LOW NOx MAXIM • PACKAGED GAS WATER HEATER

POLYSHIELD

®

 POLYMER-LINED STORAGE TANK 

125 GALLON TANK SERIES 

 

MODEL NUMBER 

20 P 125A-MXS 

27 P 125A-MXS 

40 P 125A-MXS 

 

GPH Recovery at 40° to 120° F 

245 

330 

490 

 

GPH Recovery at 40° to 140° F 

195 

260 

390 

 Input 

Btu/h 

199,000 

270,000 

399,000 

 

Minimum gas inlet pressure – " W.C. 

5.5 

5.5 

5.5 

Cold Inlet - NPT 

Hot Outlet - NPT 

Drain - NPT 

I - Beam Skids 

3 X 34-1/2 

3 x 34-1/2 

3 x 34-1/2 

E Overall 

Depth 

45 

45 

45 

F Overall 

Height 

75 

75 

82 

Flue Outlet Diameter 

Gas Inlet - NPT 

1/2 

3/4 

3/4 

Motor HP  120 V, 1Ø, 60 Hz. 

1/6 

1/6 

1/6 

 Motor 

Amps 

1.75 

1.75 

1.75 

Height to Outlet 

65 

65 

73 

Height to Inlet 

28 

28 

36 

 

Approx. Shipping Weight - lbs 

1020 

1070 

1130 

Recoveries based on 82% thermal efficiency. ASHRAE 90.1 compliant. 

1. Control Enclosure 
2. ASME Temperature & 
  Pressure Relief Valve 
3. 3” NPT Handhole

Dimensions are in inches unless otherwise specified. 
For standard and optional equipment, see Form # PV6377. 
 
 

 

 
 

Product is patented in the U.S., Canada, and Mexico. 

 

PVI INDUSTRIES, LLC 

FORT WORTH, TEXAS 76111 

PV 6378  02/05

 

(800) 784-8326  

  www.pvi.com 

STANDARD GAS PRESSURE REQUIREMENTS: 

SEE TABLE FOR MINIMUM PRESSURE BY MODEL NUMBER. 

MAXIMUM STATIC PRESSURE: 9" W.C. 

FOR GAS PRESSURES OUTSIDE OF THIS RANGE,  

CONTACT YOUR PVI REPRESENTATIVE. 

 

STANDARD ELECTRICAL REQUIREMENTS: 

CONTROL VOLTAGE

:  120V, 1Ø, 60 HZ., 2 AMPS 

 
 

VENTING REQUIREMENTS: 

-.02" TO -.06" W.C. (NEGATIVE PRESSURE). 

TYPE B VENTING. 

THE ENTIRE VENT SYSTEM  SHOULD NEVER BE SIZED BASED UPON THE 

VENT CONNECTION DIAMETER EXCLUSIVELY. 

FOR PROPER VENT SIZING, CONSULT THE NATIONAL FUEL GAS CODE 

UNDER "FAN-ASSISTED". 

 