(d) Set the parameter according to below recommendation, the max. charge current refer
to the specific battery amount of real application. Then click ‘Apply’. According to the
inverter limitation, for 2kW&3kW inverter max. is 25A, for 5kW max. is 100A, for 10kW
max. is 200A.

2.

WKS 

-

 

Off-grid

 

Solution

(

1

)

 

General

 

Compatible

 

Condition:

Battery Type

US2000B/Phantom-S

Inverter Type

W

KS

 

1K-48

W

KS

 

3K-48

W

KS

 

4K

W

KS

 

5K

Max.
charge current

33A

33A

140A

140A

Recommend
battery Amount

According to load requirement and inverter rated power.

Battery Amount N = Load power/1200W

Communication Not required, but need finish the setting on Inverter.
DOD

80%

Working Temp.

0 - 50

(Indoor operation)

Charge/Dischar
ge Current

N*25, N = Battery amount

Warranty

5yrs

Содержание Phantom-S

Страница 1: ...but need finish the setting on Inverter software DOD 80 Working Temp 0 50 Indoor operation Charge Dischar ge Current N 25 N Battery amount Warranty 5yrs 3 Inverter set up a Connect PV or Grid power t...

Страница 2: ...2 b Open Solarpower exe the inverter set up software Log in c Press Parameters Setting...

Страница 3: ...00A 2 WKS Off grid Solution 1 General Compatible Condition Battery Type US2000B Phantom S Inverter Type WKS 1K 48 WKS 3K 48 WKS 4K WKS 5K Max charge current 33A 33A 140A 140A Recommend battery Amount...

Страница 4: ...4 3 Inverter set up a Connect Inverter with battery wake up inverter b Press Enter for 5s to enter into the setting...

Страница 5: ...et to N 25A N battery amount Program 05 Set to USE Program 12 Set to 48V Program 13 Set to 51V Program 26 Set to 53 2V Program 29 Set to 47 5V Note WKS Inverter can only be waked up via battery if the...

Страница 6: ...in the m must be we d the electric ery away fro heck produc t with the loc to cut off the o not mistake device the battery a e battery is de ell grounded cal paramete om water and Before ct and packin...

Страница 7: ...because equipment s o be moved wn the battery w atteries work ble the batte wder fire extin r or disassem do not unde of violation o afety standa I or repaired with different king with faul ery QC tab...

Страница 8: ...esult in ele rendering it i ong time it is an 80 rged within 1 de ust be discon er within 24 ho nts to clean b lammable or attery includ with PV solar w excluded for hibited to inse Safety specific ba...

Отзывы: