INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide

WARNING: PLEASE READ CAREFULLY AND THOROUGHLY

•  NFPA 72 states: Fire-warning equipment for residential occupancies 

are capable of protecting about half of the occupants in potentially 
fatal 

fi

 res.  Victims are often intimate with the 

fi

  re, too old or too 

young,  or  physically  or  mentally  impaired  such  that  they  cannot 
escape  even  when  warned  early  enough  that  escape  should  be 
possible.  For  these  people,  other  strategies  such  as  protection-in-
place or assisted escape or rescue would be necessary.

•  A battery powered alarm must have a battery of the speci

fi

  ed type, 

in good condition and installed properly. 

•  Smoke alarms must be tested regularly to make sure the batteries 

and the alarm circuits are in good operating condition.

•  Smoke alarms cannot provide an alarm if smoke does not reach the 

detector.  Therefore,  smoke  alarms  may  not  sense 

fi

   res  starting  in 

chimneys, walls, on roofs, on the other side of a closed door or on a 
different 

fl

 oor.

•  If the alarm is located outside the sleeping room or on a different 

fl

 oor, it may not wake up a sound sleeper.

•  Studies have shown that smoke and heat alarms may not awaken all 

sleeping  individuals,  and  that  it  is  the  responsibility  of  individuals 
in  the  household  that  are  capable  of  assisting  others  to  provide 
assistance to those who may not be awakened by the alarm sound or 
those who may be incapable of safely evacuating the area unassisted.

•  The use of alcohol or drugs may also impair one’s ability to hear the 

smoke  alarm.  For  maximum  protection,  a  smoke  alarm  should  be 
installed in each sleeping area on every level of a home.

•  Although  smoke  alarms  can  help  save  lives  by  providing  an  early 

warning of a 

fi

 re, they are not a substitute for an insurance policy. 

Home  owners  and  renters  should  have  adequate  insurance  to 
protect their properties.

FAMILY ESCAPE PLAN

According  to  National  Fire  Protection  Association  (NFPA)  there  often 
is  very  little  time  between  the  detection  of  a 

fi

   re  and  the  time  it 

becomes deadly. This interval can be as little as 1 or 2 minutes. Planning 
and practicing for 

fi

 re conditions with a focus on rapid exit from the 

residence are important. Drills should be held so that all family members 
know the action to be taken.

SAFETY TIPS

•  Make a home escape plan. Draw a map of your home showing all 

doors and windows. Discuss the plan with everyone in your home.

17

Guide d'installation du détecteur de chaleur et de fumée sans 

fi

 l INST APD0595 A140618

•  À l'intérieur ou sous un placard
•  Dans  des  endroits  où  la  circulation  d'air  serait  obstruée  par  des  rideaux  ou 

des meubles

•  Dans un endroit où de la saleté ou de la poussière pourrait s'accumuler et bloquer 

le détecteur

•  Dans un endroit où il pourrait être cogné, endommagé ou ôté par inadvertance

Ce détecteur ne doit pas être installé dans un endroit où la température ambiante 
normale est inférieure à 4,4°C (40°F) ou là où elle est supérieure à 37,8°C (100°F).

CET ÉQUIPEMENT DOIT ÊTRE INSTALLÉ CONFORMÉMENT À LA NORME 72 DE 
LA NATIONAL FIRE PROTECTION ASSOCIATION

 

: CODE NATIONAL D'ALARME 

INCENDIE ET DE SIGNALISATION.

MONTAGE DU DÉTECTEUR
Remarque

 

Ces  dispositifs  d’alarme  doivent  être  installés  uniquement  par  un 

ingénieur/technicien compétent.
Cet appareil ne doit pas être utilisé avec une grille de protection.
Une fois que vous avez trouvé un emplacement convenable, montez le détecteur 
comme suit

 

:

1.  Consultez le schéma ci-dessous et installez le socle de 

fi

 xation au plafond ou sur 

le mur (si les décrets locaux le permettent) à l’aide des positions de vis indiquées. 
Utilisez les deux vis et les pièces d'ancrage fournies. Manipulez le socle pour que 
les vis s’emboîtent correctement dans les fentes prévues à cet effet.

2.  Ajustez  le  détecteur  sur  son  socle  en  l’alignant  dessus  comme  l'indique 

l'illustration  (l’encoche  d’alignement  du  détecteur  devrait  être  légèrement 
décalée  de  la  languette  de  sécurité  du  socle  de 

fi

 xation),  puis  tournez  le 

détecteur dans le sens horaire jusqu’à ce qu’il s'emboîte dans un déclic.

3.  Testez le détecteur à la 

fi

 n de l’installation (comme le décrit la section TESTER 

LE  DÉTECTEUR  de  ce  manuel)  et  consultez  les  instructions  du  système  de 
commande pour plus de renseignements sur l’utilisation des appareils sans 

fi

 l.

1HSDVIL[HUOHGpWHFWHXUVXUGHVSDQQHDX[GHSODIRQGDPRELEOHV

100 mm (4 in.) minimum

100 mm (4 in.)

 minimum

Fig 9.

,QVWDOODWLRQGXGpWHFWHXU

Содержание IQSmoke

Страница 1: ...ns an integrated fixed 41 F temperature freeze sensor that will send a warning signal based on temperature detected This detector is designed to provide protection with 70 foot spacing capability The detector can send alarm tamper and battery condition messages to the system s receiver Refer to the wireless system s instruction for the maximum number of transmitters that can be supported CONTENTS ...

Страница 2: ...oke Heat Alarm contains a sounder which generates the ANSI S3 41 temporal 3 pattern in an alarm condition In alarm a message is also sent to the control panel and the detector s ID is displayed at the console During an alarm condition pressing the detector s hush button will silence the sounder see table below The mounting base installation is simplifi ed by the incorporation of features compatibl...

Страница 3: ...anel will display a loss of supervision message Low Battery Detection The Wireless Smoke Heat Alarm is powered by 3 AAA Duracell Procell or 3 AAA Energizer E92 batteries included The detector regularly checks for a low battery If a low battery is detected the transmitter sends a low battery message to the control panel which displays the detector s ID at low battery In addition the yellow LED of t...

Страница 4: ...ions non autorisés pourraient entraîner l annulation de l autorisation d exploiter l équipement Cetappareilestconformeàlapartie15delaréglementationdelaFCCetauxnormes RSS sur les appareils exempts de licence d Industrie Canada Son fonctionnement est soumis aux deux conditions suivantes 1 Ce dispositif ne doit pas causer d interférences nuisibles et 2 cet appareil doit accepter toute interférence re...

Страница 5: ...incluses trois 3 piles AAA PC2400 Duracell Procell ou trois 3 piles AAA Energizer E92 Liste de matériels homologués réglementaires UL 217 Garantie deux 2 ans Accessoires inclus Trousse de matériel de montage INFORMATIONS RÉGLEMENTAIRES 5 penetrating In most fires this dead air space measures about 0 1m 4in along the ceiling from the corner and about 0 1m 4in down the wall Detectors should not be p...

Страница 6: ...échapper même si elles sont averties suffisamment tôt pour qu une évacuation soit possible Pour ces personnes d autres stratégies tellesquedesmesuresdeprotection uneévacuationouunsecoursassistéseraient nécessaires Un détecteur alimenté par piles doit avoir des piles du type spécifié en bon état et convenablement installées Les détecteurs de fumée doivent être régulièrement testés pour s assurer qu...

Страница 7: ...ur L extérieur du détecteur peut être essuyé avec un chiffon humide Après nettoyage réinstallez et testez votre détecteur à l aide du bouton de test Si le nettoyage ne restaure pas le fonctionnement normal de l alarme le détecteur doit être remplacé 7 INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide TESTING THE DETECTOR NOTE Before testing notify the central station that the detector s...

Страница 8: ... or 2 minutes Planning and practicing for fire conditions with a focus on rapid exit from the residence are important Drills should be held so that all family members know the action to be taken SAFETY TIPS Make a home escape plan Draw a map of your home showing all doors and windows Discuss the plan with everyone in your home 17 Guide d installation du détecteur de chaleur et de fumée sans fil IN...

Страница 9: ... DE FUM E SgIL NgY A PAS DE PORTE ENTRE LE SALON ET LA SALLE DE JEUX NSTALLATION D UN D TECTEUR DE FUM E REQUISE NTR E HAMBRE 3ALON 3ALLE Ë MANGER AVE NTR E HAMBRE 100 4 i Fig 5 QVWDOODWLRQ GDQV XQH PDLVRQ j GHPL QLYHDX Fig 4 8Q GpWHFWHXU LQVWDOOp j FKDTXH pWDJH 9 INST APD0595 A140618 Wireless Smoke Heat Alarm Install Guide Know at least two ways out of every room if possible Make sure all doors a...

Страница 10: ...a base de montage en tournant le détecteur dans le sens horaire jusqu à ce que les repères soient alignés 5 Après la mise sous tension la DEL verte devrait clignoter une fois toutes les 12 secondes environ pour indiquer un fonctionnement normal Si les piles ne sont pas correctement installées le détecteur ne fonctionnera pas et les piles risquent d être endommagées Si vous ne parvenez pas à mettre...

Страница 11: ...lacez les piles dès que les bips sonores recommencent Assurez vous de remplacer les anciennes piles par des neuves INSTALLATION ET REMPLACEMENT DES PILES Pour remplacer les piles 1 Déposez le détecteur de son socle de fixation en le tournant dans le sens antihoraire Enlevezlespilesetmettez lesaurebutselonlesréglementations locales 2 Afin de garantir une mise hors tension appropriée attendez 20 sec...

Страница 12: ...r le bouton pour l arrêter pendant 5 à 10 minutes Test de fumée Clignote en rouge chaque seconde ANSI S3 41 temporel 3 appuyez sur le bouton pour l arrêter pendant 5 à 10 minutes Tester le détecteur Clignote en rouge chaque seconde ANSI S3 41 temporel 3 Alarme de gel Clignote en jaune 3 fois toutes les 4 secondes Désactivé Défaut du détecteur Clignote en jaune toutes les 4 secondes Un bip sonore t...

Отзывы: