3.1.  Extended specification and technical specifications

*1.

 The maximum output power decreases as a percentage of 

220V. At 220V and above the power is 100%, below 220V it is 
calculated by the following formula [nput_voltage / 220 * regu-
lator_power = maximum_output_power].

*2.

 The Quant voltage regulator supports the overload func-

tion  to  provide  starting  currents  for  motors,  pumps,  etc.,  and 
also  monitors  the  state  for  short  circui. The  specification  for 
the operating time in the overload mode is specified in the tech-
nical specifications in lines 8 and 9. 

*3.

 It is forbidden to connect the generator directly to the regu-

lator input, as this can damage the generator and the regulator. 
The use of the generator and regulator together is allowed only 
with the use of the generator integration unit. This is described 
in more detail on the website in the article “Quant and reserve 
power supply. Generator integration unit”.

*4.

  The Quant voltage regulator limits the input and output 

current taking into account double overload. If the value is ex-
ceeded by 200% of the nominal power, the regulator will turn off 
in 1 second. Thanks to the limiting function, the regulator moni-
tors short circuits on the line and prevents uncontrolled current 
consumption. This is described in more detail in paragraph 5 
"Device and principle of operation".

*5.

    Quant  voltage  regulator  provides  starting  currents  load 

that can create a short circuit on the line, for example motors, 

compressors,  refrigerators,  etc.,  thus  the  stabilizer  does  not 
switch  off,  and  continues  the  regular  work.  While  providing 
starting currents, a short-term reduction of the input voltage is 
possible while maintaining the 220V / 230V output voltage to 
the phase. 

ATTENTION!

 If the input grid does not have enough 

power and is not able to deliver the required current to 

the regulator, it will start to settle down. If the input volt-

age drops below 80V, the regulator will turn off due to 

low voltage. This is called a "network drop" and is not a 

malfunction of the device.

99

QUANT-9  

 Automatic voltage regulator, one-phase

 

 

Содержание QUANT-9

Страница 1: ...QUANT 9 Made in Ukraine 27 1 22049061 001 2021 OUR MERIT SAFE VOLTAGE Automatic voltage regulator one phase Operation manual...

Страница 2: ...ect outlet in the house or in the perfect regulator Therefore in fact the development of QUANT regulators made anew from circuitry algorithms and software list of equipment to design and construction...

Страница 3: ...3 QUANT 9 Automatic voltage regulator one phase Find out all about QUANT stabilizers on the channel https www youtube com channel UCWVXbv4Spwr5yUb U9fvMWw OPERATION MANUAL...

Страница 4: ...ations 8 3 1 Extended specification and technical specifications 9 4 Scope of delivery 10 5 Device and principle of operation 10 6 Installation and connection 13 7 Regulator operation 16 8 Regulator o...

Страница 5: ...5 5 QUANT 9 Automatic voltage regulator one phase...

Страница 6: ...ined space box cabinet i e in conditions of insuffi cient ventilation Do not operate the regulator in direct sunlight or in atmospheric precipitation 1 3 General safety precautions keep children away...

Страница 7: ...or before the overvoltage pulse reaches the load Most dangerous situations are solved without switching off the regulator so that the load receives a clean filtered voltage for phase 220V 230V 50Hz an...

Страница 8: ...perating frequency range Hz 45 50 Operating temperature range 5 40 Humidity range 0 80 Delay before switching on sec 6 Mounting method Hinged Protection index 20 Cooling Forced Low noise Number of pha...

Страница 9: ...tage regulator limits the input and output current taking into account double overload If the value is ex ceeded by 200 of the nominal power the regulator will turn off in 1 second Thanks to the limit...

Страница 10: ...ing from the grid The input voltage from the grid is fed through the input circuit breaker to the input of the regulator circuit initially supplies a low power auxiliary power supply and the motherboa...

Страница 11: ...or its input and output filters reactive pow er compensator for normal operation mode which includes any surges and spikes in voltage within the acceptable regu lation range of the device overvoltage...

Страница 12: ...12 REGULATOR CIRCUIT QUANT 9 Automatic voltage regulator one phase...

Страница 13: ...fixed It is desirable to use special equipment or check the site plan check the site plan If you are not sure if there are any power lines in this If you are not sure if there are any power lines in...

Страница 14: ...on the back panel fit into the slots of the suspension bracket Check the accuracy of the fitting by trying to move each regulator slightly holding back from a possible fall left right and pulling dow...

Страница 15: ...15 15 VOLTAGE REGULATOR INSTALLATION CHART N L Electricity meter 220V socket Stabilizer Automaton QUANT 9 Automatic voltage regulator one phase...

Страница 16: ...ansformers in the presence of both smooth and sudden mains voltage spikes at the regulator input as long as they are within the allowable regulation range the output voltage of the regulator remains u...

Страница 17: ...vailable as soon as the device is turned on They are switched with the Left and Right buttons below the screen left and right buttons Information screens without settings MAIN SCREEN It is displayed b...

Страница 18: ...hin 3 and switching from 220V to 230V and back It is also possible to test coolers set the speed to check the quality of the coolers the absence of unnecessary noise To enter the second level menu lon...

Страница 19: ...g the RPMs To exit the menu press the middle button again You can safely move further on the menu the device will return the cooling sys tem to normal mode The value is not saved SCREEN NO 7 TECHNICAL...

Страница 20: ...on SCREEN NO 11 MAXIMUM INPUT VOLTAGE The maximum allowable voltage at the input of the regulator If this threshold is exceeded the regulator will shut down SCREEN NO 12 TURN ON DELAY Shows how many s...

Страница 21: ...Changing this parameter may cause the regulator to shut down immediately after switching on if the mains voltage is steadily increased It is not recommended to change this parameter without consulting...

Страница 22: ...r voltages In addition it is guaranteed that neither one nor the other affect the load if they do not exceed the stiffness level 4 according to DSTU protection against switching overvoltag es is made...

Страница 23: ...e load but the grid will not be able to be in an emergency for a long time and the supply of voltage may stop sooner or later WARNING If the regulator input circuit breaker trips out the regulator pro...

Страница 24: ...quant ua January 2022 OUR MERIT SAFE VOLTAGE Automatic voltage regulator one phase...

Отзывы: