MODBUS REGISTER MAP

 

                   QA-TEMP

M

O

DB

U

S

 R

E

G

IS

T

E

R

 M

AP

 

 

Q

A

-T

E

M

P

6

09

2015

DIPSW status :

bit 0-7

 =dip switch status, pos

1=bit 8,..., pos 8=bit 1

UNIT16 

R

Third wire Resistence Ohm 

FLOAT (MSW) 

R/W

Analog Input type : 2=Potentiometer,
3=Resistor400-2W, 4=Resistor400-3W,
5=Resistor400-4W, 6=Resistor4000-2W,
7=Resistor4000-3W, 8=Resistor4000-4W,
9=NI100-2W, 10=NI100-3W, 11=NI100-4W,
12=PT100-2W, 13=PT100-3W, 14=PT100-4W,
15=PT500-2W, 16=PT500-3W, 17=PT500-4W,
18=PT1000-2W, 19=PT1000-3W, 20=PT1000-4W,
21=TC J, 22=TC K, 23=TC R, 24=TC S, 25=TC T,
26=TC B, 27=TC E, 28=TC N

UNIT16 

R/W 

2...28

NOT USED

40102

Temperature mode :

bit 0-1

  = unit measure

°C/°F,

bit 7-15

  analog filter value

UNIT16 

R/W 

MSB: 1...32

40103

NOT USED

40104

NOT USED

40105

Output Analog mode :

bit 0

 =Voltage/Current,

bit

1-2

 =analog input, frequency, period,totalizer,

bit

3

= fail ur,

bit 4

  = fail or,

bit 5

  = fail  hw,

bit 6

   =

fail log,

bit 7

   = fail rtc,

bit 8

   = fail eeprom,

bit 9

= fail alarm,

bit 10-11

  = 1threshold

greater/1threshold less/2thresholds
external/2thresholds inside,

bit 12

 =Manual mode

UNIT16 

R/W 

0

40106

REMARKS:

Modbus connections: A+ and B-

;

Modbus Register reference: with reference to the logical address, for ex. 40010, corresponds to physical address n°9 as per

Modbus RTU standard

;

Modbus functions supported: 3 (Read multiple registers), 6 (Write single), 16 (Write multiple);

Any changes made by dip-switch required to switch off the power supply.

40005

Comment

Register Type R/W

Default
Value

Range

Modbus
Address

UNIT16

UNIT16

UNIT16

R

R

0

0...65535

40001

40002

40003 (MSW)

40004 (LSW)

UNIT16

R

UNIT16

R

UNIT32 (MSW) R/W

UNIT16

R/W

Float (MSW)

R

0…10000

0...4294967295

0...65535

40006

40007

40008

40009
40010

40011
40012

40013
40014

40015

Register Name

Machine ID

Firmware ID

ID

Status

Machine ID

Serial Number

Firmware ID

Status  Register:

bit  0

   =  fail  global,

bit  1

   =

alarm,

bit 2

= over range,

bit 3

 = under range,

bit 4

  = din status,

bit 5

  =dout status,

bit 6

   =

fail hw,

bit 7

  =fail log,

bit 8

  =fail rtc,

bit 9

  =fail

eeprom,

bit 10

 =fail sensor

Input Value

Totalizer

Output Value

Input Value

Input Value Normalized

Totalizer

Output Value (mV or uA)

Input Value

NOT USED

Third  wire
resistance

Analog input
type

Temperature
mode

Cold Junction
Temp

TC read

Digital Output

Dip-switch
status

NOT USED

Cold Junction Temperature

Float (MSW)

R

TC uV readed

Float (MSW)

R

40016

40017

40018

40019
40020

40021

40022

40023

UNIT16

R/W

Digital Output: bit 0= disabled/enabled

10

R

Output Analog
mode

40101

ENGLISH

Содержание QA-TEMP

Страница 1: ...2015 Analog output Contact Alarm RS485 Modbus DATALOGGER POWER SUPPLY RETRASMISSION OUTPUT PROTECTION INDEX 10 40 Vdc 20 28 Vac 50 60 Hz Onisolatedanalogoutput ABSORPTION Maximum 2 VA IP20 16 bit 50...

Страница 2: ...and 6 The Thermo couple whatever it is it requires the connection between termi nals 3 and 4 To connect a potentiometer use terminals 3 4 and 6 To make resistance measurements at 2 3 and 4 wires to fo...

Страница 3: ...ISTANCE at 400ohm or 4kohm at 2 3 4 wires Ni100 PT100 PT500 PT1000 at 2 3 4 wires TC type J K R S T B E N The QA TEMP sampling data every 100 msec you can choose to mediate the input value up to a max...

Страница 4: ...t starting as OPEN CONTACT that is if there is an alarm already set or active If you want to change the initial status of the digital output select CONTACT CLOSED from the dropdown in the upper right...

Страница 5: ...entiometer or resistor ANALOG OUTPUT the value uA or in mV output of the module This value follows the setting made via FACILE INPUT TYPE refered to the Modbus Register 101 that indicate the type of t...

Страница 6: ...reference to the logical address for ex 40010 corresponds to physical address n 9 as per Modbus RTU standard Modbus functions supported 3 Read multiple registers 6 Write single 16 Write multiple Any c...

Страница 7: ...Log name Log name 15 letters max UNIT16 R W 0 40129 Log name Log name 15 letters max UNIT16 R W 0 40130 Log name Log name 15 letters max UNIT16 R W 0 40131 RTC Year RTC Year UNIT16 R W 2000 2099 4100...

Страница 8: ...is document correspond to the products and technologies described This information may be amended or supplemented by technical and commercial requirements Disposal of Electrical Electronic Equipment A...