Page 10
7014-188B
February 3, 2010
R
CB1200-I Pellet Insert
R
R
A
B
C
D
D. Minimum Opening for Masonry and Zero
Clearance Fireplaces for Built-In Using
Rear Shroud
SIDE
W
AL
L
MANTEL
D
C
E
A
B
Face Trim
Inches
Millimeters
A Louvers to combustible
side wall
6
153
B
Insert top to mantel
12
305
C Top to Face Trim
3
76
D
Hearth Extension - Front
6
153
E Hearth Extension - Sides
8
203
Inches
Millimeters
A Rear Width
22
558
B
Depth
15-1/2
393
C
*
Height - Top Vent
25-1/2
647
Height - Rear Vent
22-1/2
571
D
Front Width
29-1/4
743
Figure 10.1
Figure 10.2
C. Minimum Clearances To Combustibles for
Masonry and Zero Clearance Fireplaces
*
The size of your floor protector choice must be added to
this dimension. If using Quadra-Fire floor protector, Part
811-0730, allow 1-1/2 inches (38mm).
NOTE
: A Quadra-Fire floor protector (Part 811-0730) is
available through your dealer to be used as a floor protec
-
tor for the section under the insert body only. Floor protec
-
tion to front and sides of insert unit must be supplied in
addition to this part.
F. Floor Protection
1. Zero Clearance Installations*
It is necessary to install a floor protection of non-combus
-
tible material with a R value of 3.0 (1 inch [25mm] minimum
thickness with a “k” value of 0.58) or a 1 inch (25mm) air
space between insert base and hearth.
2. Non-Zero Clearance Installations*
A non-combustible floor protector is required with a mini
-
mum R value of 3.0 (1 inch [25mm] minimum thickness with
a “k” value of 0.58) extending 6 inches (153mm) in front of
the insert and 8 inches (203mm) to each side of the door
opening.
* See alternate floor protection worksheet.
E. Masonry Minimum Opening
Location
Inches
Millimeters
A Rear Width
22
558
B
Depth
13
330
C Height - Top Vent
19-1/2
495
D
Front Width
29-1/4
743
A
B
C
D