background image

BODEGA BAY WOOD INSERT

Page 6

  August 20, 2008

435-1320B

IF INSTALLING THIS MODEL TO A MASONRY CHIMNEY, ALWAYS BE SURE THE CHIMNEY IS IN GOOD CONDITION AND 

THAT IT MEETS THE MINIMUM STANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) STANDARD 211.  

A FACTORY BUILT CHIMNEY MUST BE 6 INCH (152mm) UL 103 HT AND ULC S629.

THIS APPLIANCE IS MADE WITH A 6 INCH (152mm) DIAMETER CHIMNEY CONNECTOR AS THE FLUE COLLAR ON THE 

UNIT.  CHANGING THE DIAMETER OF THE CHIMNEY CAN AFFECT DRAFT AND CAUSE POOR PERFORMANCE.  IT IS NOT 

RECOMMENDED TO USE OFFSETS OR ELBOWS AT ALTITUDES ABOVE 4000 FEET ABOVE SEA LEVEL OR WHEN THERE 

ARE OTHER FACTORS THAT AFFECT FLUE DRAFT.T  SEE PAGE 5.

CAUTION:  THIS APPLIANCE IS HOT WHILE IN OPERATION AND MAY REMAIN SO UP TO 40 MINUTES AFTER THERE 

IS NO FUEL IN THE FIREBOX.   IF THIS APPLIANCE IS IN A HIGH TRAFFIC AREA OR CHILDREN MAY BE NEAR, IT IS 

RECOMMENDED THAT YOU PURCHASE A DECORATIVE BARRIOR TO GO IN FRONT OF THE APPLIANCE.

ALTERNATE FLOOR PROTECTION WORKSHEET

How to determine if alternate floor protection materials are acceptable:

All floor protection must be non-combustible (i.e., metals, brick, stone, mineral fiber boards, etc.).  Any organic materials (i.e., plastics, wood paper 

products,  etc.)  are  combustible  and  must  not  be  used.   The  floor  protection  specified  includes  some  form  of  thermal  designation  such  as  R-value 

(thermal resistance) or k-factor (thermal conductivity).

PROCEDURE:

 

1. Convert specification to R-value:

2. Determine the R-value of the proposed alternate floor protector.
 

 

i. Use the formula in step (1) to convert values not expressed as “R”.

 

 

ii. For multiple layers, add R-values of each layer to determine overall R-value.

3. If the overall R-value of the system is greater than the R-value of the specified floor protector, the alternate is acceptable.

EXAMPLE:

  The specified floor protector should be 3/4 inch thick material with a k-factor of 0.84.  The proposed alternate is 4” brick with an R-factor of 0.2 

over 1/8” mineral board with a k-factor of 0.29.

Step (a):  Use formula above to convert specification to R-value. 

Step (b):  Calculate R of proposed system.

 =

1

R =

x T

1

x  0.75  =  0.893

k

.84

Rbrick  =  0.2 x 4 = 0.8

4" brick of R = 0.2, therefore:

1/8" mineral board of k = 0.29, therefore:

Rmineral board  =

1

0.29

x  0.125  =  0.43

1

Rtotal = Rmineral board = 0.8 + 0.431 = 1.23

1

Step (c):  Compare proposed system Rtotal of 1.231 to specified R of 0.893.  Since proposed system Rtotal is greater than required, the system is acceptable.

(ft

2

)(hr)(

o

F)

Bt

u

R =

Btu(in)

ft

2

(hr)(

o

F)

= K x 12

k =

1

k

r = (ft

2

)(hr)(

o

F)

(Btu)(in)

=

K =

Btu(ft)

ft

2

(hr)(

o

F)

R =

x T

1

k

R =

x T

1

K x 12

k-factor is given with a required thickness (T) in inches: 

K-factor is given with a required thickness (T) in inches:  

r-factor is given with a required thickness (T) in inches:  R = 

R-value given - no conversion needed.

R =

x T

1

K x 12

GENERAL INSTALLATION PROCEDURE

• 

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.

• 

Install liner, if required, for your chosen installation.

• 

Attach metal warning plate to the back of the fireplace with screws or nails.

• 

Set appliance on the hearth (See Hearth Requirements 

page 4 

and Support Kit information on 

page 15.)

• 

Complete the vent connection required for your installation type.

•  

Relocate plate for Outside Air. (Required for Mobile Home Installation) 

page 12

;  Assemble Panel & Trim Set and 

install as one piece. 

See page 13.

• 

Position unit into fireplace leaving width enough for fiberglass batting to be inserted around face seal.

• 

Work unit securely into the fireplace using sheet metal shims if leveling bolts are needed.  

See Figure 11B on page 11.

• 

Remove all labels from glass prior to building first fire.

• 

Ensure that plated surfaces are cleaned prior to building first fire. 

See page 19

.

• 

Read Operation Instructions found on 

pages 17 and 18.

Содержание BODBAY

Страница 1: ...ol ashes should be disposed of carefully using a metal container 5 Do not burn wet or green wood Store wood in a dry location 6 DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE NAPHTHA OR ENGINE OIL Do not burn treated wood or wood with salt driftwood etc Burning materials other than wood including charcoal under adverse conditions may generate carbon monoxide in the home resulting in illn...

Страница 2: ...Y LABEL LOCATION On Beaded Chain Left Side Behind Outer Skin Model Name Serial Number Test Lab Report No Model BODEGA BAY Serial No Numéro De Série OMNI Test Laboratories Inc Report 061 S 40 2 O T L Tested and Listed by Beaverton Oregon USA C Made in U S A U S ENVIRONMENTAL PROTECTION AGENCY Certified to comply with July 1990 particulate emission standards 2008 2009 2010 Jan Feb Mar Apr May June J...

Страница 3: ...s 11 Securing Liner to Chimney Ring 12 PARTS ACCESSORY INSTALLATION Outside Air Installation 12 Panel and Trim Set 13 Door Handle Assembly 13 Door Latch Adjustment 13 Blower Cord Installation 14 Fan Blower Assembly Replacement 14 Zero Clearance Adjustable Trim Support 15 OPERATION OVERVIEW Wood Selection Storing 16 Overfiring 16 Building A Fire 16 Operating Tips 17 Burn Rates Opacity 17 Fan Operat...

Страница 4: ...t material Zero Clearance Installations USA Only In Canada a full length six inches 152mm S635 flue liner required as per ULC S628 NOTE When installling into a masonry fireplace the fire place must be built to UBC Chapter 37 standards Do not remove brick or mortar from masonry fireplace to accomo date insert The permanent metal warning plate provided must be attached to the back of the fireplace s...

Страница 5: ...on installation recommendations This product has met and surpassed the most stringent emissions standards in the United States The sophistication of the interior firebox design requires that a proper draft be supplied by the chim ney therefore adherence to the following factors will enable your insert to operate at its optimum capability required A minimum starter pipe reaching to the base of the ...

Страница 6: ...alternate is acceptable EXAMPLE The specified floor protector should be 3 4 inch thick material with a k factor of 0 84 The proposed alternate is 4 brick with an R factor of 0 2 over 1 8 mineral board with a k factor of 0 29 Step a Use formula above to convert specification to R value Step b Calculate R of proposed system 1 R x T 1 x 0 75 0 893 k 84 R brick 0 2 x 4 0 8 4 brick of R 0 2 therefore 1...

Страница 7: ...r structure that is within10 ft 305cm of the chimney measured horizon tally Refer to Figure 7C CHIMNEY REQUIREMENTS Non combustible fire stopping material Minimum 2 inch 51mm clearance from combustible material and insulation ceiling At least 2 ft 61cm At least 3 ft 91cm CHIMNEY HEIGHT 10 ft 305cm CHIMNEY TOP VIEW FLUE Foundation 1 2 12 7mm airspace 5 8 16mm Fireclay Flue Liner Chimney Wall 4 102m...

Страница 8: ...lowed precisely 7 Use silicone to create an effective vapor barrier at the location were the chimney or other component penetrates to the exterior of the structure 8 Follow the chimney and chimney connector manufacturer s instructions when installing the flue system for use in a mobile home Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe 2 Reinstall us...

Страница 9: ...e size of the flue should be checked to determine that it is not too large for the insert The chimney should also be checked to ensure it meets the minimum standard of the National Fire Protection Associa tion NFPA Standard 211 The following bullets list the more critical requirements for a properly constructed chimney The masonry wall of the chimney if brick or modular block must be a minimum of ...

Страница 10: ...e may be removed providing they can be stored on or within the fireplace for reassembly if the insert is removed The Quadra Fire Bodega Bay ACT Wood Stove Insert is listed to UL 1482 Standard and approved for installation into listed factory built zero clearance fireplaces listed to UL 127 conforming to the following specifications and instructions Minimum Width of cavity opening 30 in Minimum Hei...

Страница 11: ...ave been altered to accommodate the insert and must be returned to original condition for use as a conventional fireplace Circulating air chambers may not be blocked Leveling Bolts Sheet Metal Shims Place under leveling bolts and slide insert into place Leveling Bolt Reach between side of insert and outer skin cut out view The insert is shipped with 2 leveling bolts and 2 sheet metal guides for ea...

Страница 12: ...lied hex head bolts 1 4 20 3 4 NOTE Tabs are shipped from factory in a flat position Bend upwards 90 degrees Figure 12A Tools Needed Phillips Head Screwdriver 1 Remove 3 screws and cover plate from back side of insert Save the screws 2 Reattach the cover plate using the same screws to front side of the insert as shown in Figure 12B 3 Repeat same procedure for other side of insert NOTE This product...

Страница 13: ... Phillips head Screw Driver STANDARD 30 1 2 h x 44 5 8 w LARGE 34 h x 50 1 2 w PANEL and GOLD or NICKEL TRIM SET Tab with screw hole to secure panel to insert Screw side panels to top panel View of L Bracket installed Figure 13A Figure 13C Figure 13B DOOR HANDLE ASSEMBLY Door Latch Arm 5 16 Nut 1 4 20 Washer Washer 5 16 x 1 4 Fiber Handle Door Handle SP BB3044 GD Panel Trim Set Std Gold SP BB3044 ...

Страница 14: ...dard with a blower installed at the factory with blower cord on right side of insert as you face the unit The blower cord can also be installed on the left side Disconnect the cord from right side ROUTE WIRES IN FRONT OF FAN Re install on the left side Do not route cord behind the cooling fan FAN BLOWER REPLACEMENT Included in Kit Replacement Blower Tools Needed 5 32 Wrench and Phillips Head Screw...

Страница 15: ...ur straight edge 5 The double sided tape that holds front and side trims to scissors has a particularly powerful bonding adhe sive Adjustments are extremely difficult once trim has adhered to tape Do a dry run first without removing paper from tape 6 Place cut edge of trim under top lip and into position on scissors Place side pieces on first and then front piece The front piece overlaps side piec...

Страница 16: ...PERATION Before lighting your first fire in the insert make certain that the baffle is correctly positioned It should be resting against the rear support Also refer to care and cleaning of plated surfaces on page 19 before lighting your first fire CAUTION Never use gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or similar liquids to start or freshen up a fire in this heater Ke...

Страница 17: ... burn is well established then if you wish turn the fan on at a low rate 5 The fan is equipped with a rheostat speed control The highest fan speed is obtained by turning the rheostat on then adjusting back towards OFF as far as possible without turning the fan off For a low fan speed turn the control knob clockwise as far as possible Remove cold ashes not hot from the insert at regular intervals d...

Страница 18: ...taining some flames If the flames tend to go out the setting is too low The Primary Control located above the Start Up Air Control will assist you in adjusting the insert for a low burn rate The third stage of burning is the charcoal stage This happens when the flammable gases have been burned and the charcoal remains The coals burning with hot blue flames is a naturally clean portion of the burn ...

Страница 19: ...ntering of glass in door and or side frames and give all screws a final tightening CREOSOTE FORMATION AND NEED FOR REMOVAL When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture and in turn forms creosote These creosote vapors condense in the relatively cool chimney flue when a fire is newly started or from a slowly burning fire and accumulate on t...

Страница 20: ...ber Board Removing hardware exposed to combustion processes can be frustrating If your reason for removing the baffle is to clean the chimney you have alternatives which will save time and effort Call a qualified chimney sweep or an authorized Quadra Fire dealer for details 1 Remove all ash from firebox and extinguish all hot embers before disposal into a metal container 2 Remove ceramic blanket f...

Страница 21: ...side Air Cover Plate 6 Fiberboard Baffle 7 Ceramic Blanket 8 Manifold Tubes 2 3 4 Item Part Name 9 Wire Access Panel 10 Cover Plate 11 Blower 12 Door Frame 13 Glass Frame Horizontal 14 Glass Frame Vertical 15 Blower Housing 16 Blower Mount Base Item Part Name 17 Glass Front 18 Glass Sides 19 Top 20 Ashlip 21 Door Handle Assembly 22 Crown Assembly 23 Manifold Tube 1 24 Air Control Knob 5 0 14 0 10 ...

Страница 22: ...0 Baffle Fiber Board 832 3490 Blower Motor 832 0550 Brick Single give dimensions needed see page 20 832 3500 Brick Set SRV436 0380 Bricks with holes 435 5490 Ceramic Blanket 1 2 field cut to size see drawing page 21 435 5500 Component Pack includes Owner s Manual Touch up Paint Efficiency Card Warranty Card Door Handle Blower Cord Extension Wire for left side install Permanent Label If Fireplace A...

Страница 23: ...ogies discontinues the model and two 2 years for optional accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of upgraded component parts do not quality for a service call fee and will not be covered This limited Lifetime Warranty does not extend to or...

Страница 24: ...502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 D320652 D445174 D462436 Canada 1297749 2195264 2225408 or other U S and foreign patents pending Hearth Home Technologies 1445 North Highway Colville WA 99114 Division of HNI INDUSTRIES CONTACT INFORMATION Please contact your Quadra Fire dealer with any que...

Отзывы: