When each battery group
’
s current is >120A, this battery group must configure 2 pair
external power cables like the diagram.
⚫
The details of ADD Switch setting also can see the menu of battery.
3.2.2 Cables Connection for CAN (single HUB)
⚫
Each battery group can configure maximum 8pcs US2000B Plus or 8pcs US3000.
⚫
LV-Hub-A configures maximum 5 group batteries.
⚫
When each battery group
’
s current is >120A, this battery group must configure 2 pair
external power cables like the diagram.
⚫
The details of ADD Switch setting also can see the menu of battery.
⚫
When using with SMA SUNNY ISLAND, the ADD on HUB(or master HUB if there are multiple
HUBs) must be 000011(for B14V0105 presenting on product label) or 000101 (for B14V0106
presenting on product label).
3.3 Cables Connection for US2000C/US3000C/UP5000 under CANBUS
Connect power cable first:
1) each pair of cable hold max 100A constant current. Connect enough pairs of cable based on
calculation of system current.
2) Suitable protection breaker between battery system and inverter is required.