5.7.4
Output Module Outputs?
This option enables the addition of a wired output module to the Control Panel, as well as
programming of the PGM options for the outputs on the module.
5.7.5
Keypad Outputs?
Allows the programming of the PGM options for the outputs located on the wired keypads.
5.7.6
Reader Outputs?
Allows the programming of the PGM options for the outputs located on the wired readers.
5.7.7
User Outputs?
These outputs are used for creating automation control for devices. The user can control them
remotely from the user menu on the keypad or via the Home smartphone APP. The
automated user outputs can be programmed (either latched or timed).
Polarity of the PGMs: The polarity of the outputs are normally switched negative, i.e. normal status
OFF = 0v and in active status ON = 12v.
NOTE: The PGM Outputs polarity cannot be inverted.
No. Output
Type
Active
Restore
0000 Not
Used
0001 Fire
At a fire alarm activation.
When a valid code is entered.
0002 Hold Up Any
At a hold up (HU) /personal attack
activation.
When a valid code is entered.
0003 Intruder Any
At an intruder alarm from any area.
At first valid code entry.
0004 Final Set All
When ALL areas are set.
At code entry to unset.
0005 Misoperation
(Abort)
When the system is silenced after an
intruder alarm has been activated.
After two minutes.
0006 Confirmed
Any
After two intruder alarm activations.
At the next code entry.
0007 Tamper Any
Tamper alarm activation in any area.
At code entry to silence
and at the end of the confirm time.
0008 Duress Any
At a duress alarm in any area.
When a valid code is entered
0009 HU Device Any
At alarm on a HU input only, from any
area (this does not include the keypad
HU).
When a valid code is entered.
0010 Gas
At a gas alarm
When a valid code is entered.
0011 Set Fail
Pre-set time after the start of the exit
time, if the exit procedure is not
complete.
At code entry to reset.
0012 Entry Deviation
When a deviation from the entry route
occurs (during entry time).
At code entry to unset.
0013 Secure
Intruder
Any
At alarm, after exit time started, until
unset.
At the first valid code entry
and at end of confirm time.
0014 Siren Any
When the alarm is live.
When the alarm is silenced or when
the siren timer expires.
0016 Strobe Any
When the alarm is live.
When the alarm is silenced or when
the siren timer expires.
0017 Omit Rearm Any
Input omitted if active (or in alarm
condition) at the end of the confirmation
time.
When the system is unset.
0018 Unconfirmed Any
At any intruder of tamper alarm.
At code entry to silence.
0019 Can Set All
When all inputs but the ‘Entry Delay’ and
‘Follow’ inputs are closed.
If fault exists, and after final set.