4.    Compressor terminals C and S: No continuity indicates an open start winding. The compressor must be replaced. Normal start 

winding resistance is 3 to 7 ohms. 

5.    Compressor terminals C and R: No continuity indicates an open run winding. The compressor must be replaced. Normal run 

winding resistance is .5 to 2 ohms. 

6.    Compressor terminal C and overload terminal 1: No continuity indicates a defective overload lead. 
7.    Overload terminals 1 and 3: If there is no continuity, the overload may be tripped. Wait 10 minutes and try again. If there is still 

no continuity, it is defective and must be replaced. 

8.    Compressor terminal C and compressor case: Continuity indicates a grounded motor. The compressor must be replaced. 
9.    Disconnect the wires from the run capacitor. Set the ohmmeter to the Rx1 scale. The capacitor is shorted and must be 

replaced if continuity exists across its terminals. If there is no needle movement with the meter set on the Rx100000 scale, 

the capacitor is open and must be replaced. 

10.  Reconnect the wires to the compressor and capacitor. Plug in and turn on the unit. If the compressor fails to start, replace the 

run capacitor. 

11.  If the unit still does not start, adding a hard-start kit (relay & capacitor) will provide greater starting torque. If this doesn't work, 

the compressor has an internal mechanical defect and must be replaced. 

8.6B Replacing a Burned Out Compressor 

The refrigerant and oil mixture in a compressor is chemically very stable under normal operating conditions. However, when 

an electrical short occurs in the compressor motor, the resulting high temperature arc causes a portion of the refrigerant oil 

mixture to break down into carbonaceous sludge, a very corrosive acid, and water. These contaminants must be carefully removed 

otherwise even small residues will attack replacement compressor motors and cause failures. 
The following procedure is effective only if the system is monitored after replacing the compressor to insure that the clean up was 

complete. 
1.    This procedure assumes that the previously listed compressor motor circuit tests revealed a shorted or open winding. 
2.    Remove and properly dispose of the system charge. 

DO NOT vent the refrigerant or allow it to contact your eyes or skin. 

3.    Remove the burned out compressor. Use rubber gloves if there is any possibility of contacting the oil or sludge. 
4.    To facilitate subsequent steps, determine the type of burn out that occurred. If the discharge line shows no evidence of sludge 

and the suction line is also clean or perhaps has some light carbon deposits, the burn out occurred while the compressor was 

not rotating. Contaminants are therefore largely confined to the compressor housing. A single installation of liquid and suction 

line filter/driers will probably clean up the system. 

  If sludge is evident in the discharge line, it will likely be found in the suction line. This indicates the compressor burned out will 

running. Sludge and acid have been pumped throughout the system. Several changes of the liquid and suction filter/driers will 

probably be necessary to cleanse the system. 

5.    Correct the system fault that caused the burn out. Consult the factory for advice. 
6.    Install the replacement compressor with a new capacitor and an oversized liquid line filter. 
In a running burn out, install an oversized suction line filter/drier between the accumulator and compressor. Thoroughly flush the 

accumulator with refrigerant to remove all trapped sludge and to prevent the oil hole from becoming plugged. A standing burn out 

does not require a suction line filter/drier. 
7.    Evacuate the system with a good vacuum pump and accurate vacuum gauge. Leave the pump on the system for at least an 

hour. 

8.    Operate the system for a short period of time, monitoring the suction pressure to determine that the suction filter is not 

becoming plugged. Replace the suction filter/drier if pressure drop occurs. If a severe running burn out has occurred, several 

filter/driers may have to be replaced to remove all of the acid and moisture. 

Содержание Dry 105

Страница 1: ...F 60 RH while using only 4 9 amps 115V The Quest Dry 155 provides water removal of 155 pints per day at 80 F 60 RH using 8 0 amps 115V The Quest Dry 205 is the largest capacity of the group This unit...

Страница 2: ...ion 9 5 Controls 10 6 Optional Dehumidifier Ventilation System Controller 11 7 Maintenance 13 7 1 Standard Air Filter 13 7 2 High Efficiency Air Filter 13 7 3 Impeller Fan Oiling 13 7 4 Optional Fresh...

Страница 3: ...s plugged into a GFI GROUND FAULT INTERRUPT OUTLET DO NOT use the device as a bench or table DO NOT place the device directly on structural members Provide vibration isolation in order to minimize ope...

Страница 4: ...VAC 1 Phase 60 Hz Current Draw 4 9 Amps 8 0 Amps 13 2 Amps Energy Factor 4 2 3 5 2 7 Operating Temp 56 F Min 95 F Max 56 F Min 95 F Max 56 F Min 95 F Max Minimum Performance 80 F and 60 RH Water Remo...

Страница 5: ...nded with steel hanger straps or a suitable alternative from structural members unit must be supported from underneath Don t hang from sides or ends Remember to place a drain pan under the unit if it...

Страница 6: ...rt An optional condensate pump kit may be installed if a lift is required to dispose of the condensate The condensate pump kit can be ordered directly from the factory See the optional parts list for...

Страница 7: ...ming instructions for the ventilation timer Advantages of this form of ventilation include 1 Outside air is filtered before entering the building 2 Outside air will be dehumidified before entering if...

Страница 8: ...e of the tee to the air supply of the existing HVAC system A backdraft damper is required in the duct between the 10 tee and the central supply duct to prevent air from being discharged into the basem...

Страница 9: ...ed in central open area of the structure DO NOT locate the return in a bathroom or a kitchen The supply of the Quest Dry should be located in the remote areas of the structure By ducting this way the...

Страница 10: ...contact between yellow and green or brown wires To power an HVAC accessory connect the accessory to the white or red wire and the yellow wire FOR HVAC INSTALLER ONLY P N 4027370 with remote P N 40285...

Страница 11: ...com TS 673 06 11 WARNING Allowing yellow wire to contact red or white wire will destroy the transformer Dehumidifier on Connect yellow and blue wires Fan only on Connect yellow and green or brown wire...

Страница 12: ...del DEH 3000 DEH 3000R remote Operating Voltage 24 VAC Max Current DMP COMP FAN 1 AMP each Humidity Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4...

Страница 13: ...available for the Quest Dry This filter is rated as 90 95 efficient by the ASHRAE Dust Spot test method 52 76 The high efficiency pleated microglass paper filter should be used in conjunction with th...

Страница 14: ...aporator tubes contain liquid refrigerant during normal operation A flooded evaporator should maintain nearly constant pressure and temperature across the entire coil from inlet to outlet The mixture...

Страница 15: ...humidification is being called for 1 Defrost thermostat loose or defective Sec 7 8 2 Low refrigerant charge 3 Dirty air filter s or air flow restricted 4 Excessively restrictive ducting connected to u...

Страница 16: ...sisting of the motor and impeller fan If defective the complete assembly must be replaced 1 Unplug the power cord 2 Remove the cabinet access panel 3 Remove the screw attaching the impeller fan suppor...

Страница 17: ...otors and cause failures The following procedure is effective only if the system is monitored after replacing the compressor to insure that the clean up was complete 1 This procedure assumes that the...

Страница 18: ...Timer The ventilation timer controls the impeller fan and the motorized fresh air damper When the ventilation timer is activated the Quest Dry will circulate the indoor air and bring in fresh air fro...

Страница 19: ...condensate pump kit is available from the factory for use with the Quest Dry Condensate is automatically pumped to a remote location when the water level in the pump s reservoir rises to close the flo...

Страница 20: ...3 4 4032178A 1 2 3 4 BLK 3 WHT 6 A B B A BLK 7 COM COM 24V 24VAC COM BLU YEL GRN RED LINE NEUTRAL CUSTOMER SUPPLIED CONTROL WIRING N O WHT 4 UNIT E BOX 1 59 1413 WHT 4 BLK 1 8 2 3 2 2 2 3 7 5 COM COM...

Страница 21: ...lacement Kit 7 4032224 1 Dry 155 Dry 205 Compressor Replacement Kit 4029568 1 Dry 105 Compressor Overload NOT SHOWN 4029714 1 Dry 155 Compressor Overload NOT SHOWN 4031574 1 Dry 205 Compressor Overloa...

Страница 22: ...Humidity Fan 4024125 1 Control Panel Assembly Ventilation Timer Humidity 4023660 1 Controller Humidity 4023672 1 Duct Damper 6 Diameter Electrically Actuated not shown 4024153 1 Cover for Items 28 29...

Страница 23: ...he door in between the foam installation and the metal side Push down on the plastic door latch and swing door shut Once the door is shut release the door latch Collar Install Remove the 2 round ducts...

Страница 24: ...le means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification u...

Отзывы: