- 19 -
some special cases, we propose to use ±0.1 °C or ±0.2 °C (factory default)
when a heating/cooling system should be controlled. For humidification/
dehumidification we recommend you use a switching sensitivity of ±1%
(factory default) or ±2%. For more information about switching sensitivity
please refer to Chapter
6
.
7.4. Calibration of the temperature sensor (T CALIB)
The accuracy of the thermometer of the thermostat is ±0,5 °C. The temperature
displayed by the thermostat can be modified by maximum ±3.0 °C / ±6,0
°F compared to the temperature measured by the temperature sensor, in
increments of ±3.0 °C / ±6.0 °F or 0.1 °C / 0.1 °F.
7.5. Calibration of the humidity sensor (H CALIB)
The accuracy of the humidity sensor of the thermostat is ±3% RH.
The relative humidity displayed by the thermostat can be modified by
maximum ±10% compared to the humidity measured by the sensor,
in increments of 1%.
7.6. Setting the humidity limit for cooling (H LIMIT)
When a cooling system including surface cooling is controlled, it is important
that the air in the room must not reach dew point because in this case
Содержание COMPUTHERM Q20