55
System Settings
Parameter
Default Values
Range
Export Hard Limit Level [%]
100
0 to 100
Export Hard Limit Time [s]
5
0 to 100
Export Soft Limit Level [%]
100
0 to 100
Export Soft Limit Time [s]
15
0 to 100
Generation Hard Limit Level [%]
100
0 to 100
Generation Hard Limit Time [s]
5
0 to 100
Generation Soft Limit Level [%]
100
0 to 100
Generation Soft Limit Time [s]
15
0 to 100
9
Fixed Power
DE
It limits the inverter output power below fixed power with Active Power SetPoint Gradient (= Pmax
per s)
Parameter
Default Values
Range
SetPoint Value [%]
100
0 to 100
Active Power SetPoint Gradient [%]
0.5
0.33 to 0.66
10
Freq-Watt P (Freq)
DE
The inverter changes the inverter output active power according to the system frequency in order to
support the system. Ramp rate of power and start frequency can be set as in the table below
Parameter
Default Values
Range
Ramp rate [%]
1
2 to 12
Start frequency [Hz]
50.2
50.2 to 50.5
11
Fixed cos
Φ
DE
You can set the inverter output power factor as well as leading (over) and lagging (under) of reactive
power.
Parameter
Default Values
Range
Cos
Φ
Value
1
0.95 to 100
Response time [ms]
10000
6000 to 60000
12
Cos
Φ
(P) curve
DE
If inverter output power is generated more than 50 %, it outputs lagging reactive power and is
operated in the power factor of 0.95 in the maximum output. At this time, the response time can be
set and the default time is 6000 ms