Before you get started.
Before any pipe is cut, make sure your system meets
the installation requirements:
Installation site must be within 300 feet of an
installed Rachio 3 Smart Sprinkler Controller.
Backflow preventer and installation area must
be above ground (recommended).
Below ground installation requires additional steps
not included in this manual. For more information,
visit
rachio.com/flow-underground
.
The Flow Meter is not rated for potable water and
must be installed after the backflow preventer.
System must have ¾ inch or 1 inch pipe made
of either copper, PVC, PEX, or SDR9 poly.
For 1 inch PVC pipe, 1 inch copper or poly pipe,
and ¾ inch PVC pipe, you will need 14 inches of
straight pipe between the backflow preventer and
valve box.
For ¾ inch copper or poly pipe, you will need
16 inches of straight pipe between the backflow
preventer and valve box.
If you have more than one Rachio 3 controller
or more than one backflow preventer, visit
rachio.com/flow-advanced
.
Содержание Wireless Flow Meter
Страница 1: ...WIRELESS FLOW METER Let s get started ...
Страница 2: ...2 What s in the box Wireless Flow Meter Battery Cover 4 Screws 2 AA Batteries ...
Страница 11: ...11 ...
Страница 13: ...13 For copper or poly pipe For PVC or PEX pipe in Page 14 Page 18 Page 18 Page 16 in 1 in 1 in ...
Страница 15: ...15 6 16 Backflow Preventer 8 5 Valve Box Bottom fitting can be buried up to 2 inches if needed ...
Страница 17: ...17 6 14 Backflow Preventer 6 25 Valve Box Bottom fitting can be buried up to 1 inch if needed ...
Страница 19: ...19 6 14 Backflow Preventer 6 5 Valve Box Bottom fitting can be buried up to 1 inch if needed ...
Страница 21: ...21 Backflow Preventer Valve Box ...
Страница 23: ...23 Backflow Preventer Valve Box ...