PULSAR MEASUREMENT
105
P305 Input Filter
This parameter is used to ignore spurious changes of state on the digital
inputs and determines the time that a change of state has to be present
before it is recognised as a valid input.
Enter the required time in seconds.
P306 Override Level
This parameter will determine which pumps setpoints will be overridden
when Digital Input
Function P373, 376, 379, 382, 385, 388, 391 = 3
(Override “ON”).
Only pumps with,
normal “ON”,
setpoints
below
the
Override Level
will be activated when an
Override “ON”
condition exists
and that the
Override Delay (P302)
and
Min Override (P303)
, where
required, have been satisfied.
Enter the required level in
Measurement Units
(
P104
).
Digital Input
The following parameters are used to configure the use of the digital inputs.
P372, 375, 378, 381, 384, 387, 390 Type
Determines the way digital inputs will be recognised by the Zenith.
OPTIONS
DESCRIPTION
1 = Input N.C.
(Default Input 1 to 6)
Zenith recognises a
closed
condition, D.C.
signal
voltage
present
at the
input
, as a healthy/run
condition.
2 = Input N.O.
(Default Input 7)
Zenith recognises an
open
condition, D.C.
signal
voltage
not present
at the input, as a healthy/run
condition.
Содержание Zenith 140
Страница 1: ...Zenith 140 Instruction Manual ...
Страница 2: ...2 ...
Страница 14: ...ZENITH 140 INSTRUCTION MANUAL 14 EU Certificate of Conformity ...
Страница 17: ...PULSAR MEASUREMENT 17 Dimensions Fascia Mount The dimensions of the wall fixing holes are as shown below ...
Страница 19: ...PULSAR MEASUREMENT 19 Terminal connection details Fascia Mount The terminal details are as illustrated below ...
Страница 160: ...ZENITH 140 INSTRUCTION MANUAL 160 NOTES ...