manualshive.com logo in svg
background image

 

3

High- 
pressure 
water 

Attention 

Nozzle, discharge port 

(1) Never direct the nozzle to any people, which may cause injury. 

(2) Never peep into the discharge port or nozzle during preparation 

for water discharge. 

(3) Set the engine at low speed when opening or closing the 

discharge valve. 

(4) Never start the engine while the discharge valve is still open. 

Electric 
shock 

Warning Ignition 

plug

 

High-pressure cord 

Battery 

(1) Never touch during operation. 

 

(2) When replacing the battery, remove (-) terminal side first, and 

attach (+) side first. 

Injury  
(cut, etc) 

Attention 

Carrying handle 
discharge valve (ball cock) 

(1) Do not touch hinge parts when you operate handle. 

(2) Never place the hand or the finger in the discharge port during 

operation of the discharge valve. 

Scattering 
of stones 
and 
explosion,  
etc. 

Attention   

(1) Pay full attention to stones or other foreign matters which may 

cause physical risk during water discharge. 

(2) Never suck or discharge inflammable or chemicals, which may 

cause fire or explosion. 

Disposal Attention 

 

(1) When disposing of a battery or resin, contact a special agent. 

Slip Attention 

 

(1) Be careful not to spill oil. 

Be sure to wipe up spilt oil. 

 

 

  CONVERSION TABLE OF UNITS

 

Designation Conventional 

New 

Rotation speed 

Pressure 

Mass 

Volume 

Consumption 

Vacuum 

Displacement 

Output 

Number of rotation    rpm 

kgf/cm

2

 

Weight   kgf 

cc/min 

mmHg 

cc 

PS 

Rotating speed 

MPa 

Mass  kg 

ml/min 

-MPa 

ml 

kW 

rpm 

Megapascal 

Kilogram 

Liter 

Milliliter per minute 

Megapascal 

Milliliter 

Kilowatt 

 

1kgf/cm

2   

   

≒   

0.098MPa     

 

Pay attention to the unit of pressure in which new unit is about 1/10 as 
compared with the existing one. 

760mmHg 

 

≒   

-0.1013MPa 

1PS             

≒   

0.735kW 

1cc               

=   

1ml

Содержание P455SM

Страница 1: ...PORTABLE FIRE FIGHTING PUMP P455 P476 P555 P572S INSTRUCTION MANUAL WARNING BE SURE TO READ THIS MANUAL BEFORE OPERATION S M S M S M...

Страница 2: ......

Страница 3: ...ion and maintenance of the pump please contact the maintenance shops or special dealers who have been qualified for maintenance of the portable fire fighting pumps This instruction manual is intended...

Страница 4: ...get fire 1 Perform operation at a place 3 m or more off any inflammables 2 Never perform operation on dry grass If it is inevitable remove dry grass under the muffler 3 When you take off battery cap...

Страница 5: ...n of the discharge valve Scattering of stones and explosion etc Attention 1 Pay full attention to stones or other foreign matters which may cause physical risk during water discharge 2 Never suck or d...

Страница 6: ...ge turbine pump Suction port dia mm Nominal 75 fire fighting screw type fitting JIS B 9912 Discharge port dia mm Nominal 65 fire fighting screw type fitting JIS B 9912 Rated pressure MPa kg cm2 0 55 5...

Страница 7: ...ge turbine pump Suction port dia mm Nominal 75 fire fighting screw type fitting JIS B 9912 Discharge port dia mm Nominal 65 fire fighting screw type fitting JIS B 9912 Rated pressure MPa kg cm2 0 55 5...

Страница 8: ...e turbine pump Suction port dia mm Nominal 75 fire fighting screw type fitting JIS B 9912 Discharge port dia mm Nominal 65 fire fighting screw type fitting JIS B 9912 Rated pressure MPa kg cm2 0 70 7...

Страница 9: ...stage turbine pump Suction port dia mm Nominal 75 fire fighting screw type fitting JIS B 9912 Discharge port dia mm Nominal 65 fire fighting screw type fitting JIS B 9912 Rated pressure MPa kg cm2 0...

Страница 10: ...terminal Detach the liquid port plug nearest to the terminal of the battery and mount the battery liquid level sensor Exhaust Manifold Cylinder Drain Cock Ignition Plug Cover Vacuum Pump Air Exhaust...

Страница 11: ...When carrying the pump be sure to hold it correctly with the carrying handle 3 Set the pump as near as possible to a water suction level so as to minimize suction height Place the pump as level as pos...

Страница 12: ...full 4 Never start and stop the engine repeatedly without water suction Fuel mixture remaining unburnt may cause explosion after fire 2 Water discharge 1 After engine startup set the water suction le...

Страница 13: ...t the water feeding pressure of the master pump so that the compound pressure gauge of the slave pump in operation will read 0 05 to 0 1 MPa max 0 6 MPa The slave pump will not run if the compound pre...

Страница 14: ...erflow bottle Refer to the photo of the next page for overflow bottle 5 Attach the suction port cap and cover the pump before storage Notes 1 Incomplete water drain may cause damage due to freezing or...

Страница 15: ...s drained completely release your hand from the knob 4 Dispose of drained fuel in the bottle Wipe out spilt fuel if any with waste cloth Enough care should be taken of disposal of the waste cloth 5 Re...

Страница 16: ...e battery discharges much Be sure to check the battery level PUMP 1 Water Suction Port Strainer After the pump is operated for water containing alga clear the alga of the water suction strainer 2 Vacu...

Страница 17: ...ock opens LED goes on Close drain cock except in drain ON LED goes on if cooling water pressure is low Insufficient engine cooling water may cause over heating Increase water pressure by setting throt...

Страница 18: ...electricity 4 Check the electrolyte level from time to time Put distilled water into the battery up to the maximum liquid level if the electrolyte level is below the level 3 Battery Charging 1 Clean...

Страница 19: ...e pressure does not become negative confirm that the suction port cap drain cock etc are tightly closed and repeat the procedure mentioned before 3 Cover the cooling water discharge port with your pal...

Страница 20: ...h a new one Electric system Others Set the main switch to RUN and confirm that LED of Rabbit monitor battery voltage display goes on If it is on charge the battery only in S specification Difficult st...

Страница 21: ...elt Confirm that the water suction pipe is regularly tightened and that the water suction portion is regularly placed in water If not tighten the water suction pipe regularly and immerse the water suc...

Страница 22: ...AGRAM S WIRING DIAGRAM Notes 1 This pump is equipped the fuse but pay attention to correct connection with and terminals of battery 2 In connection with the battery start with In disconnection start w...

Страница 23: ...21 M WIRING DIAGRAM...

Страница 24: ...L82900940 1 2013 03 50K...

Отзывы: