background image

24

PX 181

Max. 14 of PX181s

PX 181

PX 181

Scheme connection of multiple panels PX181 and Px140 controller:

The panels should be connected on a serial basis, with the last panel being finished with a 120 

Ω 

terminal (insert a resistor with 120 Ω resistance between the positive pin and the negative pin).

Even if you want to connect just one PX181 panel to PX140, it is necessary to insert the 
120

Ω terminal.

GND

terminator

(resistor 120 Ohm)

terminator

(resistor 120 Ohm)

For communication between PX140 and PX181 and also between touch panels connected in 
series, use screened twisted pair cables with impedance of 120

, e.g.

• RS 485 LAPP UNITRONIC® LiYCY (TP) paired 2 x 2 x 0.14
• LI2Y(St)-CY 1x2x0,22mm2 120 

For the purpose of connecting the device, you can also use a twist cable and, in that case, 
you need to connect the white-and-orange colour of the cable as a plus (+), and the orange 
colour as a minus (-); and the white-and-brown colour as the screen.

Ω

Ω

DMX  OUT

REMOTE CONTROL

DMX  IN

EXT CTRL

+

-

12-24V DC

+5 V input

12 1110 15 14 13

4 5 

24

9

2

16 17 18 19 20 21

22 23

PX 140

Architectural
Lighting
Controller

USB LINK

DMX OK

POWER

www.pxm.pl

GND

GND GND GND

GND

GND

GND

+  - 

GND GND GND

GND GND GND

GND GND

The view of the terminal block

on the back of the PX181 casing

cables between the controller

and the panel should be connected

in the correct order accordance 

with the designations

 EXT CTRL on PX 140 

and PX 181: + to +, - to -

and GND to GND

Содержание PANEL DOTYKOWY

Страница 1: ...MANUAL TOUCH PANEL PX 181 R...

Страница 2: ...ty conditions 3 3 Operation of the device 3 1 Clock 3 2 Panel number and home page 3 3 Signals from PX140 3 4 Screen settings 3 5 Changing passwords 4 PC software 4 1 Installation 4 2 Application wind...

Страница 3: ...set forth below 1 The device can be connected to 12 V DC stabilised voltage with current carrying capacity compatible with technical data 2 All the conductors should be protected against mechanical a...

Страница 4: ...a home page No 1 ascribed Other users have home pages with consecutive numbers The access to user s home page can be protected with a password To navigate to a given page select an icon of a relevant...

Страница 5: ...ing panel indicator lights Irrespective of whether the panel responds to a given signal or not in the Signals from PX140 window you can see all signals coming from the control While configuring the pa...

Страница 6: ...lete the password press enter on the keyboard without entering any password In the Screen page you can set main brightness of the screen and activate the screensaver option You can set brightness leve...

Страница 7: ...llation process will be completed 2 Licence to continue the user needs to accept the terms and conditions of the licence agreement 3 Selection of components the user can choose to install the applicat...

Страница 8: ...e Item area configuration of an item marked Pages area a list of all pages and items located within those pages Preview a preview of a page marked within the pages area Quick access bar quick access t...

Страница 9: ...ection 4 3 4 Clock Section 4 3 5 Page Section 4 3 Add Control Section 4 3 3 SnapToGrid SetXGrid SetYGrid Px181 USB serves communication with the panel SaveAllPages saves all pages created within the p...

Страница 10: ...ze of the grid in X andYaxes 4 2 2 Status bar The status bar displays information about connection with the device The panel connects with the app automatically upon being connected to the computer If...

Страница 11: ...ge the items located on the page To have an even arrangement you can activate the snap to grid feature Add SnapToGrid The size of the grid separately for axes x and y can be adjusted within the 1 160x...

Страница 12: ...Delete key Context menu If you click the right mouse button on a page on the list a context menu will be displayed that includes a compilation of the most frequently used functions Delete deletes a p...

Страница 13: ...ange between 1 and 24 Input 1 Off a range between 1 and 24 NoAction no action at all 3 colour sliders RGB you can set brightness of each colour component of an object within the range between 0 and 25...

Страница 14: ...keys Ctrl C Ctrl v Within the item area you can modify the properties of the button highlighted Available parameters Width and height fields that allow you to change the dimensions of a button Positio...

Страница 15: ...to determine a position of the upper left corner of the slider Orientation vertical and horizontal orientation Action Number you can select an event programmed on the PX140 controller that will be tr...

Страница 16: ...olour it is supposed to display State OFF the fields that let you determine a signal to which the control light should respond by switching off and which colour it is supposed to display 4 3 3 Control...

Страница 17: ...between the pages and events triggered by individual items can be exported to a PDF file To do so select File Save configuration to PDF in the toolbar A preview window will be opened where you can hi...

Страница 18: ...rom your computer You can load your panel configuration to the panel at any time For that purpose connect the panel to the computer using the USB cable The status bar will display information that the...

Страница 19: ...for the first time ever the operating system will run a standard new device installation The panel connected to the computer will be detected and the system will automatically activate a wizard searc...

Страница 20: ...ectory where the configuration application was installed By default it is the Program Files PXM Px181 usb_driver directory When the driver has been successfully installed the configuration application...

Страница 21: ...ice 21 The device has a concealed mounting box and a front frame to be attached to the box with two screws 190 140 55 146 Dimensions of the mounting box 85 5 7 Dimensions of the device 58 160 212 3 Mo...

Страница 22: ...aled mounting box to the wall by means of 4 assembly screws see the positioning of the screw holes on the previous page When the box has been mounted within the wall attach the panel body to it To tha...

Страница 23: ...ned to work with the PX140 The PX140 control must have the option Enable communication with external panels turned on A scheme of connections between multiple PX181 panels and the PX140 control is vis...

Страница 24: ...20 e g RS 485 LAPPUNITRONIC LiYCY TP paired 2 x 2 x 0 14 LI2Y St CY1x2x0 22mm2 120 For the purpose of connecting the device you can also use a twist cable and in that case you need to connect the whit...

Страница 25: ...ith PX140 2 12V DC min cable cross section 0 5 mm 4W Steel Anodised aluminium 1 2 kg 5 7 320 x 240 Screened twisted pair cable with 120 impedance e g RS485 LAPP UNITRONIC LiYCY TP pair 2x2x0 14 GND GN...

Страница 26: ...N OF CONFORMITY according to guide lines 2004 108 WE tel 48 12 626 46 92 fax 12 626 46 94 48 e mail info pxm pl http www pxm pl ul Przemys owa 12 30 701 Krak w Poland Theater stage consoles digital di...

Отзывы: