R
Page 12
7004-187F September 1, 2008
Yosemite Wood Stove
Thimble Assembly:
12" (305mm) of brick
separation between
clay liner and
combustibles.
Fireclay liner 5/8"
(16mm) Minimum
or Equivalent.
Sill support
Header
Wood Stud 2"
(51mm)
Clearance
from chimney
wall
Fireclay liner 5/8"
(16mm) Minimum
or Equivalent.
MASONRY CHIMNEY
FIGURE 12A
F
or optimal performance, masonry chimneys used
to vent this appliance should be lined with a 6 inch
stainless steel liner. Installations into a clay flue without
a stainless steel liner may reduce draw which affects
performance, cause the glass to darken and produce
excessive creosote.
Ensure that a masonry chimney meets the minimum
standards of the National Fire Protection Association
(NFPA) Standard 211. It must have at least a 5/8"
(16mm) fire clay liner or a listed chimney liner system.
See Figure 12A
. Make sure there are no cracks, loose
mortar or other signs of deterioration and blockage. It
is best to have the chimney inspected by a professional
and be sure to have the chimney cleaned before the
stove is installed and operated.
The flue should be checked to determine that it is not
too large for the stove. NFPA 211 allows the cross-
sectional area of the flue to be no more than 3 times
the cross-sectional area of the flue collar of the stove
(28 x 3 = 84 square inches). It is recommended that a
chimney with a larger diameter than 6 inches (152mm)
be relined, since the oversized flue can cause poor
performance and contribute to the accumulation of
creosote. (See
page 11
for more information about
troubleshooting draft problems).
CAUTION! DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
When connecting the stove through a combustible wall to
a masonry chimney, special methods are needed. There
are several ways to make this connection, including
the construction of a masonry thimble. In Canada, this
installation shall conform to CAN/CSA-B365. Check with
your local building authorities or consult the National Fire
Protection Association (NFPA 211). Refer to
Figure 13B
(page 13) and Figures 14A & 14B (page 14).
WARNING! IF INSTALLING THIS MODEL TO A MASONRY CHIMNEY, ALWAYS BE SURE THE CHIMNEY IS IN GOOD
CONDITION AND THAT IT MEETS THE MINIMUM STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION
(NFPA) STANDARD 211.
THIS APPLIANCE IS MADE WITH A 6 INCH (152mm) DIAMETER CHIMNEY CONNECTOR AS THE FLUE COLLAR ON THE
UNIT. CHANGING THE DIAMETER OF THE CHIMNEY CAN AFFECT DRAFT AND CAUSE POOR PERFORMANCE. IT IS NOT
RECOMMENDED TO USE OFFSETS OR ELBOWS AT ALTITUDES ABOVE 4000 FEET ABOVE SEA LEVEL OR WHEN THERE
ARE OTHER FACTORS THAT AFFECT FLUE DRAFT. SEE PAGE 11.