Quincy Compressor HP 15 Скачать руководство пользователя страница 2

ENGLISH 

 

2 - Edition  02/2018 Cod. 9828093052  04 -

 

MACHINE AND MANUFACTURER IDENTIFICATION DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1) Position of the identification plate 

 

ADDRESSES OF ASSISTANCE CENTRES

 

 

In the event of breakdown or malfunction of the machine, switch it off and do not tamper with it. 

If repairs are needed, apply only to a technical assistance centre approved by the manufacturer and insist on the use of original spare parts. 

Failure to comply with the above may endanger the safety of the machine. 

INTRODUCTION 

Keep this manual with care for future consultation; the use and maintenance manual is an integral part of the machine.  Read this 

manual carefully before carrying out any operations on the compressor unit. 

The installation of the compressor unit and all operations involving it must be performed in conformity with the regulations in 

force concerning electric plants and personal safety. 

 

CHARACTERISTICS AND SAFETY PRECAUTIONS 

 

MACHINE WITH AUTOMATIC START 

 

Lock Out – Tag Out (LOTO): Open the power isolating switch and lock it with a personal lock. Tag the power isolating switch 
with the name of the service technician. 

 

BEFORE REMOVING THE PROTECTIVE GUARDS TO CARRY OUT ANY MAINTENANCE ON THE MACHINE, SWITCH OFF THE 
ELECTRIC POWER SUPPLY AND DISCHARGE THE RESIDUAL PRESSURE INSIDE THE UNIT. 

 

ALL WORK ON THE ELECTRIC PLANT, HOWEVER SLIGHT, MUST BE CARRIED OUT BY PROFESSIONALLY SKILLED 
PERSONNEL. 

 

THIS MACHINE IS NOT SUITABLE FOR EXTERNAL INSTALLATION 
 
THIS MACHINE CORRESPOND TO THE ESSENTIAL SAFETY REQUIREMENTS FORESEEN FROM THE EUROPEAN STANDARD (2006/42 
CE).

 

 

THE LUBRICATING LIQUIDS AND OTHER EVENTUAL FLUIDS MUST NOT BE DISCHARGED IN THE ENVIRONMENT. THESE POLLUTING 
AND HAZARDOUS PRODUCTS MUST COMPULSORY BE DISPOSED BY CHARGING AUTHORISED AND SPECIALISED FIRMS 
ACCORDING TO THE DIFFERENT TYPOLOGY OF PRODUCT. 

 

DIFFERENTIATE THE COMPRESSOR COMPONENTS ACCORDING TO THE DIFFERENT CONSTRUCTION MATERIALS (PLASTIC, 
COPPER, IRON, OIL FILTER, AIR FILTER ECC…) 

 

The manufacturer does not accept responsibility for damage caused as a result of negligence or failure to abide by the instructions given above. 

 

AIR RECEIVER AND SAFETY VALVE: 

 

- To limit internal corrosion, which could compromise the safety of the compressed air tank, 

the condensation that is produced must be 

discharged at least once a day

. If an automatic drain fitted to the air receiver is present, it is necessary to check that it is working correctly 

every week and repair it if necessary. 

The thickness of the receiver must be checked every year and also in accordance with legislation in force in the country where 

the receiver is installed.

 

The tank cannot be used and must be replaced if the thickness falls below the minimum level given in the instruction documents 

for the tank.

 

- The tank can be used within the temperature limits given in the conformity declaration. 

The safety valves of the air receiver and oil receiver must be checked every year and replaced 

if necessary

 

in 

accordance with legislation in force. 

 

NOT RESPECTING THE ABOVE MENTIONED PRESCRIPTION CAN RESULT IN AIR RECEIVER BURSTING HAZARD.

 

 

The manufacturer does not accept responsibility for damage caused as a result of negligence or failure to abide by the instructions given above. 

 

 

 

Содержание HP 15

Страница 1: ...RAL ORDINARY MAINTENANCE REQUIRES TRAINED PERSONNEL 3 0 OPERATION 22 0 CHANGING THE OIL 4 0 GENERAL SAFETY STANDARDS 23 0 CHANGING THE OIL SEPARATING FILTER 5 0 DESCRIPTION OF DANGER SIGNALS 24 0 OLEO...

Страница 2: ...ESEEN FROM THE EUROPEAN STANDARD 2006 42 CE THE LUBRICATING LIQUIDS AND OTHER EVENTUAL FLUIDS MUST NOT BE DISCHARGED IN THE ENVIRONMENT THESE POLLUTING AND HAZARDOUS PRODUCTS MUST COMPULSORY BE DISPOS...

Страница 3: ...nt to two separate coolers where they are cooled using a flow of air taken from the environment by a special fan inside the machine The cooled oil returns to the circuit while the compressed air passe...

Страница 4: ...1 FLUID EJECTION 6 HOT PARTS 2 DANGEROUS ELECTRIC VOLTAGE 7 MOVING PARTS 3 AIR NOT FIT FOR BREATHING 8 MOVING PARTS 4 NOISE 9 MACHINE WITH AUTOMATIC START 5 HIGH PRESSURE 10 PURGE EVERY DAY 5 1 DESCRI...

Страница 5: ...ENGLISH Cod 9828093052 04 Edition 02 2018 5 6 0 DANGERS ZONES 6 1 DANGERS ZONES FOR COMPRESSOR UNIT Risks present on the whole machine 1 2 3 7 8 5 2 2 8 2 2 1 3 8 2 5 3 FIG 3...

Страница 6: ...MPRESSOR 1 Safety screws 4 Emergency stop button with mechanical seal and rotation release 2 Side panels and door to the electric panel opened with a special key 5 Oil filling cap with safety breather...

Страница 7: ...tomatic 6 Safety valve POSITION OF PLATES 8 1 POSITION OF THE DANGER PLATES FOR COMPRESSOR UNIT The plates fitted on the compressor unit are part of the machine they have been applied for safety purpo...

Страница 8: ...ey have been applied for safety purposes and must not be removed or spoiled for any reason 1 Dangers plate Cod 1079990148 8 3 POSITION OF THE DATA PLATE FOR COMPRESSOR UNIT ELECTRICAL AND UL LABELS 1...

Страница 9: ...ning must be low to allow the intake of external air for ventilation If the environment is dusty it is advisable to fit a filtering panel on this opening 9 3 EXAMPLES OF VENTILATION OF THE COMPRESSOR...

Страница 10: ...iagram Connect the cables to the charging clamps on the electric panel and make sure they are properly tightened After the first 50 working hours check that the screws on the electric terminals are ti...

Страница 11: ...ted Drainage must comply with the local regulations in force ALL DAMAGE DUE TO THE FAILURE TO COMPLY WITH THESE INDICATIONS CANNOT BE ATTRIBUTED TO THE MANUFACTURER AND MAY CAUSE INVALIDITY OF THE GUA...

Страница 12: ...6 Weight lb with air receiver 120 Gal with dryer 1760 1777 1892 1927 Weight lb without dryer 1052 1069 1135 1171 Weight lb with air receiver 120 Gal without dryer 1553 1570 1636 1672 HP 15 kW 11 HP 20...

Страница 13: ...sure gauge tank 14 Control card 15 Safety valve 16 Water separator drain 17 Electric motor 18 Screw compressor 19 Suction unit 20 Condensate manual drainage IT IS FORBIDDEN TO TAMPER WITH THE SETTING...

Страница 14: ...ected by temperature sensor compressor element outlet temperature bigger than the programmed shut down level detected by temperature switches overload of the drive motor overload of the fan motor freq...

Страница 15: ...ymbol 9 LED Service It s lit when service is needed 10 Start button This button starts the compressor Automatic operation LED 3 lights up The Elektronikon is operative 11 Stop button This button is us...

Страница 16: ...pped Running unloaded Running loaded Machine control mode Or Local start stop Remote start stop Network control Automatic restart after voltage failure Automatic restart after voltage failure is activ...

Страница 17: ...The Main screen is the screen that is shown automatically when the voltage is switched on and one of the keys is pushed It is switched off automatically after a few minutes when no keys are pushed Typ...

Страница 18: ...This bar shows the text that corresponds to the selected icon Section D shows the Action buttons These buttons are used To call up or program settings To reset a motor overload service message or emer...

Страница 19: ...w triangle 1 pops up in the lower side of the display as in the picture below in the left side To check which is the warning highlight the yellow triangle using the Scroll keys Press the Enter key and...

Страница 20: ...tections and the one who is causing the shutdown will be highlighted as in picture below Take care that the shut down Overload motor appears in case of main motor overload or incorrect phase sequence...

Страница 21: ...urrent limit is exceeded 14 4 Ground Fault X X Discharge from output phases to ground 16 4096 Short circuit X X Short circuit in the motor or on the motor terminals 17 16 Ctrl word TO X X No communica...

Страница 22: ...ion X X Internal fault Contact compressor service 80 Drive initialized X All parameter settings are initialized to default settings 87 Auto DC Braking X The drive is auto DC braking Inputs menu Functi...

Страница 23: ...ber of motor starts the number of hours that the regulator has been powered and the number of load cycles Procedure starting from the Main screen see Main screen move the cursor to the action button M...

Страница 24: ...e press the enter button on the controller to confirm your selection The new setting is now visible on the main screen See section Used icons for the meaning of the icons Service menu Function to rese...

Страница 25: ...the indicated levels the timers must be reset From the Service menu above select Service plan 3 and press Enter Following screen appears In the example above the A Service level is programmed at 4000...

Страница 26: ...s required in the same way as described above Event history menu Function to call up the last shut down and last emergency stop data Procedure starting from the Main screen see Main screen move the cu...

Страница 27: ...con General menu Function this menu covers a list of general settings Language Time Date Date Format Units Procedure starting from the submenu screen see Modifying general settings using the Scroll ke...

Страница 28: ...down level changes to 96 C 204 F The recommended difference between the warning level and shut down level is 10 C 18 F Delay at shut down signal Is the time for which the signal must exist before the...

Страница 29: ...ng electrical cables at first 500 hrs Clean the air suction filter Clean the condenser battery on the dryer if fitted Clean the dirt collection filter Check automatic condensation emptying dryer Clean...

Страница 30: ...ate flow out When the first traces of oil appear turn off the tap CONDENSATE MUST BE DISPOSED OF IN CONFORMITY WITH THE LOCAL REGULATIONS IN FORCE Check the oil level on the indicator Ref 5 Fig 18 If...

Страница 31: ...ed reassemble the filtering panel Ref 1 Fig 19 15 6 CLEANING THE SUCTION FILTER OR CHANGING THE FILTER Switch off the machine with pushbutton Ref 1 Fig 18 in this way the machine stops after idle time...

Страница 32: ...ation is correctly emptied from the drainage pipe Ref 3 Close the panel Ref 2 and Ref 10 Fig 20 15 8 CLEAN THE DIRT COLLECTION FILTER FOR COMPRESSOR AND DRYER IF AVAILABLE Proceed as follows Close the...

Страница 33: ...e drainage pipe Check manual condensation emptying from the tank to ensure that condensation is correctly emptied from the valve Ref 2 Fig 20A PURGE EVERY DAY AFTER USE CLEAN THE DIRT COLLECTOR FILTER...

Страница 34: ...THE COMPRESSED AIR DISTRIBUTION NETWORK The condenser must be cleaned every month Proceed as follows Switch off the machine with pushbutton Ref 1 Fig 21 in this way the machine stops after idle time r...

Страница 35: ...time running Turn off the disconnect switch Ref 5 Fig 22 Close the panel Ref 2 and Ref 7 Fig 22 During periods of inactivity the unit must be protected against atmospheric agents dust and humidity wh...

Страница 36: ...P 15 kW 11 HP 20 kW 15 HP 25 kW 18 5 HP 30 kW 22 1 Suction air filter 2013400003 2 Oil filter 1625430291 3 Oil separator cartridge 2204149800 4 Filtering panel only VSD 1089955668 5 Air filter 2202260...

Страница 37: ...ion device has tripped 2C Temperature switch on element outlet has tripped Verify phases sequence to check possible motor failure environment temperature too high improve ventilation in the compressor...

Страница 38: ...d is very hot 55 C 131 F Make reference to 2B Make reference to 2C 3A The cooling circuit is not working with the right gas charge Check if there are leaks of refrigerating gas Charge it again 4 Motor...

Страница 39: ...the oil level is not as intended top up with the same oil as the original type If more than 3 months have passed between the inspection in the factory and the date of installation lubricate the screw...

Страница 40: ...ot spin in the right direction reverse two mains cables When it rotates in the correct direction the oil level Rif 5 Fig 25 Should drop after 4 or 5 seconds of operation It is very important to rememb...

Страница 41: ...ing panel VSD Clean the air suction filter Clean the air filters Every 4000 hours Maintenance kit of the automatic condensate drain dryer Clean the finned surface of the air oil cooler Change the filt...

Страница 42: ...chine will switch off PROCEED AS DESCRIBED AT POINT CHAPTER 15 4 THE OLD OIL MUST BE DISPOSED OF IN COMPLIANCE WITH THE REGULATIONS IN FORCE NOTE ON LUBRICANTS When delivered the machine is filled wit...

Страница 43: ...306 Capillary tube 105 Safety valve 308 Electronic drain 106 Oil separator 311 Hot gas bypass valve 107 Minimum pressure valve 312 Fan switch 108 After cooler Oil cooler TISHH1 Temperature sensor Tem...

Страница 44: ...ERATION COMPRESSOR Evaporat Temperat C F Evaporating Pressure bar psi Evaporating Pressure bar psi Evaporating Pressure bar psi RATED VALUES Temperat 20 C 68 F 1 2 33 8 35 6 R134a 2 1 2 3 30 4 33 3 R4...

Отзывы: