BACnet
T
‐
Stat
User’s
Manual
Rev
1.1,
7/28/11
Page
|
7
available
choices:
System,
Setpoints,
Schedules,
Clock
&
Run.
Choosing
one
of
these
options
will
present
the
available
choices.
Use
the
up/down
arrows
to
cycle
through
the
choices
for
each
field
and
the
center
button
to
accept
the
change
and
move
to
the
next
choice.
Once
you
start
in
one
of
the
program
menus,
you
must
step
through
all
choices
until
the
end
in
order
to
accept
your
changes.
Press
the
center
button
to
accept
the
current
program
value
and
go
on
to
the
next
choice.
The
factory
default
values
are
underlined
below:
NOTE:
Factory
default
for
temperature
readings
is
in
Fahrenheit.
3.4.1
Programming
flow
:
Mon
09:09A
81
F
Cool1
Fan
Auto
Access
Code
11
Program
Choices
System
Program
Choices
Run
Program
Choices
Schedules
Program
Choices
Clock
Program
Choices
Setpoints
Entering
System
Menu
Entering
Run
Menu
Entering
Schedules
Menu
Entering
Clock
Menu
Entering
Setpoints
Menu
Figure
4
‐
Programming
Flow
3.4.2
Sub
Menus
System:This
is
the
menu
for
doing
the
initial
system
setup.
Items
programmed
under
this
menu
are:
HVAC
type:
Conventional
1,
Conventional
2,
Heat
pump
1,
Heat
pump
2,
Gas
heat
1,
Gas
heat
2
Control
Mode:
Auto,
Cool,
Heat,
Off
Occupied
Fan
Mode:
Auto,
On
Unoccupied
Fan
Mode:
Auto,
On
Temperature
Units:
Fahrenheit
or
Celsius
Zone
Sensor
Spot:
On
Board
or
Off
Board
Zone
Temperature
Offset:
‐
9
to
9
(0)
Supply
Sensor
Offset:
‐
9
to
9
(0)
Occupied
Override
Time
0
‐
240
minutes
(factory
default
60)
BACnet
MAC
Address:
1
‐
127
(1)
BACnet
Network
Address:
1
‐
4194
(0)
Baud
Rate:
9,600,
19200,
38400,
57600,
76800