Quest IQ Compressor Wall OMM
20
September 2020
Routine Maintenance Program
Creating facility-specific routine maintenance program and following it is vital to equipment longevity and efficient
operation.
The suggested general maintenance operations and their frequency/intervals, listed in the table M-1 below, can be
used to create such a program. For more detailed maintenance recommendations related to specific components,
refer to the respective component manufacturer
’s manual.
Table M.1. Recommended Maintenance Tasks and Intervals
Interval
Maintenance Task
Weekly
Observe the equipment for any changes in running conditions and unusual noise
Quarterly
Air filters: Industry recommendation is to change air filters every process cycle (at minimum)
Verify that all set-points are correctly programmed as specified by the facility operator
Semi-
Annually
Inspect and clean the drain pan(s)
Tighten electrical connections, if required
Check and tighten, if required, hose clamps and sensor mounts
Inspect all airside coils (dry cooler, HVAC system coils – evaporator, etc.) for dirt, cobweb build-up,
etc.; clean as needed
Check that the P-trap is primed (filled with water). It is good practice to pour some water into the
drain pan to ensure that the P-trap is primed and operational
Check the louvres and dampers (as applicable) for accumulation of dust and clean as required
Inspect the equipment’s cabinet for corrosion or other deterioration. If any damage is found, clean
and repaint the affected surface with a rust-resistant primer
Annually
Clean the fan wheel(s). Exercise caution not to disturb balance weights/clips, if any.
Check dampers operation (linkage/actuator is not loose, damper opens/closes properly etc.)
Inspect electrical components, wiring and insulation
Rotate the fan wheel(s) and check for obstructions and rubbing
Check gasket condition on all doors to ensure an airtight seal
Check bolts on compressors, motor mounts, HVAC system bases and coils and tighten if required
Verify that the airflow around the remote condenser or dry cooler is unobstructed