background image

Legal 

 

www.qualitrolcorp.com

 

©2010 QUALITROL

®

 Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice. 

All trademarks are properties of their respective companies, as noted herein. IST-103-1-EN. 

Information in this document is subject to change without notice. This document is provided to purchasers of 
QUALITROL

®

 products for use in the installation, operation and servicing of such products. No other use, nor any 

reproduction, distribution or the making of any derivatives of this document is authorized, without the express prior written 
permission of Qualitrol. 
QUALITROL

®

 endeavors to ensure the accuracy and quality of its published materials; however, no warranty, expressed 

or implied, is provided. QUALITROL

®

 disclaims any responsibility or liability for any direct or indirect damages resulting 

from the use of the information in this manual or products described in it. Mention of any product or brand does not 
constitute an endorsement by QUALITROL

®

 of that product or brand.  

This document was originally composed in English and was subsequently translated into other languages. The fidelity of 
subsequent translations cannot be guaranteed. In case of conflict between the English version and another language 
version, the English version takes precedence. 

Содержание AKM 34/Gen2 OTI

Страница 1: ...Instruction Manual www qualitrolcorp com IST 103 1 EN AKM 345 Gen2 Oil Temperature Indicator AKM OTI Type 34 Winding Temperature Indicator AKM WTI Type 35 Document ID IST 103 1 EN...

Страница 2: ...ed without the express prior written permission of Qualitrol QUALITROL endeavors to ensure the accuracy and quality of its published materials however no warranty expressed or implied is provided QUAL...

Страница 3: ...g the AKM345 Double Gradient Option 6 5 3 1 Background 6 5 3 2 Wiring Recommendations 6 5 4 Using the 5 Amp Internal CT Option 6 5 5 Setting the Matching Resistance 7 5 5 1 Method A 7 5 5 2 Method B 7...

Страница 4: ...ount 10 Figure 8 Cover Hinge Side View 11 Figure 9 Front Cover Removal 11 Figure 10 Switch Selection 12 Figure 11 2 to 4 Switches w Optional Heater and Remotes 13 Figure 11 1 2 to 4 Switches w Optiona...

Страница 5: ...ontents Contents iii www qualitrolcorp com Figure 15 5 4 20mA 0 5V DC Suggested Wiring TD119 5 24 Figure 15 6 4 20mA 0 10V DC Suggested Wiring TD119 5 25 Figure 15 7 Suggested Wiring TD66 CU10 PT100 2...

Страница 6: ...nsion space in oil filled pockets The non vibration mountings included must be used to prevent mechanical wear out caused by transformer vibrations Installation shall prevent instrument casing tempera...

Страница 7: ...alarm set point as described above Adjust the multi turn adjusting screw located beneath the switch scale plate fully clockwise At this point the differential will be set at 5 C When turned fully anti...

Страница 8: ...D76 TD50 5 Amp Max Cont Input at 100 Load 2 2 A from CT 2 65 A from CT 5 0 A from CT Adj Range 0 80 of Input Current from CT 45 85 of Input Current from CT 0 35 of Input Current from CT Insulation 2kV...

Страница 9: ...value 4 Connect a multi meter Example Fluke set for resistance measurement to the terminals 5 5 inside the WTI 5 Adjust the matching resistance TD50 or TD76 until you reach the required resistance val...

Страница 10: ...djustment of Heating Current Keep cover mounted feed a stable current and wait 45 min before reading winding temperature Gradient C for bulb type 11 12 15 and 18 10 12 14 16 18 20 22 24 26 28 30 Oil t...

Страница 11: ...ater current Switching between the heater currents is performed external to the thermometer 5 3 2 Wiring Recommendations The potentiometers are wired to the 56 and 57 terminal block positions The CT i...

Страница 12: ...et R5 5 value which will provide the desired heater current see Section 5 1 instructions Re connect the white separable connector After the matching resistance has been set and the white connector is...

Страница 13: ...been set and the white connector is re mated the winding simulation input current is wired to the terminal block at the 5 5 positions as shown TD50 POT HEATER CT BLK OUT 2 2A BLK WHT IN 5A WHT WHITE C...

Страница 14: ...qualitrolcorp com 6 Mounting Styles and Dimensions 6 1 Seismic Mount Figure 5 Siesmic Mount Special mounting for high amplitude low frequency conditions 6 2 Universal Mount Figure 6 Universal Mount A...

Страница 15: ...M 345 Gen2 Instruction Manual Rev No ECN 27992 10 www qualitrolcorp com 6 3 Anti Vibration Standard Mount Figure 7 Anti Vibration Standard Mount Standard mounting highest instrument isolation availabl...

Страница 16: ...Removal 4 09 104 11 93 303 3 68 93 11 88 302 Figure 8 Cover Hinge Side View Figure 9 Front Cover Removal Cable glands M25 max 3 and M20 max 2 After unlocking the front cover lift the front cover up fu...

Страница 17: ...A 125 VDC 0 5 A 0 05 A 250 VDC 0 25 A 0 03 A GW STANDARD SWITCH MBO GOLD DPDT Figure 10 Switch Selection MBO Magnetic Blow Out high DC switching minimum Electrical Operations 100 000 Cycles all other...

Страница 18: ...www qualitrolcorp com 9 Terminal Block Arrangements Figure 11 2 to 4 Switches w Optional Heater and Remotes Figure 11 1 2 to 4 Switches w Optional Heater and Remotes TD50 5 Amp Figure 11 2 2 to 4 Swi...

Страница 19: ...Rev No ECN 27992 14 www qualitrolcorp com Figure 12 5 to 6 Switches only Figure 13 5 to 6 Switches w Optional heater and Remotes For options not shown please consult Configuration Form or contact QUA...

Страница 20: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 15 www qualitrolcorp com 10 Pocket Well Installation Figure 14 Pocket Well Installation...

Страница 21: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 16 www qualitrolcorp com 11 Probe Types...

Страница 22: ...into white after saturation If condensation is occurring inside the instrument replacement of the capsules will be necessary part number 47126 12 2 Mountings with Rubber Dampers Seismic Type and Univ...

Страница 23: ...r dial measurement range Load 500 max at 24V DC User adjustable output can be used to calibrate output directly to load consult factory Accuracy Relative to local indication 2 C Ambient temperature 40...

Страница 24: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 19 www qualitrolcorp com Figure 15 4 20mA Suggested Wiring TD111...

Страница 25: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 20 www qualitrolcorp com Figure 15 1 0 1mA Suggested Wiring TD119 1...

Страница 26: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 21 www qualitrolcorp com Figure 15 2 0 5mA Suggested Wiring TD119 2...

Страница 27: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 22 www qualitrolcorp com Figure 15 3 0 10mA Suggested Wiring TD119 3...

Страница 28: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 23 www qualitrolcorp com Figure 15 4 0 20mA Suggested Wiring TD119 4...

Страница 29: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 24 www qualitrolcorp com Figure 15 5 4 20mA 0 5V DC Suggested Wiring TD119 5...

Страница 30: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 25 www qualitrolcorp com Figure 15 6 4 20mA 0 10V DC Suggested Wiring TD119 5...

Страница 31: ...AKM 345 Gen2 Instruction Manual Rev No ECN 27992 26 www qualitrolcorp com Figure 15 7 Suggested Wiring TD66 CU10 PT100...

Страница 32: ...LITROL produces thousands of different types of products on demand each customized to customers unique requirements QUALITROL Field Services QUALITROL provides on site commissioning start up and compr...

Отзывы: