MODBUS REGISTER MAP
QA-TEMP
Q
A
-T
E
M
P
09
2015
Register Name
Comment
Output Analog
Input Begin scale
Output Analog Input Begin Scale
FLOAT (MSW)
R/W
0.0
Output
Analog
Input End scale
Output Analog Input End Scale
FLOAT (MSW)
R/W
10000.0
Output Analog
Begin scale
Output Analog Begin Scale
UNIT16
R/W
0
Output Analog
End scale
Output Analog End Scale
UNIT16
R/W
10000
0...65535
40112
Digital Output
UNIT16
R/W
0
40113
Alarm Low Trip
value
Alarm Low trip value
FLOAT (MSW)
R/W
0.0
Alarm High Trip
value
Alarm High trip value
FLOAT (MSW)
R/W
0.0
Alarm Hysteresis
value
Alarm Hysteresys value
FLOAT (MSW)
R/W
0.0
40118
40119
Modbus Address
Modbus astopbits : MSB Modbus
address,
bit 0-1
=parity none/odd/even,
bit 2
=stop bits 1/2
UNIT16
R/W
256
40120
Modbus Baudrate
Modbus Baudrate : value 0=1200, 1=2400,
2=4800, 3=9600, 4=19200, 5=38400, 6=57600,
7=115200
UNIT16
R/W
3
0...7
40121
Log mode
Log mode : bit 0=disabled/enabled
UNIT16
R/W
0
40122
Log sample time
Log sample time (sec)
UNIT16
R/W
1
1...65535
40123
Log name
Log name 15 letters max
UNIT16
R/W
0
40124
Log name
Log name 15 letters max
UNIT16
R/W
0
40125
Log name
Log name 15 letters max
UNIT16
R/W
0
40126
Log name
Log name 15 letters max
UNIT16
R/W
0
40127
Log name
Log name 15 letters max
UNIT16
R/W
0
40128
Log name
Log name 15 letters max
UNIT16
R/W
0
40129
Log name
Log name 15 letters max
UNIT16
R/W
0
40130
Log name
Log name 15 letters max
UNIT16
R/W
0
40131
RTC Year
RTC Year
UNIT16
R/W
2000...2099
41001
RTC Month
RTC Month
UNIT16
R/W
1...12
41002
RTC Day
RTC Day
UNIT16
R/W
1...31
41003
RTC Hour
RTC Hour
UNIT16
R/W
1...23
41004
RTC Minute
RTC Minute
UNIT16
R/W
0...59
41005
RTC Second
RTC Second
UNIT16
R/W
0...59
41006
Command
Command : value 1=Reset, 2=Save Cfg to
EEPROM, 3=Set Factory CFG,
UNIT16
R/W
Command 1
Command parameter 1
UNIT16
R/W
Command 2
Command parameter 2
UNIT16
R/W
Register Type
Digital Output :
bit 0
=default value,
bit 1
=fail ur,
bit 2
= fail or,
bit 3
= fail hw,
bit 4
=
fail log,
bit 5
= fail rtc,
bit 6
= fail eeprom,
bit 7
R/W Default
Value
Range
Modbus
Address
40107
40108
40109
40110
0...65535
40111
40114
40115
40116
40117
Upgrade FIRMWARE:
The QA-TEMP is designed to upgrade the firmware via the USB port using a standard pen drive where the file will be placed.
The firmware will allow you to implement the functionality of the card and correct any anomalies that may occur.
In order to upgrade the firmware simply, remove power from the module, insert the pen drive with the file, restore power, at this point
the card will automatically discharge the file and update the firmware without altering the configuration loaded during programming.
During the update phase the LED light will be intermittent FAIL.
7
42001
42002
42003
M
O
D
BU
S
R
E
G
IS
T
E
R
M
A
P
ENGLISH