1.03 DELIVERy AND HANDLING
A. Unit shall be delivered to job site fully assembled, and charged with refrigerant and oil
by the manufacturer. (Contractor is responsible for providing and installing the refriger-
ant charge including the charge required for the field installed interconnecting piping.
Chiller components shall ship with a dry nitrogen holding charge – remote Evaporator
option).
B. Unit shall be stored and handled per manufacturer’s instructions.
PART 2 - PRODUCTS
2.01 CHILLER MATERIALS AND COMPONENTS
A. General: install and commission, as shown on the schedules and plans, factory assem-
bled, charged, and tested air cooled scroll compressor chiller(s) as specified herein.
Chiller shall be designed, selected, and constructed using a refrigerant with flamma-
bility rating of “1”, as defined by ANSI/ASHRAE STANDARD - 34 Number Designation
and Safety Classification of Refrigerants. Chiller shall include, but is not limited to a
complete system with a single refrigerant circuit 35 tons (123kW) and below, and not
less than two refrigerant circuits above 35 tons (123kW), scroll compressors, direct
expansion type evaporator, air-cooled condenser, refrigerant, lubrication system, inter-
connecting wiring, safety and operating controls including capacity controller, control
center, motor starting components, and special features as specified herein or required
for safe, automatic operation.
B. Cabinet: External structural members shall be constructed of heavy gauge, galvanized
steel coated with baked on powder paint which, when subject to ASTm B117, 1000
hour, 5% salt spray test, yields minimum ASTm 1654 rating of “6”. Add Wire Panels
of heavy gauge, welded wire-mesh, coated to resist corrosion, to protect condenser
coils from incidental damage and restrict unauthorized access to internal components.
factory installed.
2.02 COMPRESSORS
Compressors: Shall be hermetic, scroll-type, including:
1. Compliant design with axial and radial sealing.
2.
Refrigerant flow through the compressor with 100% suction cooled motor.
3. large suction side free volume and oil sump to provide liquid handling capability.
4. Compressor crankcase heaters to provide extra liquid migration protection.
5. Annular discharge check valve and reverse vent assembly to provide low pressure
drop, silent shutdown and reverse rotation protection.
6. initial oil charge.
7. oil level sight glass.
8. Vibration isolator mounts for compressors.
9. Brazed-type connections for fully hermetic refrigerant circuits.
Guide Specifications (Cont'd)
Содержание QTC2015T
Страница 1: ...LD18973a form QTC2 EG1 515 Model QTC2 Air Cooled Scroll Chillers 15 46 TON 53 162 kW 60 Hz R 410A...
Страница 4: ...QUANTECH FORM QTC2 eg1 515 4 This Page Intentionally Left Blank...
Страница 12: ...QUANTECH FORM QTC2 eg1 515 12 This Page Intentionally Left Blank...
Страница 25: ...FORM QTC2 eg1 515 QUANTECH 25 Unit Dimensions English Cont d QTC2025T LD18674...
Страница 33: ...FORM QTC2 eg1 515 QUANTECH 33 45 1 8 18 1 2 LD18682 Unit Dimensions English Cont d QTC2045T...
Страница 47: ...FORM QTC2 eg1 515 QUANTECH 47 Unit Dimensions Metric Cont d QTC2045T 424 LD18702...
Страница 57: ...FORM QTC2 eg1 515 QUANTECH 57 Power Wiring LD18707...
Страница 58: ...QUANTECH FORM QTC2 eg1 515 58 LD18744 Power Wiring Cont d...
Страница 59: ...FORM QTC2 eg1 515 QUANTECH 59 Power Wiring Cont d LD18746...
Страница 60: ...QUANTECH FORM QTC2 eg1 515 60 Factory wired with optional transformer LD03611 Control Wiring...