30

Installation and Maintenance

Service Manual

(3) The water outlet can't be placed in water in order to drain 
smoothly.(As show in Fig.27)

Liquid valve

Gas valve

Refrigerant charging

vent
Nut of refrigerant
Charging vent

Vacuum pump

Piezometer

Valve cap

Lo

Hi

Inner hexagon

spanner

Open

Close

The drain hose can't be fluctuant

The drain hose

can't be fluctuant

The water 

outlet can't be

fluctuant

NO.

Items to be checked

Possible malfunction

1

Has the unit been 
installed firmly?

The unit may drop, shake or 
emit noise.

2

Have you done the 
refrigerant leakage test?

It may cause insufficient cooling 
(heating) capacity.

3

Is heat insulation of 
pipeline sufficient?

It may cause condensation and 
water dripping.

4 Is water drained well?

It may cause condensation and 
water dripping.

5

Is the voltage of power 
supply according to the 
voltage marked on the 
nameplate?

It may cause malfunction or 
damage the parts.

6

Is electric wiring and 
pipeline installed 
correctly?

It may cause malfunction or 
damage the parts.

7

Is the unit grounded 
securely?

It may cause electric leakage.

8

Does the power cord 
follow the specification?

It may cause malfunction or 
damage the parts.

9

Is there any obstruction 
in air inlet and air outlet?

It may cause insufficient cooling 
(heating).

10

The dust and 
sundries caused 
during installation are 
removed?

It may cause malfunction or 
damaging the parts.

11

The gas valve and liquid 
valve of connection pipe 
are open completely?

It may cause insufficient cooling 
(heating) capacity.

The water outlet 

can't be placed

in water

1. Use Vacuum Pump

(1) Remove the valve caps on the liquid valve and gas valve 
and the nut of refrigerant charging vent.
(2) Connect the charging hose of piezometer to the refrigerant 
charging vent of gas valve and then connect the other charging 
hose to the vacuum pump.
(3) Open the piezometer completely and operate for 10-15min 
to check if the pressure of piezometer remains in -0.1MPa.
(4) Close the vacuum pump and maintain this status for 1-2min 
to check if the pressure of piezometer remains in -0.1MPa. If 
the pressure decreases, there may be leakage.
(5) Remove the piezometer, open the valve core of liquid valve 
and gas valve completely with inner hexagon spanner.
(6) Tighten the screw caps of valves and refrigerant charging 
vent.
(As show in Fig.28)

1. Check after Installation

Check according to the following requirement after finishing 
installation.

2. Test operation

(1) Preparation of test operation
● The client approves the air conditioner installation.
● Specify the important notes for air conditioner to the client.
(2) Method of test operation
● Put through the power, press ON/OFF button on the remote 
controller to start operation.
● Press MODE button to select AUTO, COOL, DRY, FAN and 
HEAT to check whether the operation is normal or not.
● If the ambient temperature is lower than 16

, the air 

conditioner can’t start cooling.

2. Leakage detection

(1) With leakage detector:
Check if there is leakage with leakage detector.
(2) With soap water:
If leakage detector is not available, please use soap water for 
leakage detection. Apply soap water at the suspected position
and keep the soap water for more than 3min. If there are air 
bubbles coming out of this position, there's a leakage.

8.7 Vacuum Pumping and Leak Detection

8.8 Check after Installation and Test 

operation

Fig.26

Fig.27

Fig.28

Содержание QS09-VJ115

Страница 1: ...QS09 VJ115 QS12 VJ115 QS09 VP115 QS12 VP115 Refrigerant R410A Model INSTALLATION MANUAL...

Страница 2: ...condition must apply specialized circuit and prohibit share the same circuit with other appliances 3 The air conditioner should be installed in suitable location and ensure the power plug is touchabl...

Страница 3: ...ng tape 4 Electroprobe 7 Electronic leakage detector 10 Pipe pliers pipe cutter 2 Screw driver 5 Universal meter 8 Vacuum pump 11 Pipe expander pipe bender 3 Impact drill drill head electric drill 6 T...

Страница 4: ...east 0 5ft At least 0 5ft At least 0 5ft At least 8 2ft Space to the wall S p a c e t o t h e o b s t r u c t i o n r o o l f e h t o t e c a p S Space to the obstruction Drainage pipe Space to the wa...

Страница 5: ...or unit Make the bound pipes pass through the wall hole and then connect outdoor unit Neaten the pipes Vacuum pumping and leakage detection Check after installation and test operation Finish installat...

Страница 6: ...ditioner is grounding wire which can t be used for other purposes 3 The grounding resistance should comply with national electric safety regulations 4 The appliance must be positioned so that the plug...

Страница 7: ...e the torque wrench on the union nut Tighten the union nut with torque wrench As show in Fig 6 4 Wrap the indoor pipe and joint of connection pipe with insulating pipe and then wrap it with tape As sh...

Страница 8: ...ower connection wire go through the cable cross hole at the back of indoor unit and then pull it out from the front side As show in Fig 12 3 Remove the wire clip connect the power connection wire to t...

Страница 9: ...ve the cable crossing board 2 of right side plate for outdoor unit 2 Remove the wire clamps pass the power connection cord and power cord through the cable crossing board 1 to connect the terminal The...

Страница 10: ...Remove the valve caps on the liquid valve and gas valve and the nut of refrigerant charging vent 2 Connect the charging hose of piezometer to the refrigerant charging vent of gas valve and then conne...

Отзывы: