background image

BODEGA BAY WOOD INSERT

Page 18

  August 20, 2008

435-1320B

 AIR qUALITY AND YOUR qUADRA-FIRE INSERT 

In recent years there has been an increasing concern about the quality of our air.  Much of the blame for poor air quality has 

been placed on the burning of wood for home heating.  In order to improve this situation we at Quadra-Fire have developed 

cleaner burning inserts that surpass the stringent requirements for emissions established by our governing agencies.  Your 

Bodega Bay Wood Insert, like any other appliance, must be properly operated in order to ensure that they perform the way 

they are designed to perform.  Improper operation and maintenance may cause any wood burning unit to release more 

particulate, adversely affecting the environment.  

The story of the Three Burning Stages . .

 .

It helps to know a little about the actual burn process, which entails three discernible burning stages.  The first stage is called 

the kindling stage. During this stage the fuel reaches the boiling temperature of water, 212°F, evaporating the moisture 

found to some degree in all wood. 

 

Because the process takes heat from the insert during this initial drying stage, each new load of wood reduces the chances 

for a good, clean burn.  For this reason it is always best to burn dry, seasoned firewood, and operate the controls properly.  

The bottom control on the right side of your insert is called the Start-Up Air Control and is used primarily during this first 

kindling stage of burning. 

During the secondary stage, the wood gives off flammable gases which burn above the fuel with bright flames.  These 

flames above the fuel must be maintained until the third stage to ensure proper burning.  During this stage you may adjust 

your insert for a low burn rate.  To achieve a low burn rate it is necessary to close down the air while still maintaining some 

flames.  If the flames tend to go out, the setting is too low.  The Primary Control, located above the Start-Up Air Control, will 

assist you in adjusting the insert for a low burn rate.

The third stage of burning is the charcoal stage.  This happens when the flammable gases have been burned and the 

charcoal remains.  The coals burning with hot blue flames is a naturally clean portion of the burn.  It is very important to 

reload your insert while enough lively hot coals remain in order to provide the amount of heat needed to dry and rekindle the 

next load of wood.  Open up both controls for a short while before reloading to liven up the coal bed.  You should also break 

up any large chunks and distribute the coals so the new wood is laid on hot coals.  Leave both controls open (close the 

Start-Up-Air after 15 minutes) until the new wood load is burning well enough to maintain the secondary stage of burning 

and then set the Primary Control to your desired heat output setting.  

START-UP AIR SYSTEM

The combustion air enters at the rear of the firebox through the rear air tubes.  This air supply is controlled by the Start-Up 

Air Control. 

See Figure 18A.

PRIMARY AIR SYSTEM

The primary air enters at the upper front of the firebox near the top of the glass door.  This preheated air supplies the neces

-

sary fresh oxygen to mix with the unburned gases, helping to create second, third and fourth stages of combustion.  This 

air is regulated by the Primary Air Control.  For more primary air (more heat), push rod in.  For less primary air (less heat), 

pull rod out.  

See Figure 18A.

In other words . . .

Pulling either control towards you closes off the air available to the insert in that area. Pushing either control opens it, allow

-

ing air circulation to the area.  A good analogy to remember for this procedure is the gas pedal on your car.  Pushing in the 

gas pedal makes the engine run faster.  Letting off (pulling the control back) makes the car run slower.  

Primary Air Control

Start-Up Air Control

Figure 18A

OPEN - PUSH IN

CLOSE - PULL OUT

Содержание BODBAY

Страница 1: ...ol ashes should be disposed of carefully using a metal container 5 Do not burn wet or green wood Store wood in a dry location 6 DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE NAPHTHA OR ENGINE OIL Do not burn treated wood or wood with salt driftwood etc Burning materials other than wood including charcoal under adverse conditions may generate carbon monoxide in the home resulting in illn...

Страница 2: ...Y LABEL LOCATION On Beaded Chain Left Side Behind Outer Skin Model Name Serial Number Test Lab Report No Model BODEGA BAY Serial No Numéro De Série OMNI Test Laboratories Inc Report 061 S 40 2 O T L Tested and Listed by Beaverton Oregon USA C Made in U S A U S ENVIRONMENTAL PROTECTION AGENCY Certified to comply with July 1990 particulate emission standards 2008 2009 2010 Jan Feb Mar Apr May June J...

Страница 3: ...s 11 Securing Liner to Chimney Ring 12 PARTS ACCESSORY INSTALLATION Outside Air Installation 12 Panel and Trim Set 13 Door Handle Assembly 13 Door Latch Adjustment 13 Blower Cord Installation 14 Fan Blower Assembly Replacement 14 Zero Clearance Adjustable Trim Support 15 OPERATION OVERVIEW Wood Selection Storing 16 Overfiring 16 Building A Fire 16 Operating Tips 17 Burn Rates Opacity 17 Fan Operat...

Страница 4: ...t material Zero Clearance Installations USA Only In Canada a full length six inches 152mm S635 flue liner required as per ULC S628 NOTE When installling into a masonry fireplace the fire place must be built to UBC Chapter 37 standards Do not remove brick or mortar from masonry fireplace to accomo date insert The permanent metal warning plate provided must be attached to the back of the fireplace s...

Страница 5: ...on installation recommendations This product has met and surpassed the most stringent emissions standards in the United States The sophistication of the interior firebox design requires that a proper draft be supplied by the chim ney therefore adherence to the following factors will enable your insert to operate at its optimum capability required A minimum starter pipe reaching to the base of the ...

Страница 6: ...alternate is acceptable EXAMPLE The specified floor protector should be 3 4 inch thick material with a k factor of 0 84 The proposed alternate is 4 brick with an R factor of 0 2 over 1 8 mineral board with a k factor of 0 29 Step a Use formula above to convert specification to R value Step b Calculate R of proposed system 1 R x T 1 x 0 75 0 893 k 84 R brick 0 2 x 4 0 8 4 brick of R 0 2 therefore 1...

Страница 7: ...r structure that is within10 ft 305cm of the chimney measured horizon tally Refer to Figure 7C CHIMNEY REQUIREMENTS Non combustible fire stopping material Minimum 2 inch 51mm clearance from combustible material and insulation ceiling At least 2 ft 61cm At least 3 ft 91cm CHIMNEY HEIGHT 10 ft 305cm CHIMNEY TOP VIEW FLUE Foundation 1 2 12 7mm airspace 5 8 16mm Fireclay Flue Liner Chimney Wall 4 102m...

Страница 8: ...lowed precisely 7 Use silicone to create an effective vapor barrier at the location were the chimney or other component penetrates to the exterior of the structure 8 Follow the chimney and chimney connector manufacturer s instructions when installing the flue system for use in a mobile home Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe 2 Reinstall us...

Страница 9: ...e size of the flue should be checked to determine that it is not too large for the insert The chimney should also be checked to ensure it meets the minimum standard of the National Fire Protection Associa tion NFPA Standard 211 The following bullets list the more critical requirements for a properly constructed chimney The masonry wall of the chimney if brick or modular block must be a minimum of ...

Страница 10: ...e may be removed providing they can be stored on or within the fireplace for reassembly if the insert is removed The Quadra Fire Bodega Bay ACT Wood Stove Insert is listed to UL 1482 Standard and approved for installation into listed factory built zero clearance fireplaces listed to UL 127 conforming to the following specifications and instructions Minimum Width of cavity opening 30 in Minimum Hei...

Страница 11: ...ave been altered to accommodate the insert and must be returned to original condition for use as a conventional fireplace Circulating air chambers may not be blocked Leveling Bolts Sheet Metal Shims Place under leveling bolts and slide insert into place Leveling Bolt Reach between side of insert and outer skin cut out view The insert is shipped with 2 leveling bolts and 2 sheet metal guides for ea...

Страница 12: ...lied hex head bolts 1 4 20 3 4 NOTE Tabs are shipped from factory in a flat position Bend upwards 90 degrees Figure 12A Tools Needed Phillips Head Screwdriver 1 Remove 3 screws and cover plate from back side of insert Save the screws 2 Reattach the cover plate using the same screws to front side of the insert as shown in Figure 12B 3 Repeat same procedure for other side of insert NOTE This product...

Страница 13: ... Phillips head Screw Driver STANDARD 30 1 2 h x 44 5 8 w LARGE 34 h x 50 1 2 w PANEL and GOLD or NICKEL TRIM SET Tab with screw hole to secure panel to insert Screw side panels to top panel View of L Bracket installed Figure 13A Figure 13C Figure 13B DOOR HANDLE ASSEMBLY Door Latch Arm 5 16 Nut 1 4 20 Washer Washer 5 16 x 1 4 Fiber Handle Door Handle SP BB3044 GD Panel Trim Set Std Gold SP BB3044 ...

Страница 14: ...dard with a blower installed at the factory with blower cord on right side of insert as you face the unit The blower cord can also be installed on the left side Disconnect the cord from right side ROUTE WIRES IN FRONT OF FAN Re install on the left side Do not route cord behind the cooling fan FAN BLOWER REPLACEMENT Included in Kit Replacement Blower Tools Needed 5 32 Wrench and Phillips Head Screw...

Страница 15: ...ur straight edge 5 The double sided tape that holds front and side trims to scissors has a particularly powerful bonding adhe sive Adjustments are extremely difficult once trim has adhered to tape Do a dry run first without removing paper from tape 6 Place cut edge of trim under top lip and into position on scissors Place side pieces on first and then front piece The front piece overlaps side piec...

Страница 16: ...PERATION Before lighting your first fire in the insert make certain that the baffle is correctly positioned It should be resting against the rear support Also refer to care and cleaning of plated surfaces on page 19 before lighting your first fire CAUTION Never use gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or similar liquids to start or freshen up a fire in this heater Ke...

Страница 17: ... burn is well established then if you wish turn the fan on at a low rate 5 The fan is equipped with a rheostat speed control The highest fan speed is obtained by turning the rheostat on then adjusting back towards OFF as far as possible without turning the fan off For a low fan speed turn the control knob clockwise as far as possible Remove cold ashes not hot from the insert at regular intervals d...

Страница 18: ...taining some flames If the flames tend to go out the setting is too low The Primary Control located above the Start Up Air Control will assist you in adjusting the insert for a low burn rate The third stage of burning is the charcoal stage This happens when the flammable gases have been burned and the charcoal remains The coals burning with hot blue flames is a naturally clean portion of the burn ...

Страница 19: ...ntering of glass in door and or side frames and give all screws a final tightening CREOSOTE FORMATION AND NEED FOR REMOVAL When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture and in turn forms creosote These creosote vapors condense in the relatively cool chimney flue when a fire is newly started or from a slowly burning fire and accumulate on t...

Страница 20: ...ber Board Removing hardware exposed to combustion processes can be frustrating If your reason for removing the baffle is to clean the chimney you have alternatives which will save time and effort Call a qualified chimney sweep or an authorized Quadra Fire dealer for details 1 Remove all ash from firebox and extinguish all hot embers before disposal into a metal container 2 Remove ceramic blanket f...

Страница 21: ...side Air Cover Plate 6 Fiberboard Baffle 7 Ceramic Blanket 8 Manifold Tubes 2 3 4 Item Part Name 9 Wire Access Panel 10 Cover Plate 11 Blower 12 Door Frame 13 Glass Frame Horizontal 14 Glass Frame Vertical 15 Blower Housing 16 Blower Mount Base Item Part Name 17 Glass Front 18 Glass Sides 19 Top 20 Ashlip 21 Door Handle Assembly 22 Crown Assembly 23 Manifold Tube 1 24 Air Control Knob 5 0 14 0 10 ...

Страница 22: ...0 Baffle Fiber Board 832 3490 Blower Motor 832 0550 Brick Single give dimensions needed see page 20 832 3500 Brick Set SRV436 0380 Bricks with holes 435 5490 Ceramic Blanket 1 2 field cut to size see drawing page 21 435 5500 Component Pack includes Owner s Manual Touch up Paint Efficiency Card Warranty Card Door Handle Blower Cord Extension Wire for left side install Permanent Label If Fireplace A...

Страница 23: ...ogies discontinues the model and two 2 years for optional accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of upgraded component parts do not quality for a service call fee and will not be covered This limited Lifetime Warranty does not extend to or...

Страница 24: ...502 6170481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 D320652 D445174 D462436 Canada 1297749 2195264 2225408 or other U S and foreign patents pending Hearth Home Technologies 1445 North Highway Colville WA 99114 Division of HNI INDUSTRIES CONTACT INFORMATION Please contact your Quadra Fire dealer with any que...

Отзывы: