ALL DIP-SWITCH:
FEATURES
The control unit
QK-CE220CN
control equipment for sliding systems and road barriers to 230Vac power supply.
This panel can manage motors with or without limit switches, encoders and limitswitches.
The peculiarity of
QK-CE220CN
is that it has separate torque control, through trimmer T1 and T2 (T1 regulates the torque while
running in normal speed the T2 adjusts the torque during deceleration)
. Interacting on these devices can optimize the operation of
the automation so as to be within the actual rules. The programming of the switches and remote controls is self-learning, so everything
is easier.
In case management through ENCODER (DIP 8 ON) security will be guaranteed by the photocells/bands safety or to torque
control: if the gate find an obstacle will be reversed or blocked.
With ENCODER not active (OFF DIP 8)
not have the reverse function but only torque control through
trimmer
T1
and
T2.
PROGRAMMING REMOTE CONTROL
The control unit is able to handle radio fixed code and rolling code. The two systems can not be managed simultaneously, but
with the first remote control will be programmed encoding system.
The
QK-CE220CN
can handle 254 transmitters ROLLING CODE.
The programming of the transmitters is done by pressing the
P1 for 2sec
, the LED L2 turns on, then pressing the button of the remote
will flash twice to indicate the LED L2 is stored in memory. After 6 seconds automatically central will exit the programming function.
PROGRAMMING PEDESTRIAN MODE (by remote control)
To program this function push
P1 button for 2sec
,
release it and press it again for 1 sec
, the LED L2 starts flashing and each press
of the button on a remote control will be a rapid double flash of the LED L2, after 6sec the control board automatically exit to
programming.
The operating time of the pedestrian mode is 8 sec.
REMOVE ALL CODES
Press and hold the
P1 for 6
seconds when it is released there will be a quick flash of the LED L2, with consequent turning off after 6
seconds.
PROGRAMMING THE STROKE
The programming begins automation is closed, the first operation will be the opening, otherwise reverse the direction by
DIP switch 4.
PROGRAMMING with slow down (DIP 7ON)
To enter in programming, press the P2 button for 2 seconds, the LED3 will flash
Give a
FIRST PULSE by START
contact (terminals 1 and 2) or by transmitter already been programmed.
The operator will start the opening phase, give a
SECOND PULSE
where you want to start the slow down in opening.
The engine will complete the stroke and will stop at close limitswitch (if you chose an automatism without limitswitches must give a
further impulse to fix the stopping point of the stroke).
If you choose to have the AUTOMATIC CLOSING (OPTION 2 IN ON), the closing time will be calculated from the moment when
the operator arrives to open limitswitch until you give the THIRD PULSE, the automatism will start closure.
Where do you want start slowing down in closing you must give the
FOURTH PULSE.
The arrest will be through the closing limitswitch
and now the LED will turn off 3. If the automatism is not expected to limit switch, you will need to give a last pulse where you want
to stop.
PROGRAMMING without slow down (DIP 7OFF)
Set the option 7 to OFF for the exclusion of the slowdown phase. Follow the procedure listed above (learning with slowdown) without
transmitting the second pulse in opening and the fourth during closing. So once impulses transmitted to the beginning of the maneuvers,
in opening and in closing, they will finish at the limitswitch position.
OPERATION LOGIC OF THE SAFETY
SAFETY BAND TERMINAL (4-6)
This contact protects opening and closing.
DIP 5 ON: in opening when there is an obstacle, the engine stop and reverse for 2 sec.
DIP 5 OFF: in opening when there is an obstacle engine STOP
In both cases in closing when there there is an obstacle the gate stop.
PHOTOCELLS TERMINAL (5-6)
This contact protects only in closing
In closing when there is an obstacle engine STOP
STOP TERMINAL (18-19)
The contact if open will cause the immediate arrest of the automation in any situation.
FLASHING OPERATION WITH DIP6 ON
IN OPENING:
Flash slow
IN CLOSING:
Flash fast
IN PAUSE:
Steady light
PHOTOCELL ENGAGED:
Turn off
DIP 1
COUNTERWEIGHT DOORS/SLIDING GATE
Counterweight doors function
Sliding gate function
DIP 2
AUTOMATIC CLOSING
Automatic closing activated
Automatic closing not actived
DIP 3
CONDOMINIUM / STEP BY STEP
The automation will end the operation always on end
switches, in opening does not accept pulses, in closing a
pulse will cause the reverse.
For each pulse automation will stop
(OPEN-STOP-CLOSE-STOP)
DIP 4
INVERSION OF THE DIRECTION
Invert direction and the limitswitch
Invert direction and the limitswitch
DIP 5
SETTING SEFETY CONTACT IN OPENING
In opening the control board stop and invert for 2sec the
gate direction
In opening the control board stop the gate direction
DIP 6
FLASHING FUNCTION
Intermittent light
Steady light
DIP 7
SLOW DOWN
Activate
Not activate
DIP 8
ENCODER
Encoder actived
Encoder not actived
DIP 9
OPEN RADIO MEMORY WITH TRANSMITTER
With you can storable other transmitter without open the
control board.
Actived
Not actived
DIP
10
MANAGE SLOWDOWN
Heavy leaf
Light leaf
ON-
OFF-
ON-
OFF-
ON-
OFF-
ON-
OFF-
ON-
OFF-
ON-
OFF-
ON-
OFF-
ON-
OFF-
ON-
OFF-
ON-
OFF-