5

into existing plumbing (1” for 12 & 24 gpm models). Install “normally-closed” solenoid valve within three (3) feet of 
disinfection system. Remove the screws on the left and right side of the front aluminum panel allowing this panel to
swing open. Remove the circuit board cover plate to expose the circuit board. Remove the round, black plastic cap 
covering the access hole for the solenoid wire (cap located on back panel next to main power cord). Slide the solenoid
power cord (part# CS-MOL) through the hole and affix the connector to the exposed contacts on the circuit board
marked “SOLENOID”. The connector will only slide onto the mating pins in one direction. Attach the ground wire
(green or green/yellow) to the ground lug on the disinfection system to finish the wiring connections.

To complete the installation, push the strain relief into the hole on the backside of the unit. The strain relief allows for
the wire to run through its centre and can easily be installed using pliers. Once all the parts are connected, reattach the 
circuit board cover plate and secure the front panel of the disinfection system. Plug the disinfection system into the 
electrical outlet to return it to service. Please remember that the unit must have power in order to allow any water to
pass through the unit. If an outside tap is required at all times, including when there may be no power, plumb that line
prior to the solenoid and remember that this line will not be protected from microbiological contaminants. The solenoid
valve will only open when the UV sensor detects adequate UV intensity within the reactor chamber.

Note:

If a normally closed solenoid valve is purchased from another source, the use of the manufacturers solenoid cord

is strongly recommended as it comes with the necessary connectors to mate with the circuit board. This cord can be 
purchased from a dealer under the part number 

CS-MOL

.

INFRARED OUTPUT - REMOTE ALARM  (Standard on S12Q-GOLD & S24Q-GOLD models)

The electronics incorporated in the monitored units incorporate a micro controller, which operates an infrared (IR) 
output. This IR output can be used for diagnostic purposes as well as acting as an interface for an optional remote 
audible/visual alarm package available from your dealer. This IR-ALARM comes with the IR interface and 15.24 meters
(50’) of cable for remote monitoring of the audible and visual signals provided by the UV monitoring mechanism.

THIS ADVANCED WARNING SYSTEM HAS BEEN INSTALLED TO PROVIDE YOU WITH THE     
OPTIMUM PRECAUTIONS TO ENSURE HIGH EFFICIENCY IN THE PROTECTION AGAINST 
MICROBIOLOGICAL CONTAMINATION IN YOUR WATER.  DO NOT DISREGARD THE    
WARNING LIGHTS.

THE BEST WAY TO CHECK UV OPERATION IS TO HAVE THE WATER TESTED FOR 
BACTERIA BY A RECOGNIZED TESTING AGENCY ON A REGULAR BASIS.

Manufacturer warrants the ultraviolet disinfection system’s hardware and electrical systems to be free from defects in 
material and workmanship for a period of

five (5)

years from the date of purchase by the original owner (consumer) on a

pro-rated basis. Manufacturer warrants the ultraviolet lamps and sensor probes to be free from defects in material and
workmanship for a period of 

one (1)

year and the reactor chamber for a period of 

seven (7)

years. The warrantor will at

its option and expense, either repair or replace such units subject to the following conditions, exceptions, and 
exclusions.  

CONDITIONS, EXCEPTIONS, AND EXCLUSIONS

The foregoing limited Warranty is subject to the following terms and conditions:

1.

Water passed through the unit must fall within the following parameters:

a)  Iron: < 0.3 ppm (0.3 mg/L)
b)  Hardness*: < 7 gpg (120 mg/L)
c)  Turbidity: < 1 NTU
d)  Manganese: < 0.05 ppm (0.05 mg/L)
e)  Tannins: < 0.1 ppm (0.3 mg/L)
f)  UV Transmittance: > 75% (call factory for recommendations on applications where UVT < 75%)

* Where total hardness is less than 7 gpg, the UV unit should operate efficiently provided the quartz sleeve and/or 

sensor probe is cleaned periodically.  If total hardness is over 7 gpg, the water should be softened

Warranty will be void, if the proper steps are not taken to ensure that these impurities are not present.

2.  

This limited Warranty shall not apply to any unit which has been repaired or altered by anyone other than the  

Warrantor or by a person authorized by the Warrantor, nor to any units which have been subject to misuse, neglect, 
or accident.

3.

This limited Warranty runs exclusively to the original Consumer and with respect to the original installation only.

4.  WARRANTOR SHALL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.

5.  

This limited Warranty excludes the cost of labour in removing any defective unit or installing any replacement unit.  

This limited Warranty applies only to a unit when returned to the Warrantor at the owner’s expense and in 
accordance with shipping instructions received from the Warrantor.

W

ARRANTY

:

Содержание Sterilight S12Q

Страница 1: ...er s Manual P N 520022 October 2004 425 Clair Road West P O Box 1719 Guelph ON N1H 7X4 Canada t 519 763 1032 f 519 763 5069 t f 1 800 265 7246 e water r can com i www r can com S12Q S12Q GOLD S24Q S24...

Страница 2: ...Chemistry Page 2 Installing Your Disinfection System Page 2 Operating Maintenance Instructions Page 3 4 Warning Systems Page 4 5 Warranty Page 5 Troubleshooting Page 6 8 Parts Page 9 Specifications P...

Страница 3: ...temperatures below freezing Do not store this disinfection system where it will be exposed to the weather Do not store this disinfection system where it will be exposed to temperatures below freezing...

Страница 4: ...nnections are made slowly turn on the water supply and check for leaks The most likely cause for leaks is from the o ring seal In case of a leak shut water off drain cell remove the retainer nut wipe...

Страница 5: ...The connector is keyed and will only allow correct installation in one position Ensure the connector is fully seated onto the UV lamp 3 Once the lamp is fully seated on the connector slide the connect...

Страница 6: ...tection by constantly sensing the UV INTENSITY at the inside surface of the cell The system features a single LED indicator light which will show three distinct colours GREEN YELLOW and RED When the U...

Страница 7: ...cable for remote monitoring of the audible and visual signals provided by the UV monitoring mechanism THIS ADVANCED WARNING SYSTEM HAS BEEN INSTALLED TO PROVIDE YOU WITH THE OPTIMUM PRECAUTIONS TO EN...

Страница 8: ...the disinfection system it is imperative that the effluent water stream be shocked with chlorine after the water leaves the disinfection system the disinfection system must have a bacteria free distr...

Страница 9: ...ALARM UV LAMP ON ON OFF ON Correct operating conditions unit is functioning properly OFF OFF OFF OFF The unit is not plugged into the electrical outlet Plug unit into receptacle and ensure proper powe...

Страница 10: ...acturer replacement Always Wet Sensor Lens prior to inserting sensor check water quality see page 2 for water parameters RED ON ON UV Sensor has not detected enough UV Intensity to adequately protect...

Страница 11: ...IRCUIT BOARD for 115V unit CB 2440A 2 CIRCUIT BOARD for 230V unit RN 001 ALUMINUM RETAINING NUT CP 1240 CIRCUIT BOARD COVER CS 001 Q CORD SET 115V CS EU Q EUROPEAN SCHUKO CORD SET 230V DP750 RETAINING...

Страница 12: ...ER CONSUMPTION 42 W 42 W 95 W 95 W 190 W TOTAL LAMP WATTS 39 W 39 W 78 W 78 W 156 W MAXIMUM OPERATING PRESSURE 8 62 bar 125 psi 8 62 bar 125 psi 8 62 bar 125 psi 8 62 bar 125 psi 8 62 bar 125 psi AMBI...

Страница 13: ...N 520022 octobre 2004 425 chemin Clair ouest C P 1719 Guelph ON N1H 7X4 Canada t l 519 763 1032 s f 1 800 265 7246 t l c 519 763 5069 courriel water r can com site Internet www r can com EPA 57987 CN...

Страница 14: ...miques de l eau Page 2 L installation de votre syst me de d sinfection Page 2 Directives d utilisation et d entretien Page 3 4 Syst mes d advertissement Page 4 5 Garantie Page 5 Diagnostic Page 6 8 Co...

Страница 15: ...toujours l alimentation d eau d un syst me de d sinfection et sa prise lectrique avant de commencer son nettoyage ou son entretien Ne tirez jamais sur le cordon pour le d brancher de la prise murale...

Страница 16: ...ntenue dans le compartiment se r chauffe s il n y a pas d coulement Pour rem dier cette situation laisser couler pendant une minute un robinet d eau froide de la maison Vous vacuerez ainsi l eau chaud...

Страница 17: ...est bien cal sur la lampe UV 3 D s que la lampe est bien fix e au connecteur glissez le sur l crou de retenue en aluminium Assurez vous que la bague m tallique de retenue du connecteur n emp che pas c...

Страница 18: ...OUR VOUS PROCURER UNE PROTECTION OPTIMALE CONTRE LA CONTAMINATION MICROBIOLOGIQUE DE VOTRE EAU NE N GLIGEZ PAS LES AVERTISSEMENTS LUMINEUX LA MEILLEURE FA ON DE V RIFIER LE BON FONCTIONNEMENT DE VOTRE...

Страница 19: ...otre d taillant Cette vanne sol no de qui est normalement ferm fonctionne en parall le avec le syst me de contr le UV pour arr ter l coulement de l eau si le capteur UV d tecte qu elle n est pas trait...

Страница 20: ...d utilisation de cet appareil Contamination apr s le syst me de d sinfection Il est imp ratif que l eau effluente re oive un traitement de choc au chlore apr s que l eau quitte le syst me de d sinfec...

Страница 21: ...M E TEINTE ALLUM E Conditions de fonctionnement correctes l appareil fonctionne correctement TEINTE TEINTE TEINTE TEINTE L indicateur est DEL a br l ou le fil d amen e est cass Remplacez la DEL L appa...

Страница 22: ...llez toujours la lentille du d tecteur avant de l ins rer V rifier la qualit de l eau voir les param tres la page 2 ROUGE ALLUM E ALLUM E Le d tecteur UV n a pas d tect une intensit UV suffisante pour...

Страница 23: ...V UNIT CB 2440A 2 CARTE DE CIRCUIT FOR 230V UNIT RN 001 CROU DE RETENUE CP 1240 COUVERCLE DE LA CARTE DE CIRCUIT CS 001 Q CORDON D ALIMENTATION 120V CS EU Q CORDON D ALIMENTATION EUROP EN 230V DP750 B...

Страница 24: ...SSANCE DE LA LAMPE 39 W 39 W 78 W 78 W 156 W PRESSION MAXIMUM D OP RATION 8 62 bar 12 lb po2 8 62 bar 125 psi 8 62 bar 125 psi 8 62 bar 125 psi 8 62 bar 125 psi TEMP RATURE AMBIANTE 2 40 C 36 104 F 2...

Отзывы: