3.15 Menu “8_Buzzer Database”
The buzzer setup is almost identical to that of the relays, except that there are three butter
options.
•
Buzzer 1: Double-tap Intermittent
•
Buzzer 2: Intermittent 50% duty cycle
•
Buzzer 3: Continuous
Buzzer 3 has highest priority and Buzzer 1 has lowest priority.
The menus are identical to those for the Relay Database. For Relay Database detail and
flow chart, please refer 3.13 Menu “6_Relay Database” on page 24.
3.16 Menu “9_Output Disable”
This function is for calibration, system testing etc. When Output is disabled, the relay,
buzzer and analog output, etc., statuses will freeze in whatever state they are already in.
Default is “Output Enabled” when the unit is powered up.
3.17 Menu “10_Simu Disable”
Simulation Mode is to assist in testing the installation before commissioning. When the
simulation is enabled, the unit will not detect gas concentration, it will display the
simulating value and use it to calculate the statuses of relays and buzzer, as well as 4-
20mA analog output. This feature is available for evaluating the user settings and testing
the installation (e.g.: the travel of the valve, fan speed, relay set points, etc. can be
verified.)
Any concentration between 0ppm and 9999ppm can be simulated.
Default is “Simu Disabled” when the unit is powered up.
4. MODBUS Protocol Supported By QIRF
For ModBus protocol, please contact QEL.