).
a.
Check power to Pulse control box (power light illuminated
on PCB).
b.
If there is power to the control box, check fuse in
transformer.
2.
Individual outlets
do not operate.
3
. Outlets continue
running or run for
e x c e s s i v e
periods
a.
Plug in hand held programmer and check timing for
outlet. Reprogram if necessary.
b.
Check solenoid valve. Maintain or replace parts if
required.
4.
Outlets only run
for a short period
of time.
a.
Check output fuse on PCB. Replace as necessary.
b.
Plug in hand held controller and check that non operating
outlet is set up correctly.
c.
Plug in hand held controller and complete a system info
'error' check. This will identify if the sensor or solenoid
is incorrectly installed or faulty. Replace parts or products
as required.
d.
Check solenoid. Replace if necessary.
a.
Plug in hand held programmer and check timing for
outlet. Reprogram if necessary.