![Quincy Compressor QGD 40 Скачать руководство пользователя страница 100](http://html1.mh-extra.com/html/quincy-compressor/qgd-40/qgd-40_instruction-book_3767994100.webp)
8.2
Electric cable size and fuses
Important
• The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage.
It is however highly recommended to keep the voltage drop over the supply cables
at nominal current below 5% of the nominal voltage (IEC 60204-1).
• If cables are grouped together with other power cables, it may be necessary to use
cables of a larger size than those calculated for the standard operating conditions.
• Use the original cable entry. See section
.
To preserve the protection degree of the electric cubicle and to protect its
components from dust from the environment, it is mandatory to use a fitting
cable gland when connecting the supply cable to the compressor.
Use single core cables in conduit if two multicore cables do not fit in the supply
cable entrance.
• Local regulations remain applicable if they are stricter than the values proposed
below.
• Currents are calculated with the full service factor but we suggest to add 10% due
to over- and under-voltage.
Fuses are maximum allowed values calculated for full service factor and 10%
over- and under-voltage.
•
Caution
:
• Always double-check the fuse size versus the calculated cable size. If
required, reduce fuse size or enlarge cable size.
• Cable length should not exceed the maximum length according to IEC 60204
table 10.
Currents and fuses
UL/cUL approval
Compressor type
I (1)
Max. fuse (1)
I (2)
Max. fuse (2)
K5/
HRC form II
K5/
HRC form II
V
Hz
A
A
A
A
QGD 40
230
60
298.2
350
306.2
350
QGD 40
380
50
176.8
200
180.9
200
QGD 40
380
60
179.4
200
184.2
200
QGD 40
460
60
149.4
175
153.5
175
QGD 40
575
60
120.4
150
124.0
150
Instruction book
98
2920 7190 02
Содержание QGD 40
Страница 1: ...Quincy Oil injected rotary screw compressors QGD 40 QGD 50 QGD 60 Instruction book...
Страница 2: ......
Страница 14: ...Front view compressors with integrated dryer Instruction book 12 2920 7190 02...
Страница 15: ...Front view open compressors without dryer Instruction book 2920 7190 02 13...
Страница 16: ...Rear view compressors without dryer Instruction book 14 2920 7190 02...
Страница 17: ...Front view open compressors with integrated dryer Instruction book 2920 7190 02 15...
Страница 112: ......
Страница 113: ......
Страница 114: ...No 2920 7190 02 2021 08 Printed in Belgium Performance You Demand Reliability You Trust www quincycompressor com...