Installation Site

Please note the following guidelines that apply to the 
installation site:

• 

the modules have been tested according to iec 61215 
for operation in a temperate climate.

• 

solar modules are not suitable for use in explosive 
environments.

 

Ä

Do not operate solar modules near highly flammable gas 

and vapors (e.g. gas tanks, gas stations).

 

Ä

Do not install modules in enclosed space.

 

Ä

Do not install modules in locations where they may be 
submerged in water for lengthy periods.

 

Ä

Do not use modules as a substitute for the normal 

roofing (e.g. modules are not rainproof).

Prevention of Shadowing effects

optimal solar irradiation leads to maximum energy output:

 

Ä

For this reason, install the modules so that they face 
the sun. 

 

Ä

Avoid shadowing  (due to objects such as buildings, 
chimneys or trees). 

 

Ä

Avoid partial shading (for example through overhead 
lines, dirt, snow).

Limitations

the solar modules are designed for the following applica-
tions:

• 

operating temperatures from –40 °c to +85 °c  
(–40 °F to +185 °F). 

• 

Wind and snow loads up to max. 5,400 Pa (as tested 
according to iec 61215).

• 

installation using a mounting frame for solar modules.

Mounting frame requirements

Requirements for the mounting frame:

• 

conforms to the necessary structural requirements.

• 

compliant with local snow and wind loads.

• 

Properly fastened to the ground, the roof, or the façade.

• 

Forces acting on the module are relayed to the mounting 
substructure.

• 

Ensures sufficient rear ventilation of the module.

• 

Guarantees long-term stability. 

• 

Has electrochemical series that prevent corrosion among 
different metals.

• 

Allows for stress-free expansion and contraction due to 

temperature fluctuations.

 

Ä

ensure that no mechanical stresses (e.g., caused by vibrations, 
twisting, or expansion) are generated on the module. 

 

Ä

ensure that the clamps and the mounting frame are 
compatible.  

Clamp System requirements

use customary clamps that satisfy the following require-
ments:

• 

clamp width: 

 40  mm.

• 

clamp height compliant with a 35 mm frame height.

• 

clamp depth: 7–12 mm.

• 

clamps are not in contact with the front glass.

• 

clamps do not deform the frame.

• 

clamps that satisfy the structural requirements of the 
installation site.

• 

Long-term stable clamps that securely affix the module 

to the mounting frame.

Module orientation requirements

• 

Vertical or horizontal installation is permitted.

 

Ä

ensure that rain and melting snow can run off freely. 
No water accumulation.

 

Ä

ensure that the drainage holes in the frame are not 
covered. No sealing.

• 

A module with min 1,160 mm long 
cable can be wired as a "2nd next 
neighbor".

 

"2nd next neighbor" - Wiring without a 
return cable.

‚

 standard wiring with a return cable

Inverter

Inverter

1

2

 

Ä

maintain the permissible angle of 
inclination.

• 

minimum angle of inclination: 3°

• 

maximum angle of inclination: 80°

• 

Follow the directions for installation 
angles < 5° (“Grounding”, p. 20)

2.1  Technical specifications

2 PLaNNING

2.2  requirements

2 PLaNNING

DETAIL A

16 mm

8 mm

20.3 mm

150 mm

Junction bo×

Product label

≥ 

1160 mm

980 mm

1670 mm

4 × Fastening points (DETAIL A)

8 × Drainage holes

Cable with

connectors

Frame

6 × Grounding points ø 4.5 mm

1000

 mm

959.4 mm

Содержание Q.Pro-G3

Страница 1: ...Valid for Australia and New Zealand Q Pro G3 Q PRO BLK G3 Q Peak G3 Q PLUS G3 Installation and Operation Manual...

Страница 2: ...hibited Beware of possible danger or damage Categories Danger Risk of fatal injury Attention Risk of serious injury or damage to property Note Risk of damage to product Safety Regulations The solar mo...

Страница 3: ...ility for the functionality and safety of the modules Please observe the instructions for any other sys tem components that may be part of the complete solar power system It may be necessary to carry...

Страница 4: ...to the ground the roof or the fa ade Forces acting on the module are relayed to the mounting substructure Ensures sufficient rear ventilation of the module Guarantees long term stability Has electroc...

Страница 5: ...unting options Specifications Module type Mounting option Clamping range1 Mm Allowed static load2 PA TEST LOAD acc IEC 61215 PA Q PRO G3 Q PRO BLK G3 Q PEAK G3 Q PLUS G3 CL1 Push 245 345 346 445 3500...

Страница 6: ...ts ground leaks or defective insulation Ensure that the maximum reverse current load capacity indicated in the data sheet is observed In order to limit reverse currents that may occur we recommend usi...

Страница 7: ...ginal packaging until installation Store the modules securely in cool and dry rooms The packaging is not weatherproof Danger Risk of fatal injury due to electric shock Do not install damaged modules I...

Страница 8: ...l modules in windy or wet weather Danger Risk of fatal injury due to electric shock Only use dry insulated tools Do not carry out the installation alone Only install undamaged modules and components D...

Страница 9: ...rter and the wiring with extreme caution Ensure that the modules are disconnected at the inverter prior to separation Be sure to observe the specified time intervals after switching off the inverter H...

Страница 10: ...shock Ensure that all electrical components are in a proper dry and safe condition A module with 1 160 mm long cable can be wired as a 2nd next neighbor 2nd next neighbor Wiring without a return cabl...

Страница 11: ...of performance Maintenance The system should be inspected by an installer annually to check the following all system components sit securely and are corrosion free the connection is secure and all ele...

Страница 12: ...20 Berry Street North Sydney NSW 2060 Australia TEL 61 0 29016 3033 FAX 61 0 269016 3032 EMAIL q cells australia q cells com WEB www q cells com au Subject to change without notice Hanwha Q CELLS Gmb...

Отзывы: