Cod. 2200780133 00 - Edition 10/2014 - 15
PART “B”
T
HIS PART “B” OF THE INSTRUCTIONS MANUAL IS RESERVED FOR
PROFESSIONALLY SKILLED PERSONNEL APPROVED THE MANUFACTURER.
18.0 STARTING UP
BEFORE CARRYING OUT ANYOPERATION ON THE MACHINE, ENSURE THAT THE ELECTRIC POWER SUPPLY HAS
BEEN DISCONNECTED
WAIT AT LEAST TWO HOURS BEFORE STARTING UP, AFTER ANY MACHINE MOVEMENT (TRANSPORT OR
HANDLING).
18.1 PRELIMINARY CONTROLS
Before starting the dryer, check:
- The correct connection to the compressed air piping: remember to remove eventual caps on the drier inlet and outlet.
- The correct connection to the condensate drainage system.
- That the power supply is right.
18.2 STARTING AND STOP
Start the system before the air compressor starts running and stop it after the air compressor has been stopped. The
compressed air piping will be free of condensate only by doing so. The drier must be kept running during all the time the
air compressor is running.
WARNING
: if the drier is switched off, before starting it again, wait at least 5 minutes in order
to allow the pressure balancing.
BEFORE CARRYING OUT ANY MAINTENANCE JOBS IT IS OBLIGATORY TO STOP THE MACHINE AND DISCONNECT IT FROM THE
POWER MAINS AND FROM THE COMPRESSED AIR DISTRIBUTION NETWORK.
PRESSURE DISCHARGE PROCEDURE
Proceed as follows:
- Close the cock Ref. 1 Fig. 11
- Remove the panel Ref. 2 Fig. 11
-
Release the pressure in the dryer by pressing the condensate drain “TEST” pushbutton locate on the steam trap
Ref. 3 Fig. 11
- Switch off the machine. Turn the switch in position STOP Ref. 4 Fig. 11
- Turn on the supply automatic differential switch Ref. 5 Fig. 11
- Close the panel Ref. 2 Fig. 11
FIG. 11
3
4
2
5
1