B71050-021-000-RB.doc
ELECTROCHEMICAL TRANSMITTER
JUL. 18 2007
PRODUCT MANUAL
GENERAL SPECIFICATIONS
DIMENSIONS:
Explosion Proof:
5.7”W x 8.2”H x 4.2”D (145mm x 210mm x 110mm)
POWER SUPPLY:
24 VDC (12-36 VDC)
SIGNAL:
4 - 20 mA Linear (maximum over scale: 25 mA)
Zero = 4.00 mA ± 0.1 mA
WIRING:
2 - Wire 14 - 24 AWG
SENSOR TYPE:
Electrochemical
HUMIDITY:
Continuous:
15% - 90% RH Non-Condensing
Intermittent:
0-099% RH Non-Condensing
Standard
Recommended
Model
Gas
Gas
Measurement
Alarm Settings
Operating
Recommended
Number
Code
Type
Range
Warning
Alarm
Temperature
Mtng. Height*
QTS-61110x-
110
H
2
S
0-25 ppm
5 ppm
10 ppm
-40° C to + 50° C
Low
QTS-61115x-
115
HCN
0-20 ppm
10 ppm
15 ppm
-20° C to + 50° C
Mid
QTS-61120x-
120
Cl
2
0-3 ppm
0.5 ppm
2 ppm
-20° C to + 50° C
Low
QTS-61123x-
123
ClO
2
0-1 ppm
0.1 ppm
0.3 ppm
-20° C to + 50° C
Low
QTS-61125x-
125
HCL
0-10 ppm
5 ppm
7 ppm
-20°C to + 50° C
Mid
QTS-61140x-
140
SO
2
0-6 ppm
2 ppm
5 ppm
-20°C to + 50° C
Low
QTS-61150x-
150
NO
2
0-6 ppm
1 ppm
3 ppm
-20°C to + 50° C
Low
QTS-61160x-
160
CO
0-250 ppm
10 ppm
100 ppm
-20°C to + 50° C
Mid
QTS-61190x-
190
NO
0-100 ppm
25 ppm
50 ppm
-20°C to + 50° C
Mid
QTS-61211x-
211
H
2
0-2000 ppm
500 ppm
1000 ppm
-20°C to + 50° C
High
QTS-61220x-
220
NH
3
0-50 ppm
25 ppm
35 ppm
-25°C to + 30° C
High
QTS-61230x-
230
C
2
H
4
O
0-20 ppm
2 ppm
5 ppm
-20°C to + 50° C
Low
QTS-61240x-
240
O
3
0-3 ppm
0.5 ppm
2 ppm
-20°C to + 50° C
Mid
*Low = 9” to 18” (.23 to .45 m) above floor
*
Mid = 4ft to 6ft (1.2 to 1.8 m) above floor
*
High = 9” to 18” (.23 to .45 m) below ceiling