PVI ATMOSPHERIC GAS WATER HEATERS 

TYPICAL CONSTRUCTION 

MANUFACTURED AFTER JANUARY 1, 1994 

 

 

Figure 2-1 

 

1.  Vent stack * 

7. Control switch(es) and fuse(s) 

2.  Draft diverter (hood) 

8. Gas valve 

3.  Flue damper (on some models) 

9. Pilot line 

4.  Temperature limiting device 

10. Drip leg * 

  (set at 200°F) 

11. Gas supply line * 

5.  Upper operating thermostat 

12. Handhole cleanout 

  (set at 130°F) 

 

6. Operating 

thermostat 

 

  (set at 120°F) 

(* Not furnished by PVI) 

 

 
CAUTION: TEMPERATURES HIGHER THAN 125°F INCREASE THE RISK OF SCALD INJURY! 
 

 

IMPORTANT: Clearances to unprotected combustible material must be 8" minimum at top, sides and rear, and 24" in front. 
Clearances for servicing and inspection must be 18" minimum at sides and rear and 24" minimum in front.  

Содержание PV500-2

Страница 1: ...iting device 10 Drip leg set at 200 F 11 Gas supply line 5 Upper operating thermostat 12 Handhole cleanout set at 130 F 6 Operating thermostat set at 120 F Not furnished by PVI CAUTION TEMPERATURES HI...

Страница 2: ...wiring is brought to the terminal block in the lower part of the enclosure on the water heater See Figures 2 2 2 3 and 2 4 FOR YOUR SAFETY USE ONLY COPPER WIRE OF PROPER SIZING FOR INCOMING SERVICE D...

Страница 3: ...e combustion products either to existing overhead breeching or to an appropriate outside location 1 The control manufacturer s installation and service manual and start up procedures for the control s...

Страница 4: ...mostat setting the control circuit opens which closes both the pilot and main burner gas valves terminating burner operation 6 The flue damper is closed NOTE The spark ignition system provides additio...

Страница 5: ...dilution with ambient air from the draft diverter occurs in the vent 6 Insert temperature gauge in hole and read vent temperature Temperature should be at least 300 F but less than the room temperatu...

Страница 6: ...d the tank inspected for scale buildup If scale is present it can be loosened with a high pressure stream of water The smaller pieces can be flushed through the drain and the larger pieces removed by...

Страница 7: ...llows a Turn off all power and fuel supplies b Drain and flush tank as previously discussed c Tag power switch es indicating that fuel is off and tank is empty d To restart refill tank with water and...