8
7062-197B
February 8, 2016
Explorer I
B. Clearances to Combustibles
BACKWALL / SIDEWALL
A
B
C
D
F
CORNER INSTALLATION
E
C
ALCOVE TOP VIEW
G
A
ALCOVE SIDE VIEW
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having jurisdiction
Fire Risk.
• Comply with all minimum clearances to
combustibles as specifi ed.
• Failure to comply may cause house fi re.
WARNING
G
STOVE TO CEILING
CLEARANCE
H*
8”
(204mm)
24”
(610mm)
53-1/2”
(1359mm)
MANTEL
12” MAX
HORIZONTAL THROUGH WALL
TOP AND SIDE VIEW
11”
(280mm)
NOTE: A, C and F measure-
ments are to center of fl ue
A
B
C
D
E
F
G
H*
Vertical Install Through Ceiling And Alcove
SINGLE WALL PIPE
17 [432]
12-1/2 [318]
24 [607]
11 [279]
7-1/2 [191]
18 [457]
53-1/2
[1359]
*
DOUBLE WALL PIPE
13-1/2 [343]
9 [229]
23 [584]
10 [254]
3 [77]
13-1/2 [343]
53-1/2
[1359]
*
Horizontal Install Through Back Wall
SINGLE & DOUBLE
WALL PIPE
N/A
8 [203]
24 [607]
11 [279]
N/A
N/A
53-1/2
[1359]
*
90
°
Elbow Off The Top Of The Appliance, Then Through Back Wall
SINGLE WALL PIPE
17 [432]
12-1/2 [318]
24 [607]
11 [279]
N/A
N/A
53-1/2
[1359]
18 [457] **
DOUBLE WALL PIPE
12-1/2 [318]
8 [203]
23 [584]
10 [254]
N/A
N/A
53-1/2
[1359]
18 [457]
INSTALLATION: ALCOVE
- Six inch (6”) [152] diameter listed DOUBLE WALL air insulated connector pipe with UL 103 HT listed factory-built Class
“A” chimney, or a masonry chimney. (Mobile Home must be equipped with a spark arrestor.) Maximum depth of Alcove shall be no more than 48”
[1220] with a minimum height of 84” [2134] to top of appliance, and the referenced clearances. Canada must comply with CAN/ULC-S269 M87 for
the 650° factory built chimney
* Follow Pipe Manufacturer’s clearances
** Acceptable per NFPA 211