3
(d) Set the parameter according to below recommendation, the max. charge current refer
to the specific battery amount of real application. Then click ‘Apply’. According to the
inverter limitation, for 2kW&3kW inverter max. is 25A, for 5kW max. is 100A, for 10kW
max. is 200A.
2.
WKS
-
Off-grid
Solution
(
1
)
General
Compatible
Condition:
Battery Type
US2000B/Phantom-S
Inverter Type
W
KS
1K-48
W
KS
3K-48
W
KS
4K
W
KS
5K
Max.
charge current
33A
33A
140A
140A
Recommend
battery Amount
According to load requirement and inverter rated power.
Battery Amount N = Load power/1200W
Communication Not required, but need finish the setting on Inverter.
DOD
80%
Working Temp.
0 - 50
℃
(Indoor operation)
Charge/Dischar
ge Current
N*25, N = Battery amount
Warranty
5yrs