background image

Quest DRY 105, 155, and 205 

Installation, Operation and Maintenance Instructions

1-877-420-1330

18

www.QuestProtect.com

[email protected]

FOR HVAC INSTALLER AND OWNER

NOTE: NEVER use the compressor to evacuate the system or any part of it. 
8.6C Replacing a Compressor, Nonburn Out 

Remove the refrigerant from the system. Replace the compressor and liquid line filter/drier. Charge the system to 50 PSIG and 

check for leaks. Remove the charge and weigh in the refrigerant quantity listed on the nameplate. Operate the system to verify 

performance. 
8.7 Remote Controls 

The Quest Dry is controlled by devices mounted on a panel that is remote from the unit. You may or may not have the devices 

listed below depending on the model of the remote control panel you purchased. If the Quest Dry fails to operate as desired, 

always check the settings of the controls to insure that they are correct. Check that the controls are receiving 24Vac from the 

Quest Dry. Check the connections between the Quest Dry, the control panel, and the field control wiring. 
8.7A Humidity Control 

The humidity control is an adjustable switch that closes when the relative humidity of the air in which it is located rises to the 

dial set point. It opens when the RH drops 4 to 6% below the set point. If the Quest Dry does not run, try turning the humidity 

control clockwise until it reaches the stop and the knob pointer points at “Max Dry” (see back of control panel cover). If it still 

does not run, remove the stop screw from the panel and turn the knob farther. If it then runs, the humidity control is out of 

calibration or the RH is below 40%. 
The Quest Dry is equipped with an automatic defrost mechanism. If the Quest Dry operates in conditions that develop frost 

on the evaporator, it will sense the frost build-up and automatically defrost the evaporator. The Quest Dry may not appear to 

be operating correctly during the defrost sequence, but once the defrost sequence is completed, the Quest Dry will resume 

dehumidifying. 
8.7B Programmable Ventilation Timer 

The ventilation timer controls the impeller fan and the motorized fresh air damper. When the ventilation timer is activated, the 

Quest Dry will circulate the indoor air, and bring in fresh air from outside. The ventilation timer should be set for the required 

ventilation of the residence. The structure should be ventilated with fresh air as suggested by applicable codes and standards. 
If the Quest Dry fails to ventilate as expected, check that the time on the timer is correct. For the timer to carry out the program 

schedule, the slide switch in the upper left corner on the timer must be set to 

“AUTO”. The slide switch in the upper right corner 

of the Quest Dry must be set to 

“RUN”. Also check the programs on the timer to be sure that the timer is calling for ventilation 

at the correct times. If the timer fails to operate or operates erratically, reset the timer; see section 4.5 of this manual. 

8.8 Defrost Thermostat 

The defrost thermostat is attached to the refrigerant suction tube between the accumulator and the compressor. It will 

automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the 

evaporator coil. The impeller fan will continue to run, causing air to flow through the evaporator coil and melt the ice. When the ice 

has melted, the evaporator temperature will rise and the thermostat will restart the compressor. 

8.9 Electric Ventilation Damper 

The electric ventilation damper is controlled by the ventilation timer. The damper will open when the ventilation timer is activated 

to allow fresh air into the structure through the 6” diameter fresh air inlet duct. The electric ventilation damper will remain closed 

when the ventilation timer is not activated to prevent over-ventilating the structure when the unit is dehumidifying or recirculating 

the indoor air. 
The electric ventilation timer operates on 24 VAC from the control circuit. 

DO NOT connect high voltage to the damper motor 

or damage to the motor may result. 

DO NOT force the blade of the damper by hand or damage to the damper motor may result. 

The damper opens in one direction only. The damper rotates very slowly, allow sufficient time for the damper to cycle. The damper 

Содержание Dry 105

Страница 1: ...F 60 RH while using only 4 9 amps 115V The Quest Dry 155 provides water removal of 155 pints per day at 80 F 60 RH using 8 0 amps 115V The Quest Dry 205 is the largest capacity of the group This unit...

Страница 2: ...ion 9 5 Controls 10 6 Optional Dehumidifier Ventilation System Controller 11 7 Maintenance 13 7 1 Standard Air Filter 13 7 2 High Efficiency Air Filter 13 7 3 Impeller Fan Oiling 13 7 4 Optional Fresh...

Страница 3: ...s plugged into a GFI GROUND FAULT INTERRUPT OUTLET DO NOT use the device as a bench or table DO NOT place the device directly on structural members Provide vibration isolation in order to minimize ope...

Страница 4: ...VAC 1 Phase 60 Hz Current Draw 4 9 Amps 8 0 Amps 13 2 Amps Energy Factor 4 2 3 5 2 7 Operating Temp 56 F Min 95 F Max 56 F Min 95 F Max 56 F Min 95 F Max Minimum Performance 80 F and 60 RH Water Remo...

Страница 5: ...nded with steel hanger straps or a suitable alternative from structural members unit must be supported from underneath Don t hang from sides or ends Remember to place a drain pan under the unit if it...

Страница 6: ...rt An optional condensate pump kit may be installed if a lift is required to dispose of the condensate The condensate pump kit can be ordered directly from the factory See the optional parts list for...

Страница 7: ...ming instructions for the ventilation timer Advantages of this form of ventilation include 1 Outside air is filtered before entering the building 2 Outside air will be dehumidified before entering if...

Страница 8: ...e of the tee to the air supply of the existing HVAC system A backdraft damper is required in the duct between the 10 tee and the central supply duct to prevent air from being discharged into the basem...

Страница 9: ...ed in central open area of the structure DO NOT locate the return in a bathroom or a kitchen The supply of the Quest Dry should be located in the remote areas of the structure By ducting this way the...

Страница 10: ...contact between yellow and green or brown wires To power an HVAC accessory connect the accessory to the white or red wire and the yellow wire FOR HVAC INSTALLER ONLY P N 4027370 with remote P N 40285...

Страница 11: ...com TS 673 06 11 WARNING Allowing yellow wire to contact red or white wire will destroy the transformer Dehumidifier on Connect yellow and blue wires Fan only on Connect yellow and green or brown wire...

Страница 12: ...del DEH 3000 DEH 3000R remote Operating Voltage 24 VAC Max Current DMP COMP FAN 1 AMP each Humidity Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4...

Страница 13: ...available for the Quest Dry This filter is rated as 90 95 efficient by the ASHRAE Dust Spot test method 52 76 The high efficiency pleated microglass paper filter should be used in conjunction with th...

Страница 14: ...aporator tubes contain liquid refrigerant during normal operation A flooded evaporator should maintain nearly constant pressure and temperature across the entire coil from inlet to outlet The mixture...

Страница 15: ...humidification is being called for 1 Defrost thermostat loose or defective Sec 7 8 2 Low refrigerant charge 3 Dirty air filter s or air flow restricted 4 Excessively restrictive ducting connected to u...

Страница 16: ...sisting of the motor and impeller fan If defective the complete assembly must be replaced 1 Unplug the power cord 2 Remove the cabinet access panel 3 Remove the screw attaching the impeller fan suppor...

Страница 17: ...otors and cause failures The following procedure is effective only if the system is monitored after replacing the compressor to insure that the clean up was complete 1 This procedure assumes that the...

Страница 18: ...Timer The ventilation timer controls the impeller fan and the motorized fresh air damper When the ventilation timer is activated the Quest Dry will circulate the indoor air and bring in fresh air fro...

Страница 19: ...condensate pump kit is available from the factory for use with the Quest Dry Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the flo...

Страница 20: ...3 4 4032178A 1 2 3 4 BLK 3 WHT 6 A B B A BLK 7 COM COM 24V 24VAC COM BLU YEL GRN RED LINE NEUTRAL CUSTOMER SUPPLIED CONTROL WIRING N O WHT 4 UNIT E BOX 1 59 1413 WHT 4 BLK 1 8 2 3 2 2 2 3 7 5 COM COM...

Страница 21: ...lacement Kit 7 4032224 1 Dry 155 Dry 205 Compressor Replacement Kit 4029568 1 Dry 105 Compressor Overload NOT SHOWN 4029714 1 Dry 155 Compressor Overload NOT SHOWN 4031574 1 Dry 205 Compressor Overloa...

Страница 22: ...Humidity Fan 4024125 1 Control Panel Assembly Ventilation Timer Humidity 4023660 1 Controller Humidity 4023672 1 Duct Damper 6 Diameter Electrically Actuated not shown 4024153 1 Cover for Items 28 29...

Страница 23: ...he door in between the foam installation and the metal side Push down on the plastic door latch and swing door shut Once the door is shut release the door latch Collar Install Remove the 2 round ducts...

Страница 24: ...le means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification u...

Отзывы: