background image

QP-748MI User Manual 

Version 1.0 

W

IRING 

F

AULT 

A

LARM

 

 

1.

 

Insert the wires into the left two contacts of the 4-contact terminal 
block (Fault Alarm Relay).

 

2.

 

Tighten the screws to prevent the wires from loosening.

 

3.

 

The relay will detect the power and link failure.

 

4.

 

Users can connect the relay to an alarm and buzzer so that when 
the relay forms an open circuit, the users will be notified.

 

 

W

IRING 

D

IGITAL 

I

NPUTS

 

 

1.

 

Insert the  positive and  negative wires into the right two contacts 
(+,-) of the 4-contact terminal block (DI).

 

2.

 

Tighten the screws to prevent the wires from loosening.

 

3.

 

The system will detect the voltage go through the DI.

 

 

+13 to +30V for state "1"

 

 

-30 to +3V for state "0"

 

 

Max. input current: 8mA

 

 

D

OUBLE

-S

ECURE 

P

OWER 

I

NPUT 

F

AULT 

A

LARM

 

 

The  power  inputs  are  designed  as  a  "

common 

negative

",  which  implies  that  the  negative  input  is 

connected,  but  "

double-secure

"  is  supported  to 

prevent the unnotified failure of power from one of the 
negative  inputs.  If  one  of  the  negative  power  input 
fails,  the  system  will  detect  it  and  the  system  will 
trigger  the  event  if  the  users  set  the  fault  alarm  or 
event log for powers.

 

 

Содержание QP-748MI

Страница 1: ...QP 748MI User Manual Version 1 0 www qpcom com Hardware User Manual Industrial Managed Ethernet Switch QP 748MI...

Страница 2: ...scription 2 Front Panel Instruction 2 Dimensions 2 Top View 3 LED Instruction 3 Reset Button 4 USB Port 4 Hardware Installation 5 SFP Cabling 5 Wiring Power Inputs 6 Wiring Fault Alarm 7 Wiring Digita...

Страница 3: ...er Input Redundant 12 48VDC power Temperature Standard operating temperature 10 C 60 C 14 F 140 F Extended operating temperature 40 C 75 C 40 F 167 F Storage temperature 40 C 85 C 40 F 185 F Mechanica...

Страница 4: ...QP 748MI User Manual Version 1 0 2 Hardware Description FRONT PANEL INSTRUCTION The following picture is the front panel for QP 748MI DIMENSIONS WxHxD 72x145x118 mm...

Страница 5: ...2 Green On Power is supplied on the power input 2 Off Power is not supplied on the power input 2 Fault Green On The system boots up and in normal operation Off The system is powered off or during boot...

Страница 6: ...rt is active Flickering Data is transmitted on the port at 10 100Mbps Off The 10 100Mbps link of the port is inactive RESET BUTTON A multifunctional reset button is provided Use a pointed object such...

Страница 7: ...0 C QPCOM 1000Base X3 1310 SMF 9 5 3 20 LX 10km 40 85 C QPCOM 1000Base X4 DDM 1310 SMF 9 5 3 20 LX 10km 40 85 C 1 25Gbps 1000Base BX Single Fiber Bi Directional SFP QPCOM 1000Base BX1 Dual Rate T1310...

Страница 8: ...ve SFP Module 1 Press and remove the SFP cable 2 Open the SFP module and remove it WIRING POWER INPUTS 1 Insert the positive and negative wires into the PWR1 and PWR2 on the 4 contact terminal block c...

Страница 9: ...nto the right two contacts of the 4 contact terminal block DI 2 Tighten the screws to prevent the wires from loosening 3 The system will detect the voltage go through the DI 13 to 30V for state 1 30 t...

Страница 10: ...ING Din Rail Mounting a Screw the DIN Rail bracket to the switch b Insert the top of the DIN Rail bracket to the DIN Rail track c Pull down the DIN Rail bracket to the DIN Rail track and check if it i...

Страница 11: ...optional items If you need the wall mount brackets contact us for assistance To install the switch on the wall refer to the Wall Mounting section 4 Power On To power on the switch users must prepare...

Страница 12: ...TP ITU T G 8032 Y 1344 ERPS IEEE 802 1Q VLAN Tagging IEEE 802 1ad Stacked VLANs IEEE 802 1p Class of Service IEEE 802 1X Network Authentication IEEE 802 1AB LLDP Processing Type Store and Forward Tran...

Страница 13: ...ing capacity of 1A 24 VDC Digital Inputs 1x isolated input from the electronics 13 to 30V for state 1 30 to 3V for state 0 Max input current 8mA Button Multiple functions reset button Serial Console 1...

Страница 14: ...F Extended 40 C 75 C 40 F 167 F Storage Temperature 40 C 85 C 40 F 185 F Ambient Relative Humidity 5 to 95 Non Condensing Regulatory Approvals EMI FCC Part 15 Subpart B Class A CE EN 55022 Class A EMS...

Страница 15: ...QP 748MI User Manual Version 1 0 13 Certifications UL 60950 1 62368 Pending MTBF 100 000 hours Warranty 3 Years...

Отзывы: