background image

     

 

 

 

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, 

OBSERVE 

THE FOLLOWING: 

 

1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact 

the manufacturer at the address or telephone number listed in the warranty. 
2. Before servicing or cleaning unit, switch power off at service panel and lock the service 

disconnecting means to prevent power from being switched on accidentally. When the service 

disconnecting means cannot be locked, securely fasten a prominent warning device, such as a 

tag, to the service panel. 
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance 

with all applicable codes and standards, including fire-rated construction codes and standards. 
4. Sufficient air is needed for proper combustion and exhausting of gases through the flue 

(chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment 

manufacturer’s guideline and safety standards such as those published by the National Fire 

Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air 

Conditioning Engineers (ASHRAE), and the local code authorities. 
5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden 

utilities. 
6. To Reduce The Risk Of Fire Or Electric Shock, Do Not Use This Fan With Any Solid-State 

Speed Control Device. 
7. This unit must be grounded. 
8. Not for Use in Kitchens. 

1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and 

vapors. 
2. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, 

construction dust, etc. off power unit. 
3. For residential installations only. 
4. Read all instructions before installing or using fan. 
5. The motor is permanently lubricated and never needs oiling. If the motor bearings are making 

excessive or unusual noises, replace the blower assembly. 

MODEL 

OFF 

READ AND SAVE THESE INSTRUCTIONS 

Installer: Leave this manual with the homeowner 

 

Содержание QuF100X

Страница 1: ...w the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities 5 When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities 6 To Reduce The Risk Of Fire O...

Страница 2: ...ousing is shown upside down for clarity 3 Confirm the fan is appropriately positioned so the air flow is in the correct direction the damper is on the outlet of the fan and the fan can be easily accessed for cleaning and maintenance 4 The fan can be mounted directly to studs joist blocking using appropriate lag screws not included or suspended from hangar rods not included Use thread locker on thr...

Страница 3: ... close the cover and tighten the toggle latch ELECTRICAL CONNECTIONS 1 Remove the screw and place the wiring plate in a secure place 2 Run 120 VAC house wiring to the location of the fan Use only UL approved connectors not included to attach the house wiring to the wiring plate Refer to the wiring diagram and connect the wires as shown 3 Carefully tuck wires back inside wiring plate and replace wi...

Страница 4: ...mode 1 Low Temperature LT knob This set point establishes the low temperature limit setting Below this setpoint the fan will turn off and the unit will be in sampling mode This setting is adjustable from 32 F 50 F 0 C 13 C factory preset 40 F 4 C 2 High Temperature HT knob This set point establishes the high temperature limit setting Above this set setpoint the fan will turn off and the unit will ...

Отзывы: