PVI Industries PV500-2 Скачать руководство пользователя страница 5

PV500-2  06/10 

 

 

Section 2 

 
4.  After 20 to 30 minutes of operation or when water in 

the tank is above 120°F, insert CO (carbon monoxide) 
tester in flue damper opening under the draft diverter 
(125 gallon models) or in the flue collector opening 
(250 gallon models). CO reading must be less than 
.02% (or 200 ppm). 

 
5. Insert 

CO

2

 (carbon dioxide) tester in the flue damper 

opening under the draft diverter (125 gallon models) 
or in the flue collector opening (250 gallon models) 
and take reading. CO

2

 should be 6 to 8%. 

 

NOTE:

 Monitoring CO and CO

2

 readings in vent after the 

draft diverter will give erroneous readings. These 
measurements must be taken as flue gases exit the 
heater flue collector under the draft diverter as 
dilution with ambient air from the draft diverter occurs 
in the vent. 

 
6.  Insert temperature gauge in ¼" hole and read vent 

temperature. Temperature should be at least 300°F 
but less than the room temperature plus 400°F when 
the water temperature is approximately 130°F. 

 
7.  Connect micro-amp meter as shown in Figure 2-6 and 

check micro-amps. A minimum of two micro-amps is 
required for proper operation. 

 
8.  Record the following information for future use: 

 
A.  Inlet gas pressure ________________"W.C. 
 
B.  Gas pressure, manifold (step 2) _____ "W.C. 
 
C.  Vent draft (step 3) ________________"W.C. 
 

(should be minimum of 1 in. W.C.) 

 
D.  CO reading (step 4) ______% (less than .02%) 
 
E. CO

2

 reading (step 5) __________% (6-8%) 

 
F.  Vent gas temperature (step 6) 
 

Gross__________________

F. 

 
Less Ambient____________°F. 
 
Net____________________°F. 

 
G.  Micro-amps reading (step 7)______________. 

 

 

COMBINATION GAS VALVE 

 

Figure 2-5 

 
 
 

MICRO-AMP METER HOOK-UP 

 

Figure 2-6 

 

Содержание PV500-2

Страница 1: ...iting device 10 Drip leg set at 200 F 11 Gas supply line 5 Upper operating thermostat 12 Handhole cleanout set at 130 F 6 Operating thermostat set at 120 F Not furnished by PVI CAUTION TEMPERATURES HI...

Страница 2: ...wiring is brought to the terminal block in the lower part of the enclosure on the water heater See Figures 2 2 2 3 and 2 4 FOR YOUR SAFETY USE ONLY COPPER WIRE OF PROPER SIZING FOR INCOMING SERVICE D...

Страница 3: ...e combustion products either to existing overhead breeching or to an appropriate outside location 1 The control manufacturer s installation and service manual and start up procedures for the control s...

Страница 4: ...mostat setting the control circuit opens which closes both the pilot and main burner gas valves terminating burner operation 6 The flue damper is closed NOTE The spark ignition system provides additio...

Страница 5: ...dilution with ambient air from the draft diverter occurs in the vent 6 Insert temperature gauge in hole and read vent temperature Temperature should be at least 300 F but less than the room temperatu...

Страница 6: ...d the tank inspected for scale buildup If scale is present it can be loosened with a high pressure stream of water The smaller pieces can be flushed through the drain and the larger pieces removed by...

Страница 7: ...llows a Turn off all power and fuel supplies b Drain and flush tank as previously discussed c Tag power switch es indicating that fuel is off and tank is empty d To restart refill tank with water and...

Отзывы: