Page 18
7075-205
April 29, 2013
R
Voyageur Grand
*You will need to add additional clearances to these
dimensions for your specific installation. Also allow suf
-
ficient clearance if you are installing an outside air kit.
Quadra-fire Voyageur Grand ACC does not require a
insulating Floor Protector, as they are tested and comply
with the minimum Floor Protector requirements
of
AS/NZS 2918:2001.
NOTE: HEAT SHIELD REQUIREMENTS FOR HEAT SENSITIVE WALLS. Clearances may be reduced by provision of
an appropriately located heat shield refer to
AS/NZS 2198:2001 3.2.3
B. Clearances to Combustibles (Cont’d)
Required Protection
Suggested Protection
NOTE: Keep Ashlip
Clear of Ashes
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having juris
-
diction
Fire Risk
• Comply with all minimum clearances to
combustibles as specified.
• Failure to comply may cause house fire.
WARNING
Figure 14.2
NOTE: Hearth Rug may be used in Suggested Area
Figure 14.1
Location
Millimeters
A
Rear Width
610
B
Depth
457
C
Height
610
D
Front Width
835
A
B
C
D
Figure 14.3
C. Minimum Opening for Masonry & Factory
Built Fireplaces
2 - 15mm layers of compressed
cement sheets with a thermal
conductivity of 0.5 W/m
˚
K.
127mm or more from bottom of
unit, ember protection only
required