Location

 

 

The  location  selected  must  provide  for  electrical  service, 
cold or hot water supply, and sanitary drain.

 

 

When  selecting  a  location,  try  to  keep  the  humidifier 
within 10 feet (305 cm) of the duct to avoid unnecessary 
heat  losses,  condensation  within  the  steam  supply  line 
and excessive pressure buildup in the reservoir.

 

 

Visible “fog” will saturate and condense when it contacts 
objects  such  as  turning  vanes,  filters,  fans,  elbows,  or 
take

-

offs.    The  warmer  the  air,  the  more  easily  it  will 

dissipate the visible steam.  The most active and warmest 
portion of the duct will provide better mixing of the steam 
and  air.    The  injection  tube  should  be  mounted  a 
minimum of 2 feet (61 cm) downstream from an elbow or 
other uneven air flow area.

 

 

Avoid mounting single

-

style injection tube(s) closer than 8

-

10  feet  (244

-

305  cm)  upstream  of  objects  that  could 

become  saturated  and  condense  the  steam  (reference 
paragraph  above).   If  the  duct  layout  does  not  provide  a 
straight,  unobstructed  run  of  8

-

10  feet  (244

-

305  cm),  a 

multiple  injection  tube  system  should  be  considered  to 
reduce the visible steam travel distance.

 

 

For  Fast

-

Pac  and  Insty

-

Pac  multiple  tube  assemblies 

please  consult  factory  for  job  specific  non

-

wetting 

distances.

 

 

Reference  Fast

-

Pac  or  Insty

-

Pac  O&M’s  for  full 

installation details.

 

 

CAUTION: 

Do  not  humidify  upstream  of  filters.  Consult 

factory.

 

 

CAUTION: 

Smoke  detectors  should  not  be  located 

downstream of injection tube assemblies.

 

 
 

Location of Control Sensors

 

 

It  is  important  to  avoid  mounting  any  control  sensors 
within  the  visible  steam.    The  control  sensors  should  be 
mounted  a  minimum  of  8

-

10  feet  (244

-

305  cm) 

downstream from the humidifier injection tube.  Due to the 
temperature  rise  that  exists  within  the  visible  steam 
dissipation area, thermostats should not be mounted near 
the  injection  tube.    High

-

limit  humidistats  should  be 

installed  before  any  duct  obstruction  to  make  sure  the 
humidifier  is  interrupted  before  saturation  can  occur  on 
the object.  The high

-

limit should be mounted a minimum 

of 8

-

10 feet (244

-

305 cm) downstream from the injection 

tube.  Installing  the  high

-

limit  closer  than  8  feet  (244  cm) 

from the humidifier may cause erratic control. 

 

Mounting

 

 

Mounted from the wall.  The humidifier should be mounted 
dead  level  in  both  directions.    PURE  Humidifier  Co. 
supplies the wall mounting bracket.  Bracket is mounted to 
wall  studs  first.    The  bracket  must  be  mounted  to  wall 
studs  or  additional  support  must  be  provided  in  the  field.  
ECDDR cabinet is then hung on the slip

-

fit bracket.

 

 

Drain Pan Mounting

 

 

A  drain  pan  is  an  additional  safety  feature  which  may  be 
required to be supplied in the field.  In a proper humidifier 
installation,  a  drain  pan  is  not  required.    However,  if  the 
humidifier  and  injection  tube  are  located  in  an  area  that 
contains  valuable  equipment  or is  a  water sensitive  area, 
PURE Humidifier Co. recommends the addition of a drain 
pan under the humidifier and under the injection tube.  The 
drain  pan  should  extend  past  all  edges  of  the  humidifier 
and if installed in the duct, it should extend a minimum of 3 
feet (91 cm) downstream from the injection tube.  The pan 
should  be  of  a  size  which  is  sufficient  to  retain  sudden 
drainage of the humidifier’s contents.  The pan should be 
drained to a sanitary drain. 

 

 

Injection Tube Installation

 

 

Single tube units should have the injection tube installed in 
the center of the duct.  Multiple tube units should have the 
tubes  staggered  within  the  duct.  See  Injection  Tube  and 
Flexible Hose Installation on page 8 for details.

 

 

Injection  tube  should  be  pitched  2  inches  (5  cm)  per  foot 
(31 cm), back to the humidifier.  If proper pitch cannot be 
maintained, or the injection tube is mounted lower than the 
humidifier, a drain “tee” will be required.

 

 

Install  the  tube  with  the  steam  ports  injecting  steam  up.  
NOTE:  If  narrow  ducts  (6”/15  cm  or  less,  in  height)  are 
utilized, install the tube with the steam ports injecting with 
the air flow slightly (2 o’clock position).

 

 

Galvanized  steel  duct  plates  are  provided  to  seal  the 
opening where the tube enters the duct.

 

 

Multiple Injection Tube Assemblies

 

 

See page 9 for details.

 

Location & Mounting

 

Содержание ECDDR Series

Страница 1: ...ter ECDDR Series Electric Humidifier Installation Instructions Operation and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS Our results are comforting Form No ECDOM 10 19 PURE HUMIDIFIER and INTAC are registered trademarks of PURE Humidifier Co ...

Страница 2: ...ctrical contractors and must be in compliance with local state federal and governing codes If installed improperly this product may cause damage to property severe personal injury or death as a result of electric shock burns and or fire Do not adjust any components inside humidifier control panel without consulting the factory Installation of humidifier in high humidity or salt water atmospheres w...

Страница 3: ...V 240V 480V 600V No of Heaters 208V 240V 480V 600V ECDDR 5 5 Single 41 7 24 0 20 8 10 4 8 3 Triple 13 9 12 0 6 0 4 8 24 vac ECDDR 10 10 Double 41 7 20 8 16 7 Triple 27 8 24 1 12 0 9 6 24 vac ECDDR 15 15 Triple 31 3 25 0 Triple 41 7 36 1 18 1 14 4 24 vac ECDDR 20 20 Triple 41 7 33 3 Triple 24 1 19 2 24 vac ECDDR 25 25 Triple 41 7 Triple 30 1 24 1 24 vac ECDDR 35 34 Triple Triple 40 9 32 7 24 vac EC...

Страница 4: ...7 8 Ø 2 375 6 0 8 4375 21 4 15 00 38 1 2 00 5 1 1 50 3 8 Cabinet Overflow 1 2 NPT Water Inlet 3 8 NPT Electrical Inlet 1 1 8 Ø Note Dimensions are typical for all ECDDR models 6 50 16 5 Removable access plate allows reservoir to slide out for inspection and cleaning without disconnecting the steam supply piping See local codes for minimum clearance to electrical compartment The electrical access d...

Страница 5: ... locked doors for both reservoir and electrical access Easy and simple installation options Dispersion methods include Insty Pac Fast Pac Injection Tube or Blower Pack assembly for room distribution Manual reset over temperature safety switch INTAC microprocessor control system VAV dual modulating control system Float Ball Water Valve Float Ball Water Valve Immersion Heaters Removable Humidifier R...

Страница 6: ...r on the object The high limit should be mounted a minimum of 8 10 feet 244 305 cm downstream from the injection tube Installing the high limit closer than 8 feet 244 cm from the humidifier may cause erratic control Mounting Mounted from the wall The humidifier should be mounted dead level in both directions PURE Humidifier Co supplies the wall mounting bracket Bracket is mounted to wall studs fir...

Страница 7: ...ket must be mounted to wall studs or additional support must be provided in the field ECDDR cabinet is then hung on the slip fit bracket 1 4 Ø Typ 11 16 4 Typ 3 4 3 7 8 HANGER BRACKET HOLE DETAIL FRONT VIEW 21 3 8 6 4 2 EDGE OF EC HUMIDIFIER CABINET 17 RIGHT SIDE VIEW A A WALL WALL SUPPORT WELDED TO BACK OF CABINET DETAIL A A HANGER BRACKET BOLTED TO WALL WALL BRACKET WELDED TO BACK OF CABINET ...

Страница 8: ...e Injection Tube Assemblies For applications where you need a short dissipation distance Allows remote mounting of the humidifier reservoir from the duct Also allows the humidifier to be located below a wall mounted duct See page 9 for details Blower Pack for Direct Room Humidification Allows humidifier to be mounted directly on the wall within the space to be humidified See page 11 and 12 for det...

Страница 9: ...umidifier with stainless steel hose clamps by PURE Humidifier Co Galvanized steel duct plates are provided to seal the opening where the tube enters the duct H Water Seal Height Total KW 5 thru 20 21 thru 34 H 6 15 cm 8 20 cm Typical ECDDR Series Electric Humidifier 3 4 SW Condensate drain line by others Δ The water seal height may have to be increased if excessive duct static pressure exists Open...

Страница 10: ...piping with a smaller inside diameter than the reservoir outlet 6 Failure to follow the piping recommendation on this page may result in blown water seals leaking cover gasket or dispersion tubes spitting 7 Install a Drain Tee at any low spots in supply piping run where condensate will accumulate All horizontal to vertical up transitions require a water sealed drip leg 8 Reference job specific tub...

Страница 11: ...ng Water Supply Piping Supply pressure 35 50 psi This style humidifier utilizes a float operated fill valve system which is designed for use with deionized demineralized or reverse osmosis water Use of mineralized tap water will cause fill valve failure and will void the humidifier warranty Install stainless pipe on makeup water line within 5 feet of humidifier fill valve connection If plastic pip...

Страница 12: ...n the room and the capacity of the humidifier If this visible steam comes in contact with any solid object walls beams machinery etc it may form condensate and drip Refer to Fig 3 and Table 4 Table 4 is located on page 12 for data on visible steam travel This will aid you in planning the location of the Blower Pack Remote Mounting The Blower Pack may be remote mounted up to ten feet away from the ...

Страница 13: ...e ft 1 2 3 4 5 5 8 Throw ft 8 10 13 16 18 23 Rise ft 2 3 4 5 6 8 60 RH Throw ft 13 14 16 18 20 25 Throw is the horizontal distance the visible steam travels from the steam discharge Rise is the vertical distance the visible steam travels from the steam discharge Objects in the direct line of the visible steam or objects that are cooler than the ambient temperature may accumulate condensation Note ...

Страница 14: ...uct RH high limit should be installed at least 10 feet downstream from the humidifier tube s Any other control sensors should be at least 10 feet downstream from the humidifier tube s Smoke detectors should not be installed downstream of the humidifier tube s If a smoke detector absolutely has to be installed downstream from the humidifier tubes then it should be installed as far from the tubes as...

Страница 15: ...ached this indicates the low water safety circuit is operational This should only take a couple of minutes maximum ______ 12 Close the drain valve and open the water supply allow the humidifier to fill to the proper level ______ 13 Check operation of optional field installed safety switches airflow proving switch high limit humidistat etc to make sure that they turn the power off to the control ci...

Страница 16: ...ure all the optional safety switches are satisfied airflow proving switch high limit humidistat etc _____ 11 Turn menu 101 RH Setpoint up to a call for humidity If a Building Automation System is controlling the humidifier have it call for 100 demand For Building Automation System verify 0 and 100 demands are displayed as 0 and 100 on the INTAC display and adjust the input high and low values to m...

Страница 17: ...eservoir If excessive mineral buildup is found the cover may need to be removed to facilitate complete cleaning of the humidifier Inspect for cracks or leaks It is normal for the hose to become hard and develop a set Maintenance Cleaning Instructions Cleaning Instructions All humidifier tanks should be cleaned manually from the reservoir cover Turn off the water supply disconnect controls by unplu...

Страница 18: ...and seal the ends together with a small amount of silicone Figure B Installation Fit the gasket around the entire lip of the tank opening Cut the gasket 1 8 longer than required this will ensure proper fit when the cover is clamped back on Slide the gasket onto lip of tank around the entire perimeter Notch only the bottom flap of the gasket reference Fig C in the corners of the tank Seal the ends ...

Страница 19: ...ck and replace Check transformer output and verify voltage Verify that all safety controls are completing the safety circuit The level control circuit has interference or is damaged Mineral on low water float switch may be preventing the switch from opening on low water condition Consult factory if you are unsure of the source of the problem Verify voltage to and from humidity sensor Check and ver...

Страница 20: ...e stripper Wire crimper Pipe Wrench Tool Requirements Torque List Torque List Cover Bolts 18 inch pounds MAX Hose Cuff Screws 35 40 inch pounds MAX when hot Heater Nut 18 20 foot pounds Heater Electrical Terminal 35 inch pounds Use a pliers to hold heater sheath from twisting Cover Heater Fiber Gasket Heater Nut Electrical Terminal Nuts Metal Washer Heating Element Sheath Isolator Heater Assembly ...

Страница 21: ...20 Maintenance Notes Maintenance Notes Maintenance Performed Date By ...

Страница 22: ...21 ...

Страница 23: ...9 Door Lock and Keys 12001 1 20 Heater Contactor A 1 21 Pilot Relay 12022 A 22 Relay Socket 12020 A 23 Fuse Block A 1 24 Heater Fuses A 3 25 Step Down Transformer A 1 26 Fuse Holder A 1 27 Fuses A 2 28 Control Board A 1 29 Wiring Harness A A 30 Wiring Harness 18027 1 31 14 Point Terminal Strip 12044 1 32 SCR Relay A A 33 SCR Heat Sink A A 34 Secondary Fuse A A 35 Power Supply Cover 18008 1 Optiona...

Страница 24: ...products The Seller reserves the right to make reasonable changes in products specifications and performance of any kind without notice or liability The Seller also reserves the right to deliver revised designs or models of products against any order unless this right is specifically waived in writing by the Seller The Seller shall have no responsibility whatsoever with respect to changes made by ...

Отзывы: