ECOMBO34 RED/GREEN EXIT/EMERGENCY LIGHT
Ceiling Mount Installation
Easy Answers
EXNY3-IN-0323
Cranbury, New Jersey 08512 USA
1. De-energize the circuit at the junction box where the exit sign is to be installed.
2. Remove the exit sign stencil and set aside.
3. Remove the canopy kit, hardware pack, mounting plate and LED lamp heads
from inside the EXIT and set aside.
4. Remove the mounting hole plug on the top of the frame.
5. Place the canopy nose through the mounting hole until the side of the frame
touches the canopy. Lock the frame onto the canopy by sliding the frame in a
direction parallel to the canopy length toward the narrow end of the mounting
hole. Slide the frame until both snaps engage the canopy nose preventing any
motion back out of the hole.
6. Feed the red, black and white wires through center of mounting canopy hole.
7. Ensure blue and yellow lamp head wires are routed through side lamp head
mounting holes
(Fig 1).
Attach first lamp head to housing by aligning tabs on
lamp head assembly to lamp head mounting slots on frame of housing
(Fig 2)
.
Gently push lamp head down toward bottom of housing to lock into place. An
audible click should be heard. Repeat to install the second lamp head.
8. Route lamp head wires through proper wire channels and connect to the exit
sign lamp board.
9. Reference Wiring Diagrams section and make proper electrical connections at
the junction box in the metal housing.
10. Secure the EXIT canopy to the steel mounting plate using the screws
provided and fasten to junction box.
11. Connect battery only after continuous AC power can be provided to the unit.
12. Remove proper Chevron(s) on the Exit face plate as required.
13. Secure face plate(s) to housing.
NOTE: Unused input lead must be properly insulated with wire nut or other
approved method.
WIRING DIAGRAMS
1. Remove the faceplate(s) from the unit’s housing.
2. Gently pop out the red diffuser lens from the faceplate(s). Replace the green
diffuser lens onto the faceplate(s).
3. Toggle the dip switch from R to G on the RED/GREEN switchable LED board.
4. Replace the faceplate(s) on the housing to finish installation.
RED-to-Green Conversion
1. Remove the faceplate from the unit’s housing.
2. Remove the backplate by pushing out the two locking clips on the inside of
the unit’s housing.
3. Attach the two EXIT faceplates to the housing to complete the conversion.
Single-to-Double Face Conversion
1. Apply AC power to the unit. The LED indicator will be RED.
2. After the battery has been left to charge for 24 hours, test the unit by pushing
the switch. The LED indicator turns OFF, the LED board stays ON and the
lampheads should turn ON at this time.
3. When the switch is released, the LED indicator turns back to RED, the LED
board stays ON and the lampheads should turn OFF at this time.
OPERATION
Caution: Always turn off AC power to the equipment before servicing. Servicing
should be performed only by a qualfied service technician. Use only
MANUFACTURER supplied replacement parts.
MAINTENANCE
Fig: 3
2023
BLUE(-)
)
LAMP
To Remote lamp
DIP SWITCH
RED/GREEN
switchable LED board
STANDARD
REMOTE CAPABLE
RED
BLACK
RED
BLACK
BLUE(-)
)
LAMP
POWER
LAMP
GREEN
RED
DIP SWITCH
GREEN
RED
RED 277VAC
BLACK 120VAC
WHITE COMM
RED 277VAC
BLACK 120VAC
WHITE COMM
)
BLUE(-)
BATTERY
POWER
RED
BLACK
LAMP
)
BLUE(-)
)
BLUE(-)
RED
BLACK
BATTERY
RED/GREEN
switchable LED board
BATTERY:
The battery supplied with the Battery Backup model requires no
maintenance. However, it should be tested periodically and replaced when it no
longer operates the connected fixtures for the duration of a 30-second or
90-minute test. The battery supplied in this equipment has a life expectancy of
5 years when used in a normal ambient temperature of 72°F.
1. De-energize the circuit at the junction box where the exit sign is to be installed.
2. Remove the exit sign stencil and set aside.
3. Remove the canopy kit, hardware pack, mounting plate and LED lamp heads
from inside the EXIT and set aside.
4. Remove the mounting hole plug on the right side of the frame.
5. Place the canopy nose through the mounting hole until the side of the frame
touches the canopy. Lock the frame onto the canopy by sliding the frame in a
direction parallel to the canopy length toward the narrow end of the mounting
hole. Slide the frame until both snaps engage the canopy nose preventing any
motion back out of the hole.
6. Feed the red, black and white wires through the center of mounting
canopy hole.
7. For single face, left side end mount, remove and switch back plate and face
plate before installing the side mounted LED lamp head.
8. Ensure blue and yellow lamp head wires are routed through side lamp head
mounting holes
(Fig 1).
Attach lamp head to housing by aligning tabs on
lamp head assembly to lamp head mounting slots on frame of housing
(Fig 2)
.
Gently push lamp head down toward bottom of housing to lock into place. An
audible click should be heard.
9. Route lamp head wires through proper wire channels and connect to the exit
sign lamp board.
10. Reference Wiring Diagrams section and make proper electrical connections at
the junction box in the metal housing.
11. Secure the EXIT canopy to the steel mounting plate using the screws
provided and fasten to junction box.
12. Connect battery only after continuous AC power can be provided to the unit.
13. Remove proper Chevron(s) on the Exit face plate as required.
14. Secure face plate(s) to housing.
End Mount Installation
(with one lamp head)