BACnet
T
‐
Stat
User’s
Manual
Rev
1.1,
7/28/11
Page
|
3
Analog Input Object Detail
Supported Properties
Writable?
Property Range Restrictions
Object Identifier
N
N/A
Object Name
N
N/A
Description N
N/A
Object Type
N
N/A
Present Value
N
N/A
Status Flags
N
N/A
Event State
N
N/A
Out of Service
N
N/A
Units N
N/A
Instance Description Writable?
Notes
AI-0
Raw Zone Temp
N
Fahrenheit or Celsius reading of the zone thermistor, directly from
the sensor (no offsets applied).
A reading of -25F indicates an open sensor condition and a reading
of 150F indicates a shorted sensor condition.
AI-1
Raw Supply Air
N
Fahrenheit or Celsius reading of the supply air thermistor, directly
from the sensor (no offsets applied).
A reading of -25F indicates an open sensor condition and a reading
of 150F indicates a shorted sensor condition.
Analog Value Object Detail
Supported Properties
Writable?
Property Range Restrictions
Object Identifier
N
N/A
Object Name
N
N/A
Description N
N/A
Object Type
N
N/A
Present Value
Y (some)
Y
Status Flags
N
N/A
Event State
N
N/A
Out of Service
N
N/A
Units N
N/A
Instance Description Writable?
Units
Limits
Default
Notes
AV-0
MAC Address
Y
None
1..127
1
MS/TP MAC address needs to be
unique in each network. You should
restart the unit after changing the