Quadra-Fire • QVI-30FB • 2020-900 Rev. H • 9/07
16
Step 2. Positioning, Leveling, and
Securing the Insert
• Place the insert into position.
• Level the insert from side to side and from front to back.
Use the leveling legs if necessary to set each corner of
the base. The levelling legs are mounted behind the fan
cover plate. For location of fan cover plate, see Figure
11 on page 17.
!
!
Step 3. The Gas Control System
WARNING: THIS UNIT IS NOT FOR USE WITH
SOLID FUEL.
These models use a standing pilot ignition type of gas con-
trol system.
Standing Pilot Ignition System
This system includes millivolt control valve, standing pilot,
thermopile/thermocouple flame sensor, and piezo ignitor.
WARNING: 110-120 VAC MUST NEVER BE
CONNECTED TO A CONTROL VALVE IN A
MILLIVOLT SYSTEM.
STANDING PILOT
Figure 6. Gas Controls System
Step 4. The Gas Supply Line
NOTE: Have the gas supply line installed in accordance
with local building codes by a qualified installer
approved and/or licensed as required by the locality.
(In the Commonwealth of Massachusetts installation
must be performed by a licensed plumber or gas
fitter).
NOTE: Before the first firing of the fireplace, the gas
supply line should be purged of any trapped air.
NOTE: Consult local building codes to properly size
the gas supply line leading to the 1/2 inch (13 mm)
hook-up at the unit.
This gas fireplace is designed to accept a 1/2 inch
(13 mm) gas supply line. To install the gas supply line:
• A listed (and Commonweatlh of Massachusetts approved)
1/2 inch (13mm) tee-handle manual shut-off valve and a
listed flexible gas connector are connected to the 1/2
inch (13mm) inlet of the control valve.
NOTE:
If substi-
tuting for these components, please consult local codes
for compliance.
• Locate the gas line access hole in the outer casing of
the fireplace.
• Insert the gas supply line through the gas line hole and
connect it to the shut-off valve.
• When attaching the pipe, support the control so that the
lines are not bent or torn.
• After the gas line installation is complete, all connec-
tions must be tightened and checked for leaks with a
commercially-available, non-corrosive leak check solu-
tion. Be sure to rinse off all leak check solution following
testing.
WARNING: DO NOT USE AN OPEN FLAME TO
CHECK FOR GAS LEAKS.
!
Figure 7. Gas Supply Line
Remote Control
The receiver for the remotes must be installed
BETWEEN
the base pan of the insert and the firebox of the wood-burn-
ing fireplace (see photo below).
EXISTING BOTTOM
OF FIREPLACE
REMOTE
RECEIVER
UNIT
EXISTING SIDE
REFRACTORY
GAS
SHUT-OFF
FLEXIBLE
GAS LINE
CONTROLS