INSTRUCTIONS
X17™
XFU 3-WAY FIELD ADJUSTABLE FLOODLIGHT
SELECTABLE PHOTOCELL INSTALLATION
RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install
and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
FIELD ADJUSTMENT
Follow instructions below to change fixture
Power
(W) or
Color
Temperature
(CCT) from the factory settings and
Photocell
On/Off
option.
Factory Settings: 4000K and 60W
1. Remove
Selector Switch Caps
by turning counterclockwise
using a flat head screwdriver
(Fig. 7).
2. Locate the
Selector Switches
on the fixture
(Fig. 8).
3. Select
Power
(W) and
Color Temperature
(CCT) by sliding the
respective switch to the desired value.
4. Select
Photocell
On/Off option by by sliding respective switch
to the desired value.
POWER (W) Selector Switch
Photocell Selector Switch
CCT Selector Switch
0-10V DIMMABLE WIRING
Universal voltage driver permits operation at 120V thru 277V, 50 or
60 Hz. For 0-10 Dimming, follow the wiring directions as in
Fig. 9.
1. Connect the Black/Brown fixture lead to the LINE supply lead.
2. Connect the White/Blue fixture lead to the COMMON supply
lead.
3. Connect the Green/Yellow wire from fixture to supply ground.
Do NOT connect the GROUND of the dimming fixture to
the output.
4. Connect the purple fixture lead to the DIM V+ lead.
5. Connect the gray fixture lead to the DIM V- lead.
6. Cap the yellow fixture lead, if present. Do NOT connect.
CLEANING & MAINTENANCE
CAUTION: Be sure fixture temperature is cool enough to touch.
Do not clean or maintain while fixture is energized.
1. Clean
glass lens
with non-abrasive glass cleaning solution.
2. Do not open the fixture to clean the LED. Do not touch the LED.
TROUBLESHOOTING
1. Is the fixture grounded properly?
2. It is recommended that gloves be worn to avoid injury
during installation.
3. If any smoke or spark, please turn off the power immediately.
X17 XFU 80-60-40 IN-0921
Easy Answers
rablighting.com
Visit our website for product info
Tech Help Line
Call our experts: 888 722-1000
Answered promptly - [email protected]
Free Lighting Layouts
Answered online or by request
© 2021 RAB LIGHTING Inc.
Note:
These instructions do not cover all details or variations in equipment nor do they provide for every possible situation during installation, operation or maintenance.
73710-RAB
Selector Switch Caps
BROWN/BLACK
LINE
WHITE/BLUE
COMMON
PURPLE
(+) DIM V+
GRAY
GREEN/YELLOW
(-) DIM V-
GROUND
Fig: 7
Fig: 8
Fig: 9
TRUNNION MOUNT CONT.
To adjust the angle of the fixture using the Trunnion (Fig. 6).
1. Loosen the
Pivot Bolts
and
Angle Locking Screws
.
2. Make appropriate wire connections per NEC in a approved
enclosure
(not included)
see
Fig 9.
3. Adjust
Fixture
to desired angle
(Fig. 6)
.
4. Tighten
Pivot Bolts
and
Angle Locking Screws
.