background image

  PV500-17  05-2000 

Section 17 

11

MAXIM 

TROUBLESHOOTING SUGGESTIONS 

AXIAL FLOW GAS BURNER 

 

1. 

BURNER FAILS TO START 

 

Defective On/Off switch.

 Replace switch. 

 

A. 

Control circuit has an open control 
contact.

 Check limits, low water cutoff, proof 

of closure switch and others as applicable. 

 

B. 

Bad fuse or switch open on incoming 
power source.

 Correct as required. 

 

C. 

Flame safeguard control safety switch 
tripped out.

 Reset and determine cause for 

apparent flame failure. 

 

D. 

Loose connections or faulty wiring.

 

Tighten all terminals screws and consult 
wiring diagram furnished with the burner. 

 

E. 

Flame safeguard control starting circuit 
blocked due to flame relay being 
energized.

 Possible defective scanner or 

flame rod  - replace. Possible defective 
amplifier - replace. Scanner actually sighting 
flame due to leaking fuel valve  - correct 
unwanted flame cause. Defective flame 
safeguard control - replace. 

 

F. 

Defective blower motor.

 Check for free 

rotation of fan wheel. Repair or replace. 

 

G. 

Air proving switch is not properly 
adjusted.

 See Section 15, page 11. 

 

2. 

OCCASIONAL LOCKOUTS FOR NO 
APPARENT REASON

 

 

A. 

Gas pilot ignition failure.

 Check to see that 

ignition is instant and that flame signal 
readings are stable and above minimum 
values. Use a manometer or 0 to 10" W.C. 
gas pressure gauge to make certain that 
pressure is as recommended. 

 

B. 

Loose or broken wires.

 Check all wire nut 

connections and tighten all terminal screw 
connections in panel and elsewhere as 
appropriate. 

 

C. 

With flame safeguard controls that 
incorporate the air flow switch in the non-
recycling circuit,

 ensure that when main 

flame lights, the air flow switch is not so 
critically set as to allow occasional 
momentary opening of the air switch 
contacts. 

 
 

 

D. 

Occasional low voltage supply.

 Have local 

utility correct. Make certain the burner control 
circuit transformer (if supplied) is correct for 
the voltage and power (VAC) being supplied. 

 

E. 

Occasional low gas supply pressure.

 

Have local utility correct. 

 

3. 

BURNER MOTOR RUNS, BUT PILOT DOES 
NOT LIGHT

 

 

A. 

Gas supply to burner shut off.

 Make sure 

all manual gas supply valves are open. 
Automatic high pressure valve at meter such 
as "Sentry" type tripped shut due to high gas 
pressure. Reset valve and correct cause for 
trip out. 

 

B. 

Pilot solenoid valve not opening.

 Listen 

and feel for valve actuation. Solenoid valve 
not being powered. Check electrical circuitry. 
Replace coil or entire valve if coil is burned 
out. 

 
C. 

Defective gas pilot regulator.

 Replace. 

 

D. 

Gas pressure too high or too low at pilot 
orifice 

(if supplied). Check orifice size in gas 

pilot assembly. Replace if incorrect. Readjust 
pressure as required. 

 

E. 

Defective ignition transformer.

 Replace. 

Incorrect ignition electrode settings.

 

Readjust as required. 

 

F. 

Defective flame safeguard control or plug 
in purge timing card.

 Replace as required. 

 

G. 

Air flow switch not making circuit.

 Check 

out electrically. Defective air flow switch- 
replace. Air switch negative pressure 
sensing tube out of position-reposition as 
necessary. 

 

4. 

BURNER MOTOR RUNS & PILOT LIGHTS, BUT 
MAIN GAS FLAME IS NOT ESTABLISHED.

 

 
A. 

Main shut off or test cock closed.

 Check to 

make certain fully open. 

 

B. 

Pilot flame signal reading too low to pull in 
flame safeguard relay.

 Readjust as required. 

Содержание MAXIM

Страница 1: ...WITCH NOT FURNISHED BY PVI CAUTION Temperatures higher than 130 F increase the risk of scald injury IMPORTANT Clearance to unprotected combustible material must be 8 min at top sides and rear and 24 min in front MAXIM FOR YOUR SAFETY WHAT TO DO WHEN YOU SMELL GAS DO NOT try to light any appliance DO NOT touch any electrical switch DO NOT use any phone in your building IMMEDIATELY call your gas sup...

Страница 2: ...NVESTIGATING THE CAUSE OF ANY REPORTED OCCURRENCES OF DELAYED IGNITION 1 Using an appropriate bubble detection solution thoroughly coat all gas train pipe connections If any bubbles are detected the leaking connection must be tightened recoated and rechecked to assure stoppage of the leak 2 Attach a manometer to measure gas pressure at the manual gas shutoff valve located just upstream of the gas ...

Страница 3: ...ndhole for inspection and cleaning See Figure 17 1 page 1 To inspect tank for scale buildup remove the handhole cover If scale is present it can be loosened with a high pressure stream of water The smaller pieces can be flushed through the drain and the larger pieces removed by hand through the handhole The frequency of inspections will be determined by the rate of scale buildup Intervals of 30 60...

Страница 4: ... safety inspections and encourage the preparation of an event log for this purpose All recorded events should be dated fully described and signed by the individual performing the service repair or inspection See Table 17 1 page 5 for sample of Inspection Record CALL YOUR PVI CUSTOMER SERVICE REPRESENTATIVE IF YOU HAVE ANY QUESTIONS 1 800 433 5654 Instructions for Taking Water Heater Out of Service...

Страница 5: ...SPECTION TANK FLUSH CLEANOUT TANK FITTING INSPECTION VENT INSPECTION THERMOSTAT INSPECTION GAS TRAIN LEAK TEST Recommended Inspection Intervals YEARLY 6 MONTHS 6 MONTHS 3 MONTHS 6 MONTHS YEARLY YEARLY YEARLY TABLE 17 1 NOTE Burner Inspection and Combustion Analysis should be done by a factory authorized service person ...

Страница 6: ...ervice agency to ensure safe and efficient operation TYPICAL CONSTRUCTION FIGURE 17 2 1 FAN HOUSING 9 AIR PROVING SWITCH 2 AIR DAMPER 10 DAMPER ADJUSTMENT KNOB 3 GAS NOZZLE ASSEMBLY 11 MANUAL SHUTOFF VALVES 4 PRESSURE PLATE 12 GAS PRESSURE REGULATOR 5 BLAST TUBE BURNER HOUSING JUNCTION 13 GAS VALVE 6 IGNITION TRANSFORMER 14 AUXILIARY GAS VALVE 7 IGNITION ELECTRODE 15 MAIN GAS TRAIN 8 FLAME SENSING...

Страница 7: ...es and pressure plate attached Disconnect the electrode wires and take care not to damage the insulation on the electrodes 7 With the electrodes exposed check them for the proper settings as called for in Figure 17 3 page 8 Check for any hairline cracks in the insulators Should replacement of burner electrodes be required certain procedures must be followed In all cases removal of the electrodes i...

Страница 8: ...let pressure of the burner This is the pressure measured before all components in the gas train The manometer must stay connected throughout the testing as the inlet pressure must be monitored during the firing of the burner Record static pressure it must not exceed 14 W C Pressures above this could cause damage to the diaphragm in the gas valve or pressure regulator 15 Burners with pilot inputs o...

Страница 9: ...rners is 8 W C flow If the required manifold cannot be reached check the inlet pressure It should be a minimum of that shown on the heater decal with the burner running on full input It is important that the incoming pressure does not fall below these minimums or nuisance control lockouts could occur NOTE Where low gas pressure is a problem special arrangements may have been made to fire the burne...

Страница 10: ...pening and read gross stack temperature maximum gross stack is to be 450 F minimum net stack is to be 300 F NOTE net temperature is the total stack temperature less room temperature If an excessively high gross stack temperature is recorded check the flue tubes for turbulators i Make sure the air shutter is locked securely in place 18 On burners with pilots recheck pilot to make sure its operation...

Страница 11: ...ate the air flow switch in the non recycling circuit ensure that when main flame lights the air flow switch is not so critically set as to allow occasional momentary opening of the air switch contacts D Occasional low voltage supply Have local utility correct Make certain the burner control circuit transformer if supplied is correct for the voltage and power VAC being supplied E Occasional low gas...

Страница 12: ...t B Gas cock upstream of train inlet not fully open Check and correct C Gas line obstructed Check and correct D Gas train main and or lead test cocks not fully open Check and correct E Gas supply line between gas company regulator and burner inlet too small Check supply pressure at meter determine pressure drop and increase line size as required or raise supply pressure to compensate for small lin...

Отзывы: