PART 1 – GENERAL
1.01 SCOPE
A. The requirements of the General Conditions, Supplementary Conditions, division 1,
and drawings apply to all Work herein.
B. Provide microprocessor controlled, multiple-scroll compressor, air-cooled, liquid chill-
ers of the scheduled capacities as shown and indicated on the drawings, including but
not limited to:
1. Chiller package
2. Electrical power and control connections
3. Chilled water connections
4. Change of refrigerant oil (for factory mounted evaporator) or (evaporator shipped
separately for field installation and piping by contractor)
1.02 QUALITy ASSURANCE
A.
Products shall be Designed, Tested, Rated and Certified in accordance with, and in
-
stalled in compliance with applicable sections of the following Standards and Codes:
1. ANSi/AShrAE Standard 15 – Safety Code for mechanical refrigeration
2.
ASHRAE 90.1– Energy Efficiency compliance.
3. ANSi/NfPA Standard 70 – National Electrical Code (N.E.C.).
4. ASmE Boiler & Pressure Vessel Code, Section Viii, division 1.
5. Ahri Standard 550/590 – Positive displacement Compressors and Air Cooled ro-
tary Screw Water-Chilling Packages.
6. Conform to intertek Testing Services, formerly ETl, for construction of chillers and
provide ETl/cETl listing label.
7. manufactured in facility registered to iSo9002.
8. oShA - occupational Safety and health Act
B. factory Test: Chiller shall be pressure-tested, evacuated and fully charged with refrig-
erant and oil, and shall be factory operational run tested with water flowing through the
vessel.
C. Chiller manufacturer shall have a factory trained and supported service organization
that is within a 50 mile radius of the site.
d. manufacturer shall Warrant all equipment and material of its manufacture against de-
fects in workmanship and material for a period of one year from date of initial start-up
or eighteen (18) months from date of shipment, whichever occurs first.
Guide Specifications
Содержание QTC2015T
Страница 1: ...LD18973a form QTC2 EG1 515 Model QTC2 Air Cooled Scroll Chillers 15 46 TON 53 162 kW 60 Hz R 410A...
Страница 4: ...QUANTECH FORM QTC2 eg1 515 4 This Page Intentionally Left Blank...
Страница 12: ...QUANTECH FORM QTC2 eg1 515 12 This Page Intentionally Left Blank...
Страница 25: ...FORM QTC2 eg1 515 QUANTECH 25 Unit Dimensions English Cont d QTC2025T LD18674...
Страница 33: ...FORM QTC2 eg1 515 QUANTECH 33 45 1 8 18 1 2 LD18682 Unit Dimensions English Cont d QTC2045T...
Страница 47: ...FORM QTC2 eg1 515 QUANTECH 47 Unit Dimensions Metric Cont d QTC2045T 424 LD18702...
Страница 57: ...FORM QTC2 eg1 515 QUANTECH 57 Power Wiring LD18707...
Страница 58: ...QUANTECH FORM QTC2 eg1 515 58 LD18744 Power Wiring Cont d...
Страница 59: ...FORM QTC2 eg1 515 QUANTECH 59 Power Wiring Cont d LD18746...
Страница 60: ...QUANTECH FORM QTC2 eg1 515 60 Factory wired with optional transformer LD03611 Control Wiring...