Quantek pilot Series Скачать руководство пользователя страница 25

9

 

Troubleshooting 

 

 

Warning: 

 

Electrocution hazard! Before working on any live elements, pull out the mains plug 

 

respectively switch off the main installation switch! 

 

If a malfunction occurs which might be detrimental to the safety of the users, and 

 

which cannot be eliminated without delay, the operator must be informed and if required 

 

the installation shall be taken out of operation. The installation must be repaired as 

 

soon as possible. 

 

 

Note: 

 

Every troubleshooting procedure which is carried out must be entered into the control booklet! 

9.1

 

Drive mechanism 

No. 

Description 

Cause 

Elimination 

Checking time 

Reaction 

E1 

03 

Encoder 

Channels A+B lost 

Check the encoder connection. 
Check the motor cable. 
The sense of rotation of the motor is not 
in compliance with the rod assembly. 
The door is blocked. 
Check if a jumper has been inserted on 
X106. 

During run. 
 
 

04 

Short-circuit A+B 

05 

Dysfunctions 

06 

Motor cable plugged in 
uncorrectly 

Prior to start-up. 

07 

No channel A 

08 

No channel B 

09 

No channel A+B 

10 

Short-circuit A+B 

E2 

01 

Motor current 

Current too high 

Check the motor cable. 
Check if a jumper has been inserted on 
X106. 

Prior to star-up. 

02 

Current too low 
Jumper missing 

E3 

01 

Cushioning 

Test failed once 

Switch the drive unit to the MANUAL 
operating mode and carefully check if the 
door closes in a cushioned manner. If not: 
replace the hardware. If yes: 
check/correct the friction of the door leaf 
and the prestressing of the closing spring. 

Prior to the closing motion, 
after start-up, and 
subsequently every 24 h. 

02 

Test failed twice. 
Damping defective. 

E4 

01 

Reference 
switchr 

Detected in the open 
position. 

Check the connection and the switching 
point of the reference switch. 
The reference switch must be activated 
in the closed position (switching contact 
open). 

Open position. 

02 

Not detected in the closed 
position. 

Prior to the first setting-up 
run. 

03 

Not detected in open 
position. 

E5 

00 

Power limitation 

Overload of the control. The 
maximum power is restricted. 

Check/correct the friction of the door leaf 
and the pre-stressing of the closing 
spring. 

Permanent. 

 

9.2

 

Operating 

No. 

Description 

Cause 

Elimination 

Checking time 

Reaction 

E10 

01 

Fullteach required 

Parameter Ao, Rod, Invers 
or dAxis changed. 

Carry out a teach. 

Upon changing the 
drive unit configuration. 

02 

Minimum opening angle 
has not been reached. 

Check the locking/electric lock. 

During Teach. 

E11 

01 

Halfteach required 
(Opening) 

Parameter Vo changed. 

Carry out a complete and 
unhindered .opening cycle. 

Upon changing the 
motional parameters. 

02 

Halfteach required 
(Closing) 

Parameter Vc or FSlam 
changed. 

Carry out a complete and 
unhindered .closing cycle. 

E12 

03 

Excessively high current 
consumption during Teach 
in the open position (> 5 A) 

Drive unit pushes against 
the open position stop 
piece or an obstacle. The 
spring tension is possibly 
too high. 

Reduce the opening angle Ao. 
Reduce the spring tension. 

Open position Teach 3 
(E11). 

E14 

01 

Locking/electric lock 

The door leaf got caught in 
the locking/electric lock. 

Check the function of the locking/ 
electric lock. 

When opening from a 
closed position. 

02 

The inverted operation has 
no locking, or the 
interlocking force Fch has 
not been programmed.  

Program/increase the interlocking 
force Fch. 

At the end of the teach-in 
procedure. 

E15 

01 

Obstacle in opening 
direction 

Too many successive 
obstacles have occured. 

Examine the installation. 
Remove the obstacle. 
Move the door leaf to the target 
position. 
 

Permanent. 

H, A 
Restart 
after 60 s 

02 

Number of obstacles within 
60 seconds 

Содержание pilot Series

Страница 1: ...Swing door drive unit FD 10 pilot series Mounting and operating instructions Com no Pos Year of construction Operator Operating place...

Страница 2: ...justments 19 7 1 Motion parameters PARAMETER 19 7 2 Configuration CONFIG 20 7 3 Installation with multiple door leaves Double Door 21 8 Menu navigation 22 8 1 PARAMETER 22 8 2 CONFIG 22 8 3 DOUBLE DOO...

Страница 3: ...anent torque output shaft 56 Nm Short term torque output shaft 165 Nm Distance door hinge Output shaft Lintel mounting 100mm 160mm GSD Lintel depth Normal rods max 250mm Sliding rods pl 50 150 mm pull...

Страница 4: ...tel mounting Lintel depth Option Axle extension Standard none 10 18 36 0548 190 10 10 28 46 0548 191 20 10 38 56 0548 192 30 10 48 66 0548 193 40 10 58 76 0548 194 50 10 68 86 adjust dimensions accord...

Страница 5: ...the consequence that some measures will change 28mm and thus need to be adapted accordingly Lintel depth mm Max door opening angle 0 50 105 51 100 100 100 150 95 Option Axle extension Standard none 33...

Страница 6: ...thus need to be adapted accordingly Option Axle extension Standard none 10 18 40 0548 190 10 10 28 50 0548 191 20 10 38 60 0548 192 30 10 48 70 0548 193 40 10 58 80 0548 194 50 10 68 90 adjust dimensi...

Страница 7: ...e The fixing holes of the drive module must always be on the side facing the door hinge 2 Fasten the chassis by means of six screws M6 to lintel 3 Fasten the drive module by means of four screws M5 to...

Страница 8: ...nction the arrow with description PULL points to the chassis 4 Route the reference switch cable the mains cable and program switch cable on the side cover below the drive module 5 Screw earth cable to...

Страница 9: ...le the reference switch cable and program switch cable into the control unit c Fasten the control unit by means of three screws M5 to the chassis d For sliding rods with pulling function first release...

Страница 10: ...ace side of the control unit 7 If required route the cable for sensors motor lock button etc below the drive module and the control unit and connect them 8 Mount the selected rods according to drawing...

Страница 11: ...slight hit onto the screw heads b Open the door leaf to the desired maximum opening angle c Turn the stop piece till it stops and retighten the screws 6Nm 1 Open the door leaf and let it close by mea...

Страница 12: ...t the power supply into the mains supply terminal b Fasten the power supplies with the strain relief clip onto the side cover c Insert mains cable into the mains supply terminal 3 Fasten both side cov...

Страница 13: ...er commissioning a Degrease the glued surface on the covering b Remove white sticker protective sheet D c Affix the stencil B with the Logo C on the lower right corner of the covering and press on wel...

Страница 14: ...only act upon the Master single leaf operation Opening elements connected to Slave act upon the Master as well as on the Slave bi parting operation The safety elements SER and SES are connected to th...

Страница 15: ...desired time lag of the closing angle Note In cases where a mechanical closing sequence regulator is used start with a AcSeq of 90 6 Configuration of the Slave drive unit DubleD SlaveA AoSeq desired t...

Страница 16: ...tic closing upon expiration of the adjustable hold open time MANUAL position 0 The drive mechanism and the control elements are switched off The door leaf can be manually opened The door leaf is close...

Страница 17: ...ward once the display direction is switched to a readable position 3 Programming the type of rods Rod Move the joystick to the left to the right Validate the correct type of rods by means of OK In the...

Страница 18: ...ed closing direction 11 Upon completion of the first learning run the following message is displayed 12 The display should immediately supply the following information 13 By means of an opening comman...

Страница 19: ...Door rectification time time press close 0 0 4 0 s 0 5 s FLock Pressing force during locking force lock only effective if TLock is 0 0 0 7 0 A 2 0 A FSlam Accelerating function force slam 0 10 OFF FWi...

Страница 20: ...e if relay PCB 0 is plugged in OPEN RC 0 3 Parametrizable relay output 3 on optional PCB 1 only visible if relay PCB 0 is plugged in ERROR RC 0 4 Parametrizable relay output 4 on optional PCB 1 only v...

Страница 21: ...eD Closing sequence role Master Slave and interlock side A B OFF MastrA SlaveA MastrB SlaveB OFF AoSeq Current delay angle for opening sequence control Slave only visible if DubleD is active 0 110 20...

Страница 22: ...etection EMY Emergency element PUGO Push and Go 2nd display line at the bottom left hand side the presently enabled operating mode is displayed a frame around the symbol indicates the overriding opera...

Страница 23: ...s value is memorized 8 5 ERROR ACTIVE Pending active errors The pending active errors are displayed in a list This list is updated at the end and the latest additions appear during the next passage A0...

Страница 24: ...any other joystick movement The setting up procedure can be canceled by means of the D BEDIX C key Setting of the opening angle Ao During the first setting up run the drive unit moves to the open posi...

Страница 25: ...tching point of the reference switch The reference switch must be activated in the closed position switching contact open Open position F 02 Not detected in the closed position Prior to the first sett...

Страница 26: ...resp under voltage E32 01 24 V Safety Over resp under voltage Overload short circuit 24 VDC onto terminals X105 or X107 E33 01 24 V E Lock Error Over resp under voltage Overload short circuit 24 VDC...

Страница 27: ...ct the cabling of the opening elements LED SE safety element yellow is not lighted LED OE opening command blue is not lighted despite the active opening element The opening command is not evaluated Ch...

Отзывы: